Plan Review Details - Permit 00011000
Plan Review Stops For Permit 00011000
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By dpalmer Date 2000-08-02 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2000-08-02 Time 15:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 19:25 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 19:25 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO*****************
  
 1)NOTE:PLEASE REVISE RISER DIAGRAM.
 YOU SHOW 250 AMP 2 POLE GOING TO A 250A
 MLO PANEL WITH 1/0 WIRE. AS PER 310-16
 1/0 IS NOT RATED FOR 250AMPS.
 ALSO PLEASE CHECK LOAD CALCUALTION FOR
 CODE COMPLIANCE. AN OPTIONAL METHOD
 CALCULATION CAN BE USED FOR HEAT.
 BATH CIRCUT DOES NOT NEED TO BE FIGURED
 SEPARATE. CAN BE FIG. AS LIGHTING LOAD.
  
 PLEASE CLARIFY MAIN PANEL/DISCONNECT.
  
 2)NOTE:MISSING OUTLET IN BEDROOM #3
  
 PLEASE SUBMIT NEW RISER DIAGRAM FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By jleech Date 2000-02-05 Time 09:19 Rev Time 0.50
Received By jleech Date 2000-02-05 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-27 Cont ID  
Sent By tlarge Date 2000-01-27 Time 19:33 Rev Time 0.33
Received By tlarge Date 2000-01-27 Time 19:33 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-04-03 Cont ID  
Sent By fknapp Date 2000-04-03 Time 12:42 Rev Time 2.00
Received By fknapp Date 2000-04-03 Time 12:41 Sent To  
Notes
2001-01-08 00:00:00 
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE SAFETY GLASS AS REQUIRED.
  
 2)PROVIDE SPECIFICATIONS FOR 1 HR RATED
 GLASS BLOCK.
  
 3)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR DOUBLE
 OUTSWING ENTRY DOORS AND SINGLE OUTSWING
 FRENCH DOOR COMPLETE WITH DRAWINGS.
  
 4)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR ROOF COVERING UNDER
 SEPERATE PERMIT.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-15 Cont ID  
Sent By fknapp Date 2000-03-15 Time 13:23 Rev Time 4.00
Received By fknapp Date 2000-03-15 Time 09:43 Sent To  
Notes
2001-01-08 00:00:00 
 *****************DENIED*****************
  
 SBC 104.2.2
  
 1)PROVIDE SAFETY GLASS AS REQUIRED.
  
 2)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR 1 HOUR
 RATED GLASS BLOCK.
  
 3)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR ALL
 OUTSWING DOORS & 8-0 GARAGE DOOR OPT.
  
 4)PROVIDE OWNER/AGENT SIGNATURE ON
 ENERGY CALCULATIONS.
  
 5)PROVIDE INSTALLATION SCHEDULE FOR
 STORM PANELS.
  
 6)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-26 Cont ID  
Sent By gjoyce Date 2000-01-26 Time 08:53 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***