| Miscellaneous Information / Notes |
| INSTALL WALK-INS PER PLANS |
| |
| |
| |
| 1/30/23 PERMIT ISSUED. LEM |
| 1/26/23 REVIEWS COMPLETE, WAITING ON FEES TO ISSUE |
| PERMIT AO |
| 1/24/23 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 1/20/23 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. LEM |
| 1/19/23 RESUB RECEIVED,INCOMING COMPLETE AO |
| 1/18/23 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. LEM |
| 1/6/23, PASS FIRE, CRW, WITH PROVISO COMMENTS |
| 1/5/23 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 12/30/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
| RESUBMIT AO |
| 12/29/22, FAIL FIRE, CRW, FIRE REVIEW COMMENTS: |
| (1) THE PLAN SUBMITTAL DID NOT INDICATE THE DOOR |
| HANDLE/LOCKING ASSEMBLY THAT WOULD NOT REQUIRE THE |
| USE OF A KEY, TOOL, OR SPECIAL KNOWLEDGE OR EFFORT |
| FOR OPERATION FROM THE EGRESS SIDE. NFPA 101, |
| 7.2.1.5 |
| (2)THE PLAN SUBMITTAL DID NOT INDICATE EMERGENCY |
| LIGHTING. NFPA 101, 7.9 |
| (3)THE PLAN SUBMITTAL DID NOT INDICATE MARKING THE |
| MEANS OF EGRESS. NFPA 101, 7.10 |
| (4)FIRE SPRINKLER COVERAGE IS ADDRESSED BY PERMIT |
| #22090774. |
| |
| |
| |
| |
| 12/28/22 FEES PAID, PLANS UPLOADED, INCOMING |
| COMPLETE. AM |
| 11/21/22 APPLICANT INVITED TO PAY FEES AND UPLOAD |
| PLANS AO |