Inspection Details
INSPECTION DETAILS FOR PERMIT 14010644
Permit Number 14010644 Owner Name PALM BEACH OUTLETS I LLC
Permit Type SECURITY Permit Address 1801 PALM BEACH LAKES BLVD
Inspection Type ELECTRICAL FINAL-2 City WEST PALM BEACH
Inspect Area   Inspector 7003
Request Date 2015-04-09 Scheduled Date 2015-04-10
Instructions  
Contract Info  
Contractor FL01080 Inspect Date 2015-04-10
Result I Fail Code  
Comments  
Work Time   Confirm 422991
Fee ID  
Inspector Notes
Date Text
2015-12-18 14:52:18THIS INSPECTION WAS PASSED IN ERROR. THE
 PARKING LOT WAS NOT CONSIDERED WHEN
 CLOSING THE PERMIT IN APRIL OF 2015.
 SITE BUILT CONTROL BOXES DO NOT HAVE A
 LISTING OR FIELD EVALUATION. LIGHT POLES
 CONTAIN 480V CONDUCTORS AND CLASS 2
 WIRING AS WELL AS CCTV WIRING WITHOUT
 SEPARATION AND NO INDICATION THE WIRING
 IS PROTECTED FOR THE VOLTAGE PRESENT.
 CONTRACTOR NEEDS TO PROVIDE ADDITIONAL
 INFORMATION AND SEPARATION OF WIRING
 METHODS WITHIN THE LIGHT POLES OR
 DOCUMENTATION THAT IT IS NOT NEEDED DUE
 TO OTHER FORMS OF PROTECTION. IN
 ADDITION, PROVIDE LISTING OF FIELD BUILT
 CONTROL BOXES MOUNTED ON POLES.


Account Summary | Usage Policy | Privacy Policy