| Miscellaneous Information / Notes |
| REPLACE EXISTING FIRE ALARM PANEL WITH FL MS5UD |
| |
| |
| |
| 4/14/2023 PERMIT CLOSED PP |
| 1/17/19 ANTHONY P/U PERMIT SPALMER |
| 1/16/19 PLAN REVIEW COMPLETE, CUSTOMER INFORMED, |
| READY TO BE PICKED UP, FILED UNDER SMALL "T". CP |
| 1/10/19 SCOTT RESUB TO ADDRESS DENIED COMMENTS. AM |
| 6/11/18 PLAN REVIEW COMPLETE, CUSTOMER INFORMED |
| THEY NEED TO RESUBMIT, FILED UNDER SMALL DENIED |
| "T". CP |
| 6/5/18 - FIRE PASSED WITH THE FOLLOWING PROVISO: |
| |
| 1. PROVIDE COMPATIBILITY REPORT AT TIME OF |
| INSPECTION OF EXISTING DEVICES WITH NEW FACP. |
| |
| 2. ENSURE THAT NOTIFICATION APPLIANCES ARE |
| CREATING 75DB AT THE PILLOW TOP OF EACH BEDROOM IN |
| ACCORDANCE WITH NFPA 72 ? 7.4.4.1 |
| |
| 3. TEST ALL EXISTING DEVICES TO ENSURE |
| COMPATIBILITY AND FUNCTIONALITY WITH NEW FACP. |
| |
| 4. PROVIDE RECORD OF COMPLETION AT TIME OF |
| INSPECTION. |
| |
| 5. NOTIFY OWNERS AND ALL TENANTS 24 HOURS IN |
| ADVANCE OF FIRE ALARM TESTING WITH THE AHJ. |
| NOTIFICATION SHALL BE PROVIDED BY POSTING EACH |
| UNIT. |
| |
| 6. PROVIDE NFPA CODE COMPLIANT ?LOCAL ALARM ONLY? |
| SIGNAGE AT EACH PULL STATION. |
| |
| 7. ANY DETECTORS EXPOSED TO THE ELEMENTS OR |
| INSTALLED INSIDE OF AN AIR CONDITIONED OR FAN |
| CONDITIONED FACP SURFACE MOUNTED ENCLOSURE SHALL |
| BE HEAT DETECTION AS OPPOSE TO SMOKE DETECTION TO |
| ALLEVIATE FALSE ALARMS. |
| |