| Miscellaneous Information / Notes |
| MASTER 21101420 ACCESS CONTROL |
| ELECTRIC REVIEW PASSED PENDING PROVISION TO |
| PROVIDE ACCURATE, SIGNED AND SEALED PLANS BEFORE |
| FINAL INSPECTION |
| |
| |
| |
| 7/26/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
| DOWNLOAD PLANS, PERMIT CARD UPLOADED. LEM |
| 7/26/22, PASS FIRE, CRW |
| 7/25/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 7/25/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. LEM |
| 7/14/22, FAIL FIRE, CRW, PROVIDE A DETAILED METHOD |
| OF OPERATION OF THE ACCESS CONTROL DOORS TO ENSURE |
| FREE EGRESS IN THE EVENT OF AN EMERGENCY. THE PLAN |
| SHOULD INCLUDE MOUNTING REQUIREMENTS FOR CARD |
| READERS AS WELL AS ANY OTHER REQUIRED HARDWARE FOR |
| EGRESS. NFPA 101 7.2.1.6.2 |
| |
| |
| 7/13/22 APPLICANT RESUBMITTED DIGITALLY,INCOMING |
| COMPLETE AO |
| 6/15/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. AO |
| 6/3/22, FAIL FIRE, CRW, PROVIDE A DETAILED METHOD |
| OF OPERATION OF THE ACCESS CONTROL DOORS TO ENSURE |
| FREE EGRESS IN THE EVENT OF AN EMERGENCY. THE PLAN |
| SHOULD INCLUDE MOUNTING REQUIREMENTS FOR CARD |
| READERS AS WELL AS ANY OTHER REQUIRED HARDWARE FOR |
| EGRESS. NFPA 101 7.2.1.6.2 |
| |
| |
| 6/3/22 PLANS UPLOADED,INCOMING COMPLETE.CD |
| 5/11/22 APPLICANT INVITED TO PAY FEES AND UPLOAD |
| PLANS AO |