| Miscellaneous Information / Notes |
| INSTALLATION OF VINYL PLANK FLOORING FOR LROOM, |
| FAM GRT R, KITCHEN & HALL |
| |
| |
| |
| |
| 8/22/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
| DOWNLOAD PLANS, PERMIT CARD UPLOADED AO |
| 8/19/22 PASSED BY FIRE.PML |
| 8/18/22 APPLICANT RESUBMITTED DIGTALLY,INCOMING |
| COMPLETE AO |
| 8/16/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
| RESUBMIT AO |
| 8/15/22, FAIL FIRE, CRW, THE SUBMITTED INFORMATION |
| IS FOR THE UNDERLAYMENT ONLY. |
| PROVIDE THE SPECIFICATIONS ON THE TESTING FOR THE |
| FIRE PERFORMANCE OF THE FINISHED FLOORING |
| MATERIALS INCLUDING THE CRITICAL RADIANT FLUX. |
| NFPA 101, 10.2.7 |
| |
| |
| 8/14/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 8/2/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. LEM |
| 8/1/22, FAIL FIRE, CRW, THE SUBMITTED INFORMATION |
| IS FOR THE UNDERLAYMENT MATERIAL. |
| PROVIDE THE SPECIFICATIONS ON TESTING FOR THE FIRE |
| PERFORMANCE OF THE FLOORING MATERIALS INCLUDING |
| THE CRITICAL RADIANT FLUX. NFPA 101, 10.2.7 |
| 7/29/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 7/25/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. LEM |
| 6/27/22, FAIL FIRE, CRW, WITH COMMENTS |
| 6/24/22 PLANS UPLOADED,INCOMING COMPLETE.CD |
| 6/23/22 APPLICANT INVITED TO PAY FEES AND UPLOAD |
| PLANS AO |