| Miscellaneous Information / Notes |
| ADDITION, REMODEL CHURCH BATHROOM |
| |
| |
| |
| |
| 3/29/23 ABANDONED PERMIT EXPIRD. LAST |
| INSPECTIONDONE ON 7/28/22. CD |
| 7/23/20215 VENITA P/U PERMIT NSD |
| 7/22/15 READY IN LARGE B/EMAILED CONTR/CC |
| 7/22/15: MECHANICAL APPROVED WITH EXCEPTION. |
| REVISIONS TO THE APPROVED PLANS FOR THE ITEMS |
| LISTED BELOW SHALL BE SUBMITTED, REVIEWED AND |
| APPROVED PRIOR TO 1ST INSPECTION. |
| |
| 1) THE MECHANICAL CLOSET LOUVERED DOOR #2 SHALL BE |
| OF NON-COMBUSTIBLE MATERIALS: THE DOOR SCHEDULE IS |
| INDICATING A WOOD DOOR- REFERENCE SECTIONS 202, |
| 602, AND 603.1 FBC-10 MECHANICAL. |
| 2) INDICATE HOW THE O/A DAMPER IS BEING |
| CONTROLLED- REFER TO SECTION 503.2.5.4 FBC-10 |
| ENERGY CONSERVATION. |
| 3) THE TOILET EXHAUST FAN FOR BATH-1 SHALL HAVE A |
| MINIMUM EXHAUST CAPACITY OF 100 CFM'S PER TABLE |
| 403.3 FOOTNOTE E. 50 CFM PER TOILET OR URINAL. |
| 4) PROVIDE TIE DOWN ENGINEERING FOR THE AC |
| CONDENSERS- SECTION 301.12 FBC-10 MECHANICAL |
| |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |
| |
| 7/21/15 CALLED CONTRACTOR, DENIED PLANS ARE FILED |
| UNDER "B" LARGE PLANS. JW |
| 7/17/15- MECH DENIED/SENT TO JW/CC |
| 7/16/15 RESUB ADDRESSING DENIED COMMENTS NO FEE |
| SPALMER |
| 07/13/2015 PLANS SIGNED OUT NSD |
| 7/10/15 PLAN REVIEW COMPLETE, APPLICANT NEEDS TO |
| RESUBMIT, PLANS IN LARGE DENIED UNDER "B". CP |
| 6/26/15- MECH DENIED/RETURNED TO C13/CC |
| 6/10/15 PASSED BY ENG. RETURNED TO C13. KEC |
| 6/5/15 PASSED BY FIRE PREVENTION, RETURNED TO |
| C13.PML |
| 06/04/2015 RESUB - RETURNED PLANS FROM IMPACT |
| FEES. MM |
| 5/21/15 CUSTOMER SIGNED OUT 1 SET OF NOA. MM |
| 5/8/15 CUSTOMER SIGNED OUT 1 SET OF PLANS SPALMER |
| 4/28/15 CONTACTED OWNER VIA EMAIL AT |
| [email protected] AND PUT IN LARGE FAILED |
| DRAWER. (B) KC |
| 3/5/15 PASSED BY FIRE PREVENTION WITH COMMENTS, |
| RETURNED TO C13.PML |