| Miscellaneous Information / Notes |
| REMOVE & REPLACE 827SQ OF FLOORING |
| |
| |
| |
| |
| 4/14/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
| DOWNLOAD PLANS, PERMIT CARD UPLOADED AO |
| 4/13/22 PASS FIRE CLF |
| 4/10/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
| 3/15/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. AO |
| 3/11/22 FAIL FIRE CLF |
| THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. |
| FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
| COMMENTS: |
| |
| 1) THE APPLICATION INDICATES THERE WILL BE THE |
| REPLACEMENT OF FLOORING WITH THE DOCUMENTS |
| IDENTIFYING MATERIALS BEING USED, BUT YOU HAVE |
| ONLY PROVIDE THE RADIENT FLUX FOR THE UNDERLAYMENT |
| PLEASE PROVIDE THE PRODUCT SPECS FOR THE ALLEN + |
| ROTH WATER RESISTANT SCARLET OAK LAMINATE FLOORING |
| THAT INCLUDE THE FIRE RATING. |
| |
| PER NFPA 101 CHAPTER 10, 10.2.7.2 |
| |
| SHALL MEET THE MINIMUM CRITICAL RADIENT FLUX. |
| |
| CAITLIN L. FRANCIS |
| FIRE INVESTIGATOR |
| 561-804-4728 |
| [email protected] |
| |
| |
| 3/9/22 APPLICANT RESUBMITTED DIGITALLY,INCOMING |
| COMPLETE AO |
| 3/1/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. LEM |
| 2/23/22 APPLICANT RESUBMITTED DIGITALLY, INCOMING |
| COMPLETE AO |
| 2/22/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT. AO |
| 2/3/22 FAILED FIRE CLF |
| THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. |
| FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
| COMMENTS: |
| |
| 1) THE APPLICATION INDICATES THERE WILL BE THE |
| REPLACEMENT OF FLOORING WITH THE DOCUMENTS |
| IDENTIFYING MATERIALS BEING USED, BUT PLEASE |
| PROVIDE THE PRODUCT SPECS FOR THE LAMINATE |
| FLOORING THAT INCLUDE THE FIRE RATING. |
| |
| PER NFPA 101 CHAPTER 10, 10.2.7.2 |
| |
| SHALL MEET THE MINIMUM CRITICAL RADIENT FLUX. |
| |
| CAITLIN L. FRANCIS |
| FIRE INVESTIGATOR |
| 561-804-4728 |
| [email protected] |
| |
| 2/1/22 PLANS UPLOADED,INCOMING COMPLETE.CD |
| 1/31/22 APPLICANT INVITED TO PAY FEES AND UPLOAD |
| PLANS. AO |