2013-06-25 14:00:30PERMIT ISSUED WITH THE FOLLOWING PROVISO:
 LOW VOLTAGE DATA CONDUCTORS ARE REQUIRED TO BE
 SEPARATED FROM THE POWER CONDUCTORS WITHIN A
 NONCONDUCTIVE SLEEVE. NEC 725.136 (D)(2)
  
 80 AMP MAIN BREAKER IS THE MAXIMUM ALLOWED FOR LISTED
 SERVICE CONDUCTORS. NEC T310.16
  