Plan Review Details - Permit 00010990
Plan Review Stops For Permit 00010990
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-03-14 Cont ID  
Sent By bstaples Date 2000-03-14 Time 13:06 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00AS PER H. PIKURA 3/10/00

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-03-01 Cont ID  
Sent By hpiskura Date 2000-03-01 Time 15:36 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-05-10 Cont ID  
Sent By dpalmer Date 2000-05-10 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2000-05-10 Time 18:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-14 Cont ID  
Sent By dpalmer Date 2000-03-14 Time 12:48 Rev Time 0.00
Received By dpalmer Date 2000-03-14 Time 12:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-09 Cont ID  
Sent By dpalmer Date 2000-02-09 Time 14:11 Rev Time 0.00
Received By dpalmer Date 2000-02-09 Time 14:11 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: DISCONNECT IS REQ`D INLINE AND
 INSIDE THE BLDG. REQ`D BY 225-8 OF THE
 NEC.
  
 PLEASE SUBMIT THE PLANS WITH THE MADE
 CORRECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-25 Cont ID  
Sent By rturnque Date 2000-01-25 Time 15:47 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-05-31 Cont ID  
Sent By cthirben Date 2000-05-31 Time 10:20 Rev Time 1.00
Received By cthirben Date 2000-05-31 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-14 Cont ID  
Sent By cthirben Date 2000-03-14 Time 12:29 Rev Time 1.00
Received By cthirben Date 2000-03-14 Time 12:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-01-31 Cont ID  
Sent By ndenmark Date 2000-01-31 Time 15:31 Rev Time 1.00
Received By ndenmark Date 2000-01-31 Time 15:31 Sent To  
Notes
2001-01-08 00:00:00***********DENIED***********************
 1)PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2)PROVIDE DETAIL ON FAN SHUT DOWN BY
 DUCT SMOKE DETECTORS, AS REQUIRED BY
 1997 SMC 406 AND NFPA 90A
 3) ROOFTOP EQUIPMENT STANDS TO HAVE MIN.
 18" CLEARANCE FROM ROOF SURFACE TO
 BOTTOM OF SUPPORT STRUCTURE OF STAND
 PER LOCAL AMENDMENTS

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-02-04 Cont ID  
Sent By tlarge Date 2000-02-04 Time 17:01 Rev Time 0.75
Received By pschmitz Date 2000-02-04 Time 17:01 Sent To  
Notes
2001-01-08 00:00:00********************PROVISO*************
 RELIEF OUTLET WASTE SHALL DISCHARGE TO
 EXTERIOR PER COUNTYWIDE AMENDMENTS TO
 SPC 507.6.(3).
  
 JOB SPEC.15400-7- 2.07(5)-CLEANOUTS
 SHALL COMPLY W/SPC SEC.710.2.4.FOR
 SPACING REQS.
  
 JOB SPEC.15400-9- 2.13-SUPPORTS FOR
 HORIZONTAL COPPER SHALL COMPLY W/SPC
 SEC.310.3.4.