2019-12-18 16:33:40 | INSUFFICIENT - DO NOT RESUBMIT IF SURVEY PREPARED BY |
| FLORIDA LICENSED SURVEYOR SHOWS POLE ON PRIVATE |
| PROPERTY |
| |
| PERMIT 19100097 SPRINT MI90XS888-1 412 S. TAMARIND |
| 2ND REVIEW |
| |
| PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE |
| DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401 |
| OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE |
| COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION. |
| THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO |
| REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF |
| HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS, |
| THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION, |
| NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE |
| APPROVED. |
| |
| 1) REVISED COMMENT: ENGINEERING PLAN |
| |
| A. THE SUBMITTED ENGINEERING PLAN MUST BE BASED ON THE |
| REQUIRED SURVEYS. NOTE: EVEN THOUGH YOUR SURVEY EXHIBIT |
| SHEET DOES NOT QUALIFY AS A SURVEY, IT SHOWS THE |
| EXISTING POLE LOCATION ON PRIVATE PROPERTY; THEREFORE, |
| THIS IS NOT A RIGHT-OF-WAY INSTALLATION. THE CITY'S |
| ZONING AND LAND DEVELOPMENT REGULATIONS ONLY PERMIT THE |
| ATTACHMENT OF NON-CONCEALED WIRELESS EQUIPMENT ON HIGH |
| VOLTAGE ELECTRIC POWER TRANSMISSION TOWERS AND LIGHT |
| STANCHIONS NOT LOCATED IN PUBLIC RIGHTS-OF-WAY. THE |
| EXISTING POLE IS NEITHER OF THESE, SO YOU MAY NOT MOUNT |
| AN ANTENNA TO IT. |
| |
| B. IF THIS IS A MOUNTING ON AN EXISTING POLE, THEN YOU |
| MUST SUBMIT A STRUCTURAL CAPACITY REPORT FOR THE |
| SUPPORT STRUCTURE, AS EVIDENCED BY A SEALED STATEMENT |
| FROM A STRUCTURAL ENGINEER LICENSED IN THE STATE OF |
| FLORIDA, THAT THE POLE CAN SUPPORT THE PROPOSED |
| ELEMENTS. THIS WAS NOT PROVIDED. |
| |
| C. YOU MAY NOT INSTALL GROUND EQUIPMENT IN A |
| RIGHT-OF-WAY FOR AN ANTENNA INSTALLATION ON PRIVATE |
| PROPERTY. |
| |
| 2) REPEAT COMMENT: SURVEY OF UNDERGROUND FACILITIES - |
| THE BASE OF THE POLE IS BEING INSTALLED UNDERGROUND SO |
| THIS IS REQUIRED. |
| |
| A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON A |
| SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR. |
| |
| B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS |
| SURVEY INFORMATION. |
| |
| 3) REPEAT COMMENT: SURVEY OF ABOVEGROUND FACILITIES - A |
| NEW POLE IS BEING USED OR INSTALLED ABOVEGROUND SO THIS |
| IS REQUIRED. PLEASE NOTE THAT AS PART OF THE |
| APPLICATION YOU WILL NEED TO PROVIDE THE CONSENT FROM |
| FPL FOR THE ATTACHMENT TO THEIR POLE. CONTRARY TO THE |
| RESPONSE TO THESE COMMENTS THE CONSENT WAS NOT |
| INCLUDED. OWNERSHIP INFORMATION MUST BE SHOWN ON THE |
| SURVEY. |
| |
| A. IDENTIFY ALL ABOVEGROUND FEATURES TO INCLUDE TREES |
| ON A SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR. |
| SHEET SE-1 IS NOT A SURVEY PREPARED BY A FLORIDA |
| LICENSED SURVEYOR, NOR DOES IT SHOW ALL THE ABOVEGROUND |
| FEATURES. |
| |
| B. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN |
| THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S |
| EXISTING FACILITIES - NO INFORMATION ON EXISTING |
| FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE |
| PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO |
| FACILITIES, THIS SHALL BE NOTED ON THE SURVEY. |
| |
| C. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS |
| SURVEY INFORMATION. |
| |
| 4) REPEAT COMMENT: CONCEALMENT METHODS DESCRIPTIONS - |
| NO CONCEALMENT INFORMATION WAS PROVIDED. REGARDLESS OF |
| IF THIS IS A NEW POLE OR ATTACHMENT TO AN EXISTING |
| POLE, THE EXTERIOR CABLES, NON-CONCEALED ANTENNAS AND A |
| REMOTE EQUIPMENT CABINET DO NOT COMPLY WITH THE |
| CONCEALMENT STANDARDS OUTLINED IN SECTION 78-411 OF THE |
| CITY CODE. THE POLE ELEVATION MUST INCLUDE ALL THE |
| DIMENSIONS. PLEASE NOTE THAT NON-CONCEALED ATTACHMENTS |
| ARE ONLY PERMITTED ON ELECTRICAL TRANSMISSION POLES AND |
| LIGHT POLES, WHICH THIS POLE IS NOT. |
| |
| 5) REPEAT COMMENT: CONSTRUCTION TIMETABLE - YOU MUST |
| PROVIDE AN ESTIMATED TIMETABLE FOR CONSTRUCTION OF THE |
| PROJECT. |
| |
| 6) REPEAT COMMENT: RESTORATION ESTIMATE - YOU MUST |
| PROVIDE A RESTORATION ESTIMATE, WHICH IS THE COST FOR |
| THE RESTORATION THAT YOU LIST ON SHEET R-1. THE NOTES |
| ON SHEET R-1 MUST BE UPDATED TO NOT REFERENCE THE CITY |
| OF FORT LAUDERDALE REQUIREMENTS.. |
| |
| 7) REPEAT COMMENT: EVIDENCE OF INSURANCE COVERAGE - YOU |
| ARE REQUIRED TO SUBMIT VERIFICATION OF INSURANCE IN |
| ACCORDANCE WITH THE PROVISIONS OF SECTION 78-406 OF THE |
| CITY CODE OF ORDINANCES. |
| |
| 8) REPEAT COMMENT: START OF OPERATION - AN ATTESTATION |
| FROM THE COMMUNICATIONS FACILITIES SERVICE PROVIDER |
| THAT COMMUNICATIONS SERVICES FACILITIES WILL BE |
| INSTALLED AND OPERATIONAL ON THE PROPOSED STRUCTURE NO |
| LATER THAN NINE MONTHS AFTER THE DATE THE APPLICATION |
| IS APPROVED IS REQUIRED. PROVIDE THE REQUIRED |
| ATTESTATION. |
| |
| 9) REPEAT COMMENT: PUBLIC UTILITY LETTERS, TELEPHONE, |
| NATURAL GAS, ELECTRIC SERVICE, AND TELEVISION CABLE - |
| THE PUBLIC UTILITY LETTERS WERE NOT PROVIDED. PROVIDE |
| COPIES OF THE PUBLIC UTILITY LETTERS. |
| |
| 10) REPEAT COMMENT: POLE OWNER APPROVAL - THE APPROVAL |
| FROM THE OWNER OF THE POLE PERMITTING THE INSTALLATION |
| OF A FACILITY WAS NOT PROVIDED. PLEASE NOTE THAT IF |
| THIS IS BEING INSTALLED ON A CITY POLE, THEN FEE IS |
| REQUIRED TO BE PAID TO THE CITY. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |