Plan Review Details - Permit 00011001
Plan Review Stops For Permit 00011001
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By dpalmer Date 2000-08-02 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2000-08-02 Time 15:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 18:44 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 18:44 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO*****************
  
 1)NOTE: PLEASE REVISE RISER DIAGRAM.
 CLARIFY RISER? YOU SHOW 2P 250 GOING TO
 250 MLO PANEL WITH 1/0 AS CONDUCTORS.
 AS PER 310-16,,,,1/0 IS ONLY RATED FOR
 150AMPS.
 ALSO PLEASE CHECK LOAD CALCULATIONS.
 BATH CIRCUTCAN BE FIGURED UNDER LIGHT-
 -ING LOAD. DOES NOT NEED FIGURED SEPAR-
 ATE. PLEASE CHECK HEATING UNDER OPTIONAL
 METHOD IN THE NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-13 Cont ID  
Sent By jleech Date 2000-03-13 Time 15:58 Rev Time 0.50
Received By jleech Date 2000-03-13 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-02-05 Cont ID  
Sent By jleech Date 2000-02-05 Time 08:15 Rev Time 0.35
Received By jleech Date 2000-02-05 Time 08:15 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.A/C FLOOR PLAN DOES NOT MATCH FLOOR
 PLAN OF HOUSE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-06-16 Cont ID  
Sent By tlarge Date 2000-06-16 Time 06:41 Rev Time 0.25
Received By tlarge Date 2000-06-16 Time 06:41 Sent To  
Notes
2001-01-08 00:00:00RISER SHALL BE SIGNED AND SEALED PER FLA
 STATUTE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-27 Cont ID  
Sent By tlarge Date 2000-01-27 Time 19:35 Rev Time 0.33
Received By tlarge Date 2000-01-27 Time 19:35 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-18 Cont ID  
Sent By fknapp Date 2000-03-18 Time 13:36 Rev Time 2.00
Received By fknapp Date 2000-03-18 Time 13:36 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO NOTES WITH R STOP1

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-14 Cont ID  
Sent By fknapp Date 2000-03-14 Time 16:42 Rev Time 4.00
Received By fknapp Date 2000-03-14 Time 13:40 Sent To  
Notes
2001-01-08 00:00:00 
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE SAFETY GLASS AS REQUIRED.
  
 2)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE PRODUCT APPROVALS FOR 1 HOUR
 RATED GLASS BLOCK.
  
 3)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR ALL
 OUTSWING DOORS & 8-0 GARAGE DOOR OPT.
  
  
  
  
 5)PROVIDE INSTALLATION SCHEDULE FOR
 STORM PANELS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-26 Cont ID  
Sent By gjoyce Date 2000-01-26 Time 09:26 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***