Plan Review Details - Permit 00010201
Plan Review Stops For Permit 00010201
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-06-16 Cont ID  
Sent By dpalmer Date 2000-06-16 Time 07:56 Rev Time 0.00
Received By dpalmer Date 2000-06-16 Time 07:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-20 Cont ID  
Sent By lmartine Date 2000-07-20 Time 07:46 Rev Time 0.00
Received By lmartine Date 2000-06-16 Time 15:13 Sent To  
Notes
2001-01-08 00:00:00************PROVISO************
  
 SUBMIT CORRECT TEST REPORTS FOR ROOF
 COVER AND EXTERIOR WINDOWS AND DOORS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-08 Cont ID  
Sent By dpalmer Date 2000-01-08 Time 15:27 Rev Time 0.00
Received By dpalmer Date 2000-01-08 Time 15:27 Sent To  
Notes
2001-01-08 00:00:00************UNSAT*******************
  
 1)NOTE:NEED TO SUBMIT SERVICE SIZE!!
 TO INCLUDE SIZE OF EXISTING METERCAN.
 SUBMIT COMPLETE AND TOTAL LOAD
 CALCULATIONS ON 200A MAIN PANEL.
 IF EXISTING 100 PANEL SHOWN ISCOMING FRO
 METER WITH NO MAIN THEN MAIN DISC. MUST
 BE INSTALLED. MIANS MUST BE GROUPED!!!
 SHOW HOW NEW PANEL 'C' IS BEING FED. IS
 IT COMING FROM EXISITING 200A PANEL?
 IS THERE GOING TO BE A MAIN BRKR IN
 PANEL 'A' FOR PANEL 'C'????
 GIVE COMPLETE DETAILED PANEL SCHEDULES
 FOR ALL PANELS.
 ALL MAINS MUST BE GROUPED PER 230-72!!!
 SHOW ALL EXISTING WIRE SIZES FOR SERVICE
 TO INCLUDE # OF CONDUCTORS IN EACH PIPE.
 ALL THE ABOVE FALLS UNDER THE FOLLOWING
 PROVIDE AIC RATINGS OF NEW EQUIPMENT
 BEING INSTALLED. AIC RATING IS FIGURED
 FROM FAULT CURRENT CALCULATIONS.
  
 ALL THE ABOVE ITEMS ARE FROM THE FOLLOW-
 -ING ARTS IN THE NEC,,,310-16/215-5/230-
 65/220-3-D-1/230-72
  
 2)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS IN ANY NEW CONST.
 BY CODE MORETHAN 50% OF THE ELECTRIC
 IS BEING DONE,,,SMOKE DETECTORS ARE
 GOING TO BE REQ`D IN EXISTING SLEEPING
 ROOMS.
  
 3)NOTE: PLEASE LIST DEDICATED BATH(S)
 CIRCUT(S) WHICH ARE REQ`D BY 210-52D.
 THEY ARE TO BE 20AMP AND #12 AWG.
 SHOW FOR NEW BATH IN ADDITION.
  
 )NOTE:SEEING THAT MORETHAN 50% OF ELEC.
 IS BEING DONE. THEN FIELD INSPECTOR
 MAY REQ OTHER ELECTRICAL ITEMS TO BE
 BROUGHT UP TO CODE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL!!!!ALL THE ABOVE
 ITEMS NEED TO BE ADDRESED.IF THERE ARE
 ANY QUESTIONS THEN PLEASE CALL ME AT
 THE FOLLOWING # 659-8096 EXT.8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-06-15 Cont ID  
Sent By cthirben Date 2000-06-15 Time 12:34 Rev Time 1.00
Received By cthirben Date 2000-06-15 Time 12:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-06-15 Cont ID  
Sent By cthirben Date 2000-06-15 Time 10:05 Rev Time 1.00
Received By cthirben Date 2000-06-15 Time 10:01 Sent To  
Notes
2001-01-08 00:00:00DENIED*****************************
 1. LIST SPECIFIC A/C UNIT INFORMATION.
 2. CFM VALUE FOR EACH A/C DROP TO BE
 INDICATED ON PLANS.
 3. PROVIDE RETURN AIR FROM BATHROOM #3
 TO AIR HANDLER UNIT.
 4. REQUIRE DUCT MATERIAL INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-01-10 Cont ID  
Sent By jleech Date 2000-01-10 Time 07:53 Rev Time 0.50
Received By jleech Date 2000-01-10 Time 07:52 Sent To  
Notes
2001-01-08 00:00:00UNSAT;
 1. SIZE ALL DUCTS.
 2. INDECATE DUCT MATERIAL.
 3. AMOUNT OF CUBIC FEET PER MINUTE FOR
 EACH DROP.
 4. RETURN AIR GRILL MUST NOT BE RESRICED
 BY DOOR. SHOULD BE IN FAMILY ROOM.
 5. LIST EQUIPMENT, MODEL NUMBERS AND
 SEER EFFICIENCY.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-06-17 Cont ID  
Sent By tlarge Date 2000-06-17 Time 09:03 Rev Time 0.50
Received By tlarge Date 2000-06-17 Time 08:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-08 Cont ID  
Sent By tlarge Date 2000-01-08 Time 05:47 Rev Time 0.65
Received By tlarge Date 2000-01-08 Time 05:47 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-07-20 Cont ID  
Sent By lmartine Date 2000-07-20 Time 07:57 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00***********PROVISO***********
  
 CORRECT PRODUCT TEST REPORTS FOR ROOF
 COVER AND ALL EXTERIOR WINOWS AND DOORS
 SHALL BE SUBMITTED FOR APPROVAL BEFORE
 INSPECTIONS.
  
 L.MARTINEZ
 659-8096#8456

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-07-19 Cont ID  
Sent By lmartine Date 2000-07-19 Time 07:41 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE COMMENTS ON BACK OF APPLICATION,LM
 7/19/00

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-01-12 Cont ID  
Sent By jcaloger Date 2000-01-12 Time 08:58 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS NEEDS COUNTY IMPACT REVIEW
  
 PROVIDE ENERGY CALCULATIONS
  
 THE FRONT SETBACK WILL NOT HAVE THE
 MINIMUM REQUIRED 1000 SQUARE FOOT OF
 LANDSCAPING.
  
 PROVIDE EASEMENT CONSENT FORM FOR
 INSTALLING THE FENCE WITH GATE IN THE
 SIDE EASEMENT.
  
 THE KITCHENETTE IS NOT ALLOWED.REMOVE
 FROM THE PLAN.
  
 THE DRIVEWAY APPROACH IS REQUIRED TO BE
 6" THICK CONCRETE WITH NO REINFORCING.
 REVISE PLAN.
  
 PROVIDE PRODUCT APPROVAL FOR THE WINDOWS
 EXTERIOR DOORS, ROOFING, HURRICANE
 SHUTTERS.
  
 PROVIDE HURRICANE MISSLE IMPACT PROTECT
 AT ALL NEW GLAZED OPENINGS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-06 Cont ID  
Sent By gjoyce Date 2000-01-06 Time 11:51 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***