Plan Review Details - Permit 00010370
| Plan Review Stops For Permit 00010370 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-04-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-04-21 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-02-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-02-01 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-01-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-01-15 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-01-15 |
Time |
17:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-01-12 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-01-12 |
Time |
09:36 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-02-11 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-02-11 |
Time |
07:08 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-02-11 |
Time |
07:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION SHOWS CORRECTIONS TO 1ST REVIEW | | | COMMENTS | | | SEPARATE PERMIT REQUIRED FOR MED GAS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-01-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-01-28 |
Time |
13:40 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-01-28 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1) TIE NEW A/C UNIT TO BUILDING FIRE | | | ALARM WITH DUCT SMOKE DETECTOR | | | 2) MEDICAL GAS REQUIRES MECHANICAL PER- | | | MIT. PROVIDE DETAILS AND SPECS WITH PLAN | | | FOR REVIEW AT TIME OF MECHANICAL PERMIT | | | APPLICATION, INCLUDE EQUIPMENT LOCATION | | | AND EXHAUST TERMINATION FOR VACUUM AND | | | SOURCE OF AIR FOR COMPRESSED AIR UNIT. | | | INSTALLATION TO COMPLY WITH NFPA 99C |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-04-25 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-04-25 |
Time |
14:42 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-03-07 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-07 |
Time |
07:21 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
2000-03-07 |
Time |
07:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-02-09 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-02-09 |
Time |
15:17 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-01-31 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-01-31 |
Time |
15:52 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-02-01 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW# 102 | | | DENIED | | | (1) SHT-2 BOTTLED WATER DISPENSER NOT | | | PERMITED IN LEIU OF DRINKING FOUNTAIN, | | | ALSO TO COMPLY WITH ADA ACCESSIBLE | | | FACBC 4.1.3 (10)(A), SPC TAB 407. | | | (2) FLOOR DRAINS REQUIRED WITH TRAP | | | PRIMERS IN REST RMS SEC 409.4 EXCEPTION. | | | (3)INFORMATION ON WASTE FROM PROCESSOR | | | FOR PH LEVEL. | | | (4) ALL EQUIPMENT CONNECTED TO THE WATER | | | SULLLY TO BE PROTECTED WITH A APPROVED | | | BACK FLOW PREVENTER. | | | (5) BREAK ROOM SINK TO BE ADA ACCESSIBLE | | | 34" HIGH COUNTER TOP. 4.24 TO4.24.7 | | | FACBCEND OF COMMENTS |
|
|
|