| Miscellaneous Information / Notes |
| MASTER 22010834 FIRE SPRINKLER UNDERGROUND |
| |
| |
| |
| |
| 7/19/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
| DOWNLOAD PLANS, PERMIT CARD UPLOADED. LEM |
| 7/18/22, PASS FIRE, CRW, WITH PROVISO COMMENTS |
| 7/15/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 7/11/22 7/11/22 PLAN REVIEW COMPLETE, CUSTOMER |
| INFORMED THEY NEED TO RESUBMIT. CP |
| 7/8/22, FAIL FIRE, CRW, INDICATE ON THE PLAN THE |
| DISTANCE FROM THE NEAREST FIRE HYDRANT TO THE FIRE |
| DEPARTMENT CONNECTION (FDC). NFPA 1141 8.1.3 * |
| (2017 EDITION) |
| WHERE MUNICIPAL-TYPE WATER SYSTEMS ARE AVAILABLE, |
| FIRE DEPARTMENT CONNECTIONS FOR SPRINKLER SYSTEMS |
| DESIGNED TO NFPA 13 OR NFPA 13R SHALL BE LOCATED |
| NOT MORE THAN 100 FT (30.5 M) ALONG AN APPROVED |
| PATH FROM A FIRE HYDRANT AND SHALL BE ARRANGED SO |
| THAT HOSE LINES CAN BE READILY AND CONVENIENTLY |
| ATTACHED TO THE INLETS WITHOUT INTERFERENCE FROM |
| ANY NEARBY OBJECTS, INCLUDING BUILDINGS, SIGNS, |
| FENCES, POSTS, OR OTHER FIRE DEPARTMENT |
| CONNECTIONS. |
| PROVIDE SUPPORTING MANUFACTURERS DOCUMENTATION FOR |
| PIPE SPECIFICATIONS, LISTING, BOLT TORQUE |
| SPECIFICATIONS, CORROSION RESISTANCE, ETC. |
| THIS PERMIT APPLIES ONLY TO THE UNDERGROUND FIRE |
| LINE. THE SUPPORTING DOCUMENTS INCLUDED THE FIRE |
| PUMP, THAT IS NOT PART OF THIS PERMIT. |
| ALL JOINTS SHALL BE INSPECTED BY THE FIRE |
| DEPARTMENT PRIOR TO COVERING. |
| |
| |
| |
| 7/7/22 PLANS UPLOADED,INCOMING COMPLETE.CD |
| 7/5/22 APPLICANT INVITED TO PAY FEES AND UPLOAD |
| PLANS AO |