2019-12-18 16:33:40INSUFFICIENT - DO NOT RESUBMIT IF SURVEY PREPARED BY
 FLORIDA LICENSED SURVEYOR SHOWS POLE ON PRIVATE
 PROPERTY
  
 PERMIT 19100097 SPRINT MI90XS888-1 412 S. TAMARIND
 2ND REVIEW
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) REVISED COMMENT: ENGINEERING PLAN
  
 A. THE SUBMITTED ENGINEERING PLAN MUST BE BASED ON THE
 REQUIRED SURVEYS. NOTE: EVEN THOUGH YOUR SURVEY EXHIBIT
 SHEET DOES NOT QUALIFY AS A SURVEY, IT SHOWS THE
 EXISTING POLE LOCATION ON PRIVATE PROPERTY; THEREFORE,
 THIS IS NOT A RIGHT-OF-WAY INSTALLATION. THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS ONLY PERMIT THE
 ATTACHMENT OF NON-CONCEALED WIRELESS EQUIPMENT ON HIGH
 VOLTAGE ELECTRIC POWER TRANSMISSION TOWERS AND LIGHT
 STANCHIONS NOT LOCATED IN PUBLIC RIGHTS-OF-WAY. THE
 EXISTING POLE IS NEITHER OF THESE, SO YOU MAY NOT MOUNT
 AN ANTENNA TO IT.
  
 B. IF THIS IS A MOUNTING ON AN EXISTING POLE, THEN YOU
 MUST SUBMIT A STRUCTURAL CAPACITY REPORT FOR THE
 SUPPORT STRUCTURE, AS EVIDENCED BY A SEALED STATEMENT
 FROM A STRUCTURAL ENGINEER LICENSED IN THE STATE OF
 FLORIDA, THAT THE POLE CAN SUPPORT THE PROPOSED
 ELEMENTS. THIS WAS NOT PROVIDED.
  
 C. YOU MAY NOT INSTALL GROUND EQUIPMENT IN A
 RIGHT-OF-WAY FOR AN ANTENNA INSTALLATION ON PRIVATE
 PROPERTY.
  
 2) REPEAT COMMENT: SURVEY OF UNDERGROUND FACILITIES -
 THE BASE OF THE POLE IS BEING INSTALLED UNDERGROUND SO
 THIS IS REQUIRED.
  
 A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON A
 SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
  
 B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 3) REPEAT COMMENT: SURVEY OF ABOVEGROUND FACILITIES - A
 NEW POLE IS BEING USED OR INSTALLED ABOVEGROUND SO THIS
 IS REQUIRED. PLEASE NOTE THAT AS PART OF THE
 APPLICATION YOU WILL NEED TO PROVIDE THE CONSENT FROM
 FPL FOR THE ATTACHMENT TO THEIR POLE. CONTRARY TO THE
 RESPONSE TO THESE COMMENTS THE CONSENT WAS NOT
 INCLUDED. OWNERSHIP INFORMATION MUST BE SHOWN ON THE
 SURVEY.
  
 A. IDENTIFY ALL ABOVEGROUND FEATURES TO INCLUDE TREES
 ON A SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
 SHEET SE-1 IS NOT A SURVEY PREPARED BY A FLORIDA
 LICENSED SURVEYOR, NOR DOES IT SHOW ALL THE ABOVEGROUND
 FEATURES.
  
 B. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN
 THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S
 EXISTING FACILITIES - NO INFORMATION ON EXISTING
 FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE
 PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO
 FACILITIES, THIS SHALL BE NOTED ON THE SURVEY.
  
 C. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 4) REPEAT COMMENT: CONCEALMENT METHODS DESCRIPTIONS -
 NO CONCEALMENT INFORMATION WAS PROVIDED. REGARDLESS OF
 IF THIS IS A NEW POLE OR ATTACHMENT TO AN EXISTING
 POLE, THE EXTERIOR CABLES, NON-CONCEALED ANTENNAS AND A
 REMOTE EQUIPMENT CABINET DO NOT COMPLY WITH THE
 CONCEALMENT STANDARDS OUTLINED IN SECTION 78-411 OF THE
 CITY CODE. THE POLE ELEVATION MUST INCLUDE ALL THE
 DIMENSIONS. PLEASE NOTE THAT NON-CONCEALED ATTACHMENTS
 ARE ONLY PERMITTED ON ELECTRICAL TRANSMISSION POLES AND
 LIGHT POLES, WHICH THIS POLE IS NOT.
  
 5) REPEAT COMMENT: CONSTRUCTION TIMETABLE - YOU MUST
 PROVIDE AN ESTIMATED TIMETABLE FOR CONSTRUCTION OF THE
 PROJECT.
  
 6) REPEAT COMMENT: RESTORATION ESTIMATE - YOU MUST
 PROVIDE A RESTORATION ESTIMATE, WHICH IS THE COST FOR
 THE RESTORATION THAT YOU LIST ON SHEET R-1. THE NOTES
 ON SHEET R-1 MUST BE UPDATED TO NOT REFERENCE THE CITY
 OF FORT LAUDERDALE REQUIREMENTS..
  
 7) REPEAT COMMENT: EVIDENCE OF INSURANCE COVERAGE - YOU
 ARE REQUIRED TO SUBMIT VERIFICATION OF INSURANCE IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 78-406 OF THE
 CITY CODE OF ORDINANCES.
  
 8) REPEAT COMMENT: START OF OPERATION - AN ATTESTATION
 FROM THE COMMUNICATIONS FACILITIES SERVICE PROVIDER
 THAT COMMUNICATIONS SERVICES FACILITIES WILL BE
 INSTALLED AND OPERATIONAL ON THE PROPOSED STRUCTURE NO
 LATER THAN NINE MONTHS AFTER THE DATE THE APPLICATION
 IS APPROVED IS REQUIRED. PROVIDE THE REQUIRED
 ATTESTATION.
  
 9) REPEAT COMMENT: PUBLIC UTILITY LETTERS, TELEPHONE,
 NATURAL GAS, ELECTRIC SERVICE, AND TELEVISION CABLE -
 THE PUBLIC UTILITY LETTERS WERE NOT PROVIDED. PROVIDE
 COPIES OF THE PUBLIC UTILITY LETTERS.
  
 10) REPEAT COMMENT: POLE OWNER APPROVAL - THE APPROVAL
 FROM THE OWNER OF THE POLE PERMITTING THE INSTALLATION
 OF A FACILITY WAS NOT PROVIDED. PLEASE NOTE THAT IF
 THIS IS BEING INSTALLED ON A CITY POLE, THEN FEE IS
 REQUIRED TO BE PAID TO THE CITY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  