Date |
Text |
2020-08-19 09:29:53 | FAILED |
| |
| PERMIT 20041106 - UNDERGROUND FIBER MCIMETRO PROJECT |
| #1801CVFF.225 SOUTH OLIVE AND CONNISTON |
| |
| PROVIDE WRITTEN RESPONSE TO COMMENTS. |
| |
| THE FOLLOWING ITEMS NEED TO BE ADDRESSED OR THE PERMIT |
| WILL NOT BE APPROVED. |
| |
| 1) ENGINEERING PLAN - |
| |
| A. THE ENGINEERING PLAN DOES NOT MATCH THE TREE |
| PLACEMENT AS SHOWN ON THE SURVEY FOR THE HANDHOLE AT |
| 125+15. PROVIDE AN ACCURATE PLAN WHICH VERIFIES THAT |
| THE HANDHOLE WILL NOT DAMAGE THE ROOT ZONE OF THE TREE. |
| THE ENGINEERING PLAN NEEDS TO SHOW THE TREES AND A TEN |
| (10) FOOT SETBACK FROM THE TREES TO THE HANDHOLE IN |
| ORDER TO PREVENT DAMAGE TO THE TREES OR THEIR ROOT |
| ZONES FROM BOTH THE BORE AND THE HANDHOLE INSTALLATION. |
| |
| B. THE BORE SHOWN AT 10 FEET BELOW GRADE IS AT A |
| SUFFICIENT DEPTH TO AVOID PALM TREE DAMAGE. |
| |
| PLEASE NOTE: |
| |
| THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE 811 |
| TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY ALL |
| DEPTHS PRIOR TO CONSTRUCTION. ALL CITY UTILITIES MUST |
| BE LOCATED BY SOFT DIG METHODS BEFORE STARTING THE |
| WORK. |
| |
| THE RIGHT-OF-WAY USE PERMIT REQUIRES YOU TO PROVIDE A |
| CERTIFICATE OF LIABILITY INSURANCE, WHICH IN ACCORDANCE |
| WITH SECTION 78-406 OF THE CITY CODE SPECIFICALLY NAMES |
| THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS, |
| OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |
| |