Plan Review Details - Permit 00010258
Plan Review Stops For Permit 00010258
Review Stop P PLUMBING
Rev No 2 Status P Date 2000-01-19 Cont ID  
Sent By tlarge Date 2000-01-19 Time 06:14 Rev Time 0.65
Received By tlarge Date 2000-01-19 Time 06:14 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 RELIEF VALVE DRAIN SHALL DISCHARGE TO
 EXTERIOR PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.507.6(3).
  
 DETAIL OF LADDER FOR EWH SHALL BE SIGNED
 AND SEALED & SUBMITTED PRIOR TO FINAL
 PLBG. INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-01-19 Cont ID  
Sent By tlarge Date 2000-01-06 Time 10:11 Rev Time 0.33
Received By tlarge Date 2000-01-06 Time 10:11 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A SIGNED AND SEALED FLOOR PLAN
 SHOWING LOCATIONS OF ALL PLBG.FIXTURES.
 (ORIGINAL PLANS DO NOT SHOW ANY PLBG.)
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.3
  
 PLANS SHALL REFLECT ENTIRE SCOPE OF PLBG
 WORK TO BE DONE.(COMPLETE WATER RISER
 REQD.)COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.(A PERMANENT LADDER
 SHALL BE INSTALLED OR RELOCATE WATER
 HEATER TO FLOOR.)