| Miscellaneous Information / Notes |
| FULL RENOVATION OF CONDO FLOORS WALLS BATHROOMS |
| |
| |
| |
| 6/2/22 PERMIT ISSUED. LEM |
| 6/1/22 REVIEWS COMPLETE, WAITING ON UPDATED SUB |
| CONTRACTOR INFO TO ISSUE PERMIT. LEM |
| 5/13/22, PASS FIRE, CRW |
| 5/13/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS |
| PASSED AND ROUTED TO STORAGE.MP |
| 5/12/22 RESUB RECEIVED, INCOMING COMPLETE AO |
| 5/11/22 RESUB DOCS UPLOADED INTO PROJECTDOX. PAPER |
| ROUTED TO MPETERSON FOR SIGNATURE REVIEW.CD |
| 5/10/22 CUSTOMER REQUESTED INCREASE IN VALUE TO |
| $272,735.42 AS PER REVIEWER REQUEST. LEM |
| 4/21/22 CUSTOMER REQUESTED TO SUBMIT A DEMO-INT |
| PERMIT - ADJUSTED THE VALUE TO NOT INCLUDE THE |
| $7200 - SEE PERMIT 22041085. LEM |
| 3/31/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. AO |
| 3/9/22, FAIL FIRE, CRW, FIRE REVIEW COMMENTS: |
| FOR CLARIFICATION OF THE PLAN SUBMITTED, THE TITLE |
| SHEET NOTE 38 STATES THE CONTRACTOR SHALL MAINTAIN |
| ALL LIFE SAFETY SYSTEMS IN OPERATION. THE DEMO |
| SHEET HAS SEVERAL LOCATIONS WHERE THE CONTRACTOR |
| IS TO REMOVE AND CAP FIRE SPRINKLER HEADS AS |
| NEEDED. PLEASE ADDRESS HOW ADEQUATE FIRE SPRINKLER |
| COVERAGE WILL BE MAINTAINED.ANY WORK PERFORMED |
| CONNECTED TO THE BUILDING FIRE ALARM SYSTEM WILL |
| REQUIRE A SEPARATE PERMIT AND SHOP DRAWINGS TO BE |
| SUBMITTED AND APPROVED.REVIEW PERFORMED BY,RANDY |
| WALKER, SENIOR FIRE INSPECTOR(561) |
| [email protected] |
| |
| |
| 3/8/22 PLANS UPLOADED SCANNING FEES ADDED,INCOMING |
| COMPLETE.PAPER ROUTED TO RMCPHERSON FOR SIGNATURE |
| REVIEW.CD |
| 3/8/22 CHANGED FROM PAPER TO DIGITAL.CD |