| Miscellaneous Information / Notes |
| OUTDOOR AWNING 2751 S DIXIE HWY PINK STEAK |
| RESTAURANT |
| |
| 6/29/23 FAILED FIRE CLF |
| |
| THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L |
| FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
| COMMENTS: |
| |
| 1) THERE ARE NO SPECIFICATIONS OF THE MATERIAL OR |
| STRUCTURE OF THE CANOPY SUBMIT WITH THE SITE PLAN, |
| AND THESE MUST MEET THE FOLLOWING CODES FROM NFPA |
| 13 CHAPTER 8: |
| |
| 8.15.7* EXTERIOR PROJECTIONS. |
| 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, |
| 8.15.7.3, OR |
| 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED |
| UNDER EXTERIOR |
| PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. |
| 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE |
| OMITTED WHERE |
| THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH |
| MATERIALS THAT |
| ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE |
| RETARDANT??? |
| TREATED WOOD AS DEFINED IN NFPA 703. |
| 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE |
| OMITTED FROM BELOW |
| THE EXTERIOR PROJECTIONS OF COMBUSTIBLE |
| CONSTRUCTION, PROVIDED |
| THE EXPOSED FINISH MATERIAL ON THE EXTERIOR |
| PROJECTIONS ARE NONCOMBUSTIBLE, |
| LIMITED-COMBUSTIBLE, OR FIRE RETARDANT???TREATED |
| WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR |
| PROJECTIONS CONTAIN |
| ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE |
| FOLLOWING |
| UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES: |
| (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY |
| WITH NONCOMBUSTIBLE |
| INSULATION |
| (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE |
| NONCOMBUSTIBLE |
| OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY |
| ATTACHED |
| TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE |
| ENCLOSED |
| JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME, |
| INCLUDING |
| SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON |
| TOP OR WITHIN |
| THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED |
| ATTIC [SEE |
| 11.2.3.1.4(4)(D)] |
| (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR |
| PROJECTIONS |
| NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA |
| 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE |
| OMITTED FROM |
| EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF |
| THE CORRIDOR |
| ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR |
| IS ENTIRELY |
| OF NONCOMBUSTIBLE CONSTRUCTION. |
| 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER |
| EXTERIOR PROJECTIONS |
| GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE |
| COMBUSTIBLES |
| ARE STORED. |
| |
| CAITLIN L FRANCIS |
| FIRE INVESTIGATOR |
| WEST PALM BEACH FIRE RESCUE |
| 561.804.4728 |
| [email protected] |
| |
| |
| |
| 6/21/23 FEES PAID, PLANS UPLOADED, INCOMING |
| COMPLETE. AM |
| 6/20/23 APPLICANT INVITED TO UPLOAD PLANS AND PAY |
| FEES. AM |