| 2001-01-08 00:00:00 | *************** PROVISO *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT THE LOAD CALCU- |
| | -LATION SHOWING ALL THE APPLIANCES. |
| | |
| | 2)NOTE: SUBMIT THE PANEL SCHEDULES FOR |
| | BOTH PANELS; HOUSE AND GARAGE. |
| | |
| | 3)NOTE:SUBMIT NEW GARAGE RISER TO SHOW |
| | WIRE SIZES,CONDUITS, UNDER/OVER SERVICE |
| | ENTRANCE. SHOW GROUNDING ELECTRODE |
| | SYSTEM; TO INCLUDE BLDG.STEEL,GROUND ROD |
| | AND COLD WATER PIPE IF ANY IN GARAGE. |
| | |
| | 4)NOTE: IF EXISTING PANEL IS BEING MOVED |
| | INSIDE THEN PLEASE INDICATE WEATHER OR |
| | NOT THE EXISTING WIRE ETC. IS STAYING |
| | THE SAME?WHAT SIZE & TYPE? ALSO PLESE |
| | SHOW THE EXISTIG GROUNDING SYSTEM. |
| | |
| | 5)NOTE:AS REQ`D BY NFPA-72 2-2.1.1.1 |
| | SMOKE DETECTORS ARE REQ`D INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOMS. OVER 50% |
| | OF THE ELELCTRICAL WORK IS BEING DONE |
| | ALL ELECTRICAL MUST BE BROUGHT UP TO |
| | NEC AND ANY APP.LOCAL CODES. |
| | |
| | 6)NOTE: PLEASE INDICATE ALL OUTLETS |
| | SERVIGN KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECTED. AS REQ`D BY ART;210-8-A-6 |
| | OF THE NEC. |
| | |
| | PLEASE ALSO NOTE THE TYPE OF LIGHT FIX- |
| | -TURE AND CLEARENCES REQ`D BY 410-8 |
| | IN THE MASTER BEDROOMS CLOSETS. |
| | |
| | PLEASE HAVE ALL THE ABOVE INFORMATION |
| | SUBMITTED FOR REVIEW AND APPROVAL BEFORE |
| | THE FIRST ROUGH ELECTRICAL INSPECTION |
| | IS CALLED IN. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8372 |