Plan Review Notes
Plan Review Notes For Permit 19100097
Permit Number 19100097
Review Stop ENG-P
Sequence Number 2
Notes
Date Text
2019-12-10 09:33:31PERMIT 19100097S TAMARIND AVE SOUTH OF FERN ST.
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) SURVEY OF UNDERGROUND FACILITIES:
 MISSING UTILITY INFORMATION FROM DRAWING, ALSO COPIES
 OF CITY UTILITY DRAWINGS NOT PROVIDED.
  
 2) DRAWING: SH PS-1, A MINIUM OF 36" IS REQUIRED FOR
 ADA. PROVIDE DIMENSION FROM PROPOSED BOX LOCATION AND
 EXISTING STOP SIGN.