Plan Review Details - Permit 00010411
Plan Review Stops For Permit 00010411
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-02-18 Cont ID  
Sent By hpiskura Date 2000-02-18 Time 14:32 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-01-27 Cont ID  
Sent By jleahy Date 2000-01-27 Time 12:46 Rev Time 0.45
Received By jleahy Date 2000-01-27 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2000-01-15 Cont ID  
Sent By dpalmer Date 2000-01-15 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2000-01-15 Time 14:50 Sent To  
Notes
2001-01-08 00:00:00************ NO REVIEW ****************
  
 1)NO ELECTRICAL PLANS SUBMITTED FOR
 REVIEW.
 SUBMIT ELETRICAL PLANS WITH PERMIT
 APPLICATION WHICH WILL BE REQ`D FOR
 ELECTRICAL WORK TO BE DONE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-12 Cont ID  
Sent By rturnque Date 2000-01-12 Time 09:57 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-28 Cont ID  
Sent By ndenmark Date 2000-01-28 Time 13:19 Rev Time 0.50
Received By ndenmark Date 2000-01-28 Time 13:19 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 SHOWER ROOM 8123 REQUIRES EXHAUST FROM
 ROOM

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-01 Cont ID  
Sent By tlarge Date 2000-02-01 Time 06:24 Rev Time 1.50
Received By tlarge Date 2000-02-01 Time 06:24 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SQ.FOOTAGE OF TENANT SPACE FOR
 OCCUPANT LOAD TO ENSURE COMPLIANCE W/SPC
 TABLE 407 FOR MINIMUM FIXTURE REQS.
  
 LOUNGE SINK SHALL COMPLY W/FACBC SECS.
 4.24.1-4.24.7.
  
 A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407 AND SHALL COMPLY W/FACBC SEC.
 4.1.3(10)(A),4.15.1-4.15.5.
  
 WIDTH OF HANDICAP TOILET STALLS SHALL
 COMPLY W/FACBC SEC.4.17.3(EXCEPTION:NEW
 CONSTRUCTION.)
  
 MAX.HEIGHT OF URINAL SHALL BE 17" PER
 FACBC SEC.4.18.1-4.18.4.
  
 ALL TOILET ROOMS IN HEALTH CARE
 FACILITIES SHALL HAVE FLOOR DRAINS PER
 SPC 409.4.1.1(EXCEPTION)
  
 FLOORS AND WALLS IN TOILET ROOMS SHALL
 BE IMPERVIOUS TO A HEIGHT OF 4' PER SBC
 SEC.1204.2.
  
 SHOWER IN MASSAGE ROOM SHALL BE HANDICAP
 ACCESSIBLE PER FACBC SEC.4.1.3.(11),
 4.23.8.
  
 SUBMIT A WATER RISER DIAGRAM FOR REVIEW
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 SHOWER VALVES SHALL COMPLY W/SPC SEC.
 613.1/TABLE 613.

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***