2013-06-25 15:18:30PERMIT ISSUED WITH THE FOLLOWING PROVISO:
 LOW VOLTAGE DATA CONDUCTORS ARE REQUIRED TO BE
 SEPARATED FROM THE POWER CONDUCTORS WITHIN A
 NONCONDUCTIVE SLEEVE. NEC 725.136 (D)(2)
  
 MAX 80 AMPS ALLOWED FOR SERVICE MAIN DISCONNECT. NEC T.
 310-16
  
 RL