Plan Review Details - Permit 00010891
Plan Review Stops For Permit 00010891
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-21 Cont ID  
Sent By dpalmer Date 2000-09-21 Time 15:17 Rev Time 0.00
Received By dpalmer Date 2000-09-21 Time 15:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-22 Cont ID  
Sent By dpalmer Date 2000-01-22 Time 10:51 Rev Time 0.00
Received By dpalmer Date 2000-01-22 Time 10:51 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: PLEASE SUBMIT THE LOAD CALCU-
 -LATION SHOWING ALL THE APPLIANCES.
  
 2)NOTE: SUBMIT THE PANEL SCHEDULES FOR
 BOTH PANELS; HOUSE AND GARAGE.
  
 3)NOTE:SUBMIT NEW GARAGE RISER TO SHOW
 WIRE SIZES,CONDUITS, UNDER/OVER SERVICE
 ENTRANCE. SHOW GROUNDING ELECTRODE
 SYSTEM; TO INCLUDE BLDG.STEEL,GROUND ROD
 AND COLD WATER PIPE IF ANY IN GARAGE.
  
 4)NOTE: IF EXISTING PANEL IS BEING MOVED
 INSIDE THEN PLEASE INDICATE WEATHER OR
 NOT THE EXISTING WIRE ETC. IS STAYING
 THE SAME?WHAT SIZE & TYPE? ALSO PLESE
 SHOW THE EXISTIG GROUNDING SYSTEM.
  
 5)NOTE:AS REQ`D BY NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. OVER 50%
 OF THE ELELCTRICAL WORK IS BEING DONE
 ALL ELECTRICAL MUST BE BROUGHT UP TO
 NEC AND ANY APP.LOCAL CODES.
  
 6)NOTE: PLEASE INDICATE ALL OUTLETS
 SERVIGN KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. AS REQ`D BY ART;210-8-A-6
 OF THE NEC.
  
 PLEASE ALSO NOTE THE TYPE OF LIGHT FIX-
 -TURE AND CLEARENCES REQ`D BY 410-8
 IN THE MASTER BEDROOMS CLOSETS.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 THE FIRST ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-21 Cont ID  
Sent By tlarge Date 2000-01-21 Time 07:34 Rev Time 0.65
Received By tlarge Date 2000-01-21 Time 07:34 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-17 Cont ID  
Sent By fknapp Date 2000-03-17 Time 12:15 Rev Time 2.00
Received By fknapp Date 2000-03-17 Time 12:15 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************PROVISO****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR NEW
 EXTERIOR DOORS,WINDOWS TO BE USED AND
 GARAGE DOORS.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION.
  
 2)PROVIDE MECHANICAL DRAWINGS AND
 MANUEL J WITH MECHANICAL PERMIT
 APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-04 Cont ID  
Sent By fknapp Date 2000-03-04 Time 13:50 Rev Time 4.00
Received By fknapp Date 2000-03-04 Time 11:58 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************DENIED*****************
  
 SBC 104.2.2
  
 1)PROVIDE PLANS WITH COMPLETE DEMOLITION
 DETAILS AND COMPLETE ELEVATIONS.
  
 2)PROVIDE 2 CURRENT SURVEYS,SIGN,SEALED
 AND DATED, LESS THAN ONE YEAR OLD.
  
 3)PROVIDE 2 CURRENT,COMPLETE SBCCI OR
 METRO-DADE PRODUCT APPROVALS FOR ROOF
 COVERING AND ALL EXTERIOR DOORS AND
 WINDOWS TO BE USED.
  
 4)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN FOR STORM PANELS WITH SPECIFIC
 ANCHORS TO BE USED.
  
 5)PROVIDE ENERGY CALCULATIONS.
  
 6)PROVIDE ROOF FRAMING PLAN.
  
 7)PROVIDE SPECIFIC WINDOW AND DOOR BUCK
 CONNECTION DETAILS FOR WINDLOAD SBC1606
  
 8)PROVIDE COMPLETE DIMENSIONS AND BEAM
 HEIGHTS ON ALL ELEVATIONS.
  
 9)PROVIDE COMPLETE STAIR SECTIONS WITH
 TREAD,RISER,HANDRAIL,GUARDRAIL
 DIMENSIONS.
  
 10)PROVIDE MECHANICAL DRAWINGS AND
 MANUEL J WITH MECHANICAL PERMIT
 APPLICATION.
  
 11)PROVIDE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-23 Cont ID  
Sent By gjoyce Date 2000-02-23 Time 16:45 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***