Plan Review Details - Permit 00010492
Plan Review Stops For Permit 00010492
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-03 Cont ID  
Sent By lmartine Date 2000-03-03 Time 07:16 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00"PROVISO"
 DOORS #105,#111 MUST COMPLY W/4.13.6
 1997 F.A.C.
 COMPLETE DOOR SCHEDULE
 SUBMIT ENERGY CALCULATIONS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-07-17 Cont ID  
Sent By dpalmer Date 2000-07-17 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2000-07-17 Time 18:47 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
  
 1)NOTE: PLEASE TAKE CARE OF THE ORIGINAL
 NOTES GIVEN AS A PROVISO.
 SEE NOTES ATTACHED FROM FIRST REVIEW.
  
 PLEASE SUBMIT FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-15 Cont ID  
Sent By dpalmer Date 2000-01-15 Time 15:58 Rev Time 0.00
Received By dpalmer Date 2000-01-15 Time 15:58 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE: PLEASE SHOW LOAD CALCULATIONS
 ON ALL NEW PANELS.NOTE ALL CONTINUOUS
 LOADS TO BE FIGURED AT 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-12 Cont ID  
Sent By rturnque Date 2000-01-12 Time 10:11 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-28 Cont ID  
Sent By ndenmark Date 2000-01-28 Time 14:08 Rev Time 0.50
Received By ndenmark Date 2000-01-28 Time 14:08 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 MAINTAIN 10' SEPARATION BETWEEN OUTSIDE
 AIR INTAKE AND EXHAUST AIR INLET
 AREAS WITH 300 CFM OF GREATER TO HAVE
 RETURN FROM AREA

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-05-06 Cont ID  
Sent By tlarge Date 2000-05-06 Time 07:37 Rev Time 0.75
Received By tlarge Date 2000-05-06 Time 07:37 Sent To  
Notes
2001-01-08 00:00:00CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC SEC.914.1.
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS SEC.911.1.1.
  
 SANITARY RISER DIAGRAM ON P4.1 DOESN'T
 MATCH SANITARY PLAN ON P2.1.CLARIFY.
  
 SINK IN CONFERENCE ROOM NOT SHOWN ON
 WATER OR SANITARY RISERS.CLARIFY.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-02-26 Cont ID  
Sent By tlarge Date 2000-02-26 Time 10:00 Rev Time 0.65
Received By tlarge Date 2000-02-26 Time 10:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-02-20 Cont ID  
Sent By tlarge Date 2000-02-20 Time 08:10 Rev Time 1.00
Received By tlarge Date 2000-02-20 Time 08:10 Sent To  
Notes
2001-01-08 00:00:00AN ADDITIONAL STALL IN THE WOMEN'S REST-
 ROOM SHALL COMPLY W/FACBC SEC.4.22.4,
 FIGURE 30(D) AND SEC.4.26.WATER CLOSETS
 IN SUCH STALLS SHALL COMPLY W/FACBC SEC.
 4.16.
  
 NO MORE THAN 2 FIXTURES SHALL BE
 CONNECTED TO 1/2" COLD WATER LINE PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.607.7.
 (SEE URINALS AND FIXTURES IN BREAKROOM.
  
 WATER RISER SHOWS 1/2" COLD WATER LINE
 SUPPLYING 3/4" LINE TO URINALS.COMPLY W/
 SPC TABLE 607.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-01 Cont ID  
Sent By tlarge Date 2000-02-01 Time 10:20 Rev Time 0.00
Received By tlarge Date 2000-02-01 Time 10:20 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SQ.FOOTAGE OF STRUCTURE AND
 OCCUPANT LOAD TO ENSURE COMPLIANCEW/
 TABLE 407 OF SPC.
  
 BREAKROOM SINK SHALL BE HANDICAP ACCESS-
 IBLE PER FACBC SEC.4.24.1-4.24.7.
  
 WALLS AND FLOORS IN TOILET ROOMS SHALL
 BE NON-ABSORBENT TO A HEIGHT OF 4" PER
 SBC SEC.1204.2.
  
 HEIGHT OF H.C.WATER CLOSET SHALL COMPLY
 W/FACBC SEC.4.16.3.(17"-19").
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER FACBC SEC.501.7.SUPPLY PERMANENT
 LADDER OR RELOCATE EWH TO FLOOR.
  
 SHT.PO.1-"M" COPPER NOT PERMITTED U/G
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 611.3.
  
 NO MORE THAN 2 FIXTURES SHALL BE
 CONNECTED TO 1/2" C.W.LINE PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.607.7.
  
 WATER RISER SHOWS 1/2" LINE SUPPLYING
 3/4" TO URINALS.SPC TABLE 607.
  
 CONNECTION OF CONDENSATE DRAINS TO STORM
 DRAINAGE SYSTEM SHALL BE BY INDIRECT
 CONNECTIONS PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.804.3.