| Miscellaneous Information / Notes |
| INSTALL 1258SQFT OF VINYL FLOORING |
| |
| 7/24/23 FAILED FIRE CLF |
| THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L |
| FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
| COMMENTS: |
| |
| 1) THERE ARE INDICATIONS OF VINYL FLOORING BUT NO |
| SPECIFICATIONS SHEETS THAT INDICATE MEETING THE |
| REQUIREMENTS PER NFPA' |
| |
| PER NFPA 101, CHAPTER 10 SECTION 10.2.7 |
| |
| 10.2.7* INTERIOR FLOOR FINISH TESTING AND |
| CLASSIFICATION. |
| 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR |
| FINISHES SHALL |
| COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR |
| IGNITION |
| CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING |
| MATERIALS. |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR |
| WHICH 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, |
| SHALL HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED |
| IN THE CLASSES SPECIFIED |
| IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH |
| THE CRITICAL RADIANT FLUX |
| REQUIREMENTS. |
| 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
| INTERIOR FLOOR FINISH |
| SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS |
| THAN 0.45 W/CM2, AS DETERMINED |
| BY THE TEST DESCRIBED IN 10.2.7.3. |
| 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS |
| II INTERIOR FLOOR FINISH |
| SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS |
| THAN 0.22 W/CM2, BUT LESS |
| THAN 0.45 W/CM2, AS DETERMINED BY THE TEST |
| DESCRIBED IN 10.2.7.3. |
| |
| PLEASE REVIEW AND PROVIDE SPEC SHEETS. |
| |
| |
| |
| CAITLIN L FRANCIS |
| FIRE INVESTIGATOR |
| 561-804-4728 |
| [email protected] |
| |
| |
| **NEED QUALIFIER'S NOTARIZED SIGNATURE ON APP |
| PRIOR TO ISSUANCE - SIGNATURE IS NOT QUALIFIER** |
| |
| |
| 7/21/23 PLANAS UPLOADED, INCOMING COMPLETE.CD |
| 7/19/23 APPLICANT INVITED TO UPLOAD PLANS AND PAY |
| FEES. LEM |