Plan Review Details - Permit 00010370
Plan Review Stops For Permit 00010370
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-04-21 Cont ID  
Sent By lmartine Date 2000-04-21 Time 14:15 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-02-01 Cont ID  
Sent By lmartine Date 2000-02-01 Time 11:05 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-15 Cont ID  
Sent By dpalmer Date 2000-01-15 Time 17:10 Rev Time 0.00
Received By dpalmer Date 2000-01-15 Time 17:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-12 Cont ID  
Sent By rturnque Date 2000-01-12 Time 09:36 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-02-11 Cont ID  
Sent By ndenmark Date 2000-02-11 Time 07:08 Rev Time 1.00
Received By ndenmark Date 2000-02-11 Time 07:08 Sent To  
Notes
2001-01-08 00:00:00REVISION SHOWS CORRECTIONS TO 1ST REVIEW
 COMMENTS
 SEPARATE PERMIT REQUIRED FOR MED GAS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-28 Cont ID  
Sent By ndenmark Date 2000-01-28 Time 13:40 Rev Time 0.50
Received By ndenmark Date 2000-01-28 Time 13:40 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1) TIE NEW A/C UNIT TO BUILDING FIRE
 ALARM WITH DUCT SMOKE DETECTOR
 2) MEDICAL GAS REQUIRES MECHANICAL PER-
 MIT. PROVIDE DETAILS AND SPECS WITH PLAN
 FOR REVIEW AT TIME OF MECHANICAL PERMIT
 APPLICATION, INCLUDE EQUIPMENT LOCATION
 AND EXHAUST TERMINATION FOR VACUUM AND
 SOURCE OF AIR FOR COMPRESSED AIR UNIT.
 INSTALLATION TO COMPLY WITH NFPA 99C

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-04-25 Cont ID  
Sent By pschmitz Date 2000-04-25 Time 14:42 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-03-07 Cont ID  
Sent By tlarge Date 2000-03-07 Time 07:21 Rev Time 0.75
Received By tlarge Date 2000-03-07 Time 07:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-09 Cont ID  
Sent By pschmitz Date 2000-02-09 Time 15:17 Rev Time 0.75
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00N

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-31 Cont ID  
Sent By pschmitz Date 2000-01-31 Time 15:52 Rev Time 1.00
Received By tlarge Date 2000-02-01 Time 08:05 Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW# 102
 DENIED
 (1) SHT-2 BOTTLED WATER DISPENSER NOT
 PERMITED IN LEIU OF DRINKING FOUNTAIN,
 ALSO TO COMPLY WITH ADA ACCESSIBLE
 FACBC 4.1.3 (10)(A), SPC TAB 407.
 (2) FLOOR DRAINS REQUIRED WITH TRAP
 PRIMERS IN REST RMS SEC 409.4 EXCEPTION.
 (3)INFORMATION ON WASTE FROM PROCESSOR
 FOR PH LEVEL.
 (4) ALL EQUIPMENT CONNECTED TO THE WATER
 SULLLY TO BE PROTECTED WITH A APPROVED
 BACK FLOW PREVENTER.
 (5) BREAK ROOM SINK TO BE ADA ACCESSIBLE
 34" HIGH COUNTER TOP. 4.24 TO4.24.7
 FACBCEND OF COMMENTS