Plan Review Details - Permit 00010485
Plan Review Stops For Permit 00010485
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 18:03 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 18:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-01-22 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2000-01-22 Time 12:57 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: NEED TO SUBMIT A NEW REVISED
 RISER DIAGRAM?? YOU SHOW TWO PANELS BUT
 ON RISER ONLY SHOWS ONE. ALSO LOAD
 EXCEEDS THE 200 AMP RATING OF RISER
 EQUIPMENT.
  
 2)NOTE: MISSING OUTLET PER 210-52
  
 3)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS OF NEW
 DWELLINGS. REQ`D BY 1993/1996 NFPA-72
 2-2.1.1.1.
  
 4)NOTE; AS REQ`D BY ARTS;210-52/215-5
 NEED TO HAVE DEDICATED BATH(S) CIRCUT(S)
 LISTED ON PANEL SCHEDULE AS 20 AMP
 # 12 AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REIVEW AND APPROVAL.IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT;
 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-18 Cont ID  
Sent By jleech Date 2000-01-18 Time 14:59 Rev Time 0.50
Received By jleech Date 2000-01-18 Time 14:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-15 Cont ID  
Sent By tlarge Date 2000-01-15 Time 05:49 Rev Time 0.50
Received By tlarge Date 2000-01-15 Time 05:49 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-02-23 Cont ID  
Sent By fknapp Date 2000-02-22 Time 15:08 Rev Time 4.00
Received By fknapp Date 2000-02-22 Time 14:55 Sent To  
Notes
2001-01-08 00:00:00 
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRODADE PRODUCT APPROVALS FOR:
 STEEL ENTRY DOOR
 SLIDING GLASS DOORS
  
 2)PROVIDE MISSILE IMPACT PROTECTION
 INFORMATION UNDER SEPERATE PERMIT.
  
 3)ROOFING UNDER SEPERATE PERMIT.
  
 4)PROVIDE GARAGE DOORS THAT MEET OR
 EXCEED DESIGN PRESSURES ON PLANS.
  
 5)PROVIDE TRUSS LAYOUT PLAN THAT HAS
 BEEN REVIEWED AND APPROVED BY DESIGNER
 OF RECORD.
  
 6)PROVIDE TRUSS ENGINEERING SHEETS WITH
 ORIGINAL SIGNATURE OF ENGINEER ON EACH
 SHEET OR TRUSS DESIGN CERTIFICATION WITH
 RAISED SEAL AND SIGNATURE.
  
 7)PROVIDE BUTT GLASS ENGINEERING PRIOR
 TO INSTALLATION.
  
 8)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR FIX GLASS OVER 60".

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-13 Cont ID  
Sent By gjoyce Date 2000-01-13 Time 13:15 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***