Plan Review Notes For Permit 19060073 |
Permit Number |
19060073 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-12 10:40:49 | 1) SHT. C-04 SHOWS A RESIDENTIAL PRESSURE VACUUM | | BREAKER DETAIL TO BE USED ON THIS IRRIGATION SYSTEM | | WHICH IS NOT PERMITTED. A LEAD FREE REDUCED PRESSURE | | ZONE BACKFLOW PREVENTER IS REQUIRED FOR THE SECTIONS TO | | BE EQUIPPED WITH A BACKFLOW PREVENTION DEVICE PER THE | | CITY OF WPB CROSS CONNECTION CONTROL MANUAL. | | 2) PIPING FROM THE OUTLET OF THE WATER METERS TO THE | | INLET OF THE BACKFLOW PREVENTION DEVICE SHALL BE TYPE | | "K" OR "L" COPPER, BRASS, OR STAINLESS STEEL. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|