Plan Review Details - Permit 22031268
Plan Review Stops For Permit 22031268
Review Stop AD ADDRESSING
Rev No 3 Status F Date 2023-06-14 Cont ID  
Sent By cpuell Date 2023-06-14 Time 09:50 Rev Time 0.00
Received By cpuell Date 2023-06-14 Time 09:50 Sent To  
Notes
2023-06-14 09:50:38AN @ ADDRESS NEEDS TO BE ASSIGNED TO THIS PROJECT.
 PLEASE EMAIL A SITE PLAN SHOWING THE EXACT LOCATION OF
 THE WHERE THE WORK IS TO BE DONE. IN THE FUTURE PLEASE
 MAKE SURE THAT YOU COORDINATE WITH
 [email protected] OR CALL 561-805-6659 BEFORE
 APPLYING FOR A PERMIT TO BE ISSUED AN @ ADDRESS.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-03-13 Cont ID  
Sent By cpuell Date 2023-03-13 Time 13:33 Rev Time 0.00
Received By cpuell Date 2023-03-13 Time 13:33 Sent To  
Notes
2023-03-13 13:35:03MCI METRO HAS BEEN ASSIGNED A GENERIC PCN AN ADDRESS
 NEEDS TO EB ASSIGNED TO THIS PROJECT. PLEASE EMAIL A
 SITE PLAN SHOWING THE EXACT LOCATION OF THE WHERE THE
 WORK IS TO BE DONE. IN THE FUTURE PLEASE MAKE SURE THAT
 YOU COORDINATE WITH [email protected] OR CALL
 561-805-6659 BEFORE APPLYING FOR A PERMIT TO BE ISSUED
 AN @ ADDRESS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By cpuell Date 2022-08-03 Time 15:18 Rev Time 0.00
Received By cpuell Date 2022-08-03 Time 14:10 Sent To  
Notes
2022-08-03 14:12:13PLEASE CONTACT [email protected], TO BE ASSIGNED A
 GENERIC PROPERTY CONTROL NUMBER FOR MCI METRO, ALSO
 PLEASE EMAIL A SITE PLAN SHOWING THE EXACT LOCATION OF
 THE WHERE THE WORK IS TO BE DONE. IN THE FUTURE PLEASE
 MAKE SURE THAT YOU COORDINATE WITH
 [email protected] OR CALL 561-805-6659 BEFORE
 APPLYING FOR A PERMIT TO BE ISSUED AN @ ADDRESS.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2023-05-17 Cont ID  
Sent By cseifer Date 2023-05-17 Time 08:32 Rev Time 0.00
Received By cseifer Date 2023-05-17 Time 08:30 Sent To  
Notes
2023-05-17 08:32:311. CONDUIT APPEARS TO BE CROSSING PRIVATE PROPERTY AT
 THE CORNER OF CLEARWATER AND AUSTRALIAN. PLEASE SHOW
 THERE IS AN EASEMENT ALONG THIS CROSSING TO OCCUR.
  
 2. PROVIDE A COPY OF COUNTY AND FDOT PERMIT APPROVING
 WORK WITHIN THEIR RIGHT-OF-WAY.
  
 CHLOE SEIFER
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By sberglun Date 2022-08-17 Time 10:08 Rev Time 0.00
Received By sberglun Date 2022-08-17 Time 10:08 Sent To  
Notes
2022-08-17 10:08:031) CITY UTILITIES ARE SHOWN INCORRECTLY ON PLANS.
 INCLUDE CITY UNDERGROUND UTILITIY PIPE SIZE, PIPE
 MATERIAL, AND DESCRIPTION ON BOTH PLAN VIEW AND PROFILE
 VIEW. CONTACT JANICE TARBILL, [email protected] FOR
 AS-BUILT INFORMATION. INCLUDE AS-BUILT INFORMATION IN
 YOUR RESUBMITTAL.
 2) ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE
 REQUIRED PER CITY STANDARD, PARTIAL SIDEWALK FLAG
 REPLACEMNTS ARE NOT ACCEPTABLE. PLEASE USE CITY OF WEST
 PALM BEACH STANDARD DETAILS.
  
 SUZANNE BERGLUND
 [email protected]
 561-494-1075
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-06-07 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-18 Cont ID  
Sent By aoliver Date 2023-05-18 Time 07:46 Rev Time 0.00
Received By aoliver Date 2023-03-08 Time 15:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-26 Cont ID  
Sent By aoliver Date 2022-08-26 Time 07:57 Rev Time 0.00
Received By aoliver Date 2022-07-20 Time 18:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-08-26 Cont ID  
Sent By aoliver Date 2022-08-26 Time 07:57 Rev Time 0.00
Received By aoliver Date 2022-08-26 Time 07:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-06-29 Cont ID  
Sent By ckimmerl Date 2023-06-29 Time 16:13 Rev Time 0.00
Received By ckimmerl Date 2023-06-29 Time 15:57 Sent To  
Notes
2023-06-29 15:59:10INSUFFICIENT
  
 REPEAT COMMENTS:
  
 1. PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE
 SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG
 THE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY THAT
 THE BORE AND ANY REQUIRED BORE PITS AND HANDHOLES ARE
 WITHIN THE PUBLIC RIGHT-OF-WAY. THE SURVEY NEEDS TO
 INCLUDE THE LOCATION OF CONDUIT, PROPOSED HANDHOLES,
 AND THE BORE SECTIONS. IN ORDER TO INSTALL HANDHOLES
 AND BORE UNDER PRIVATE PROPERTY THE SCOPE OF WORK MUST
 BE WITHIN A GENERAL UTILITY EASEMENT. THIS GENERAL
 UTILITY EASEMENT MUST BE CLEARLY SHOWN ON THE SURVEY.
  
 [NEW COMMENT 3.21.23] CONDUIT APPEARS TO CROSS OVER
 PRIVATE PROPERTY AT CORNER INTERSECTION OF CLEARWATER
 AND AUSTRALIAN. PLEASE SHOW EASEMENT GRANTING THIS
 CROSSING.
  
 [UPDATE 6.29.23] THANK YOU FOR PROVIDING SURVEY
 SECTIONS, PLEASE OVERLAY FIBER CONDUIT PATH AS WELL AS
 ANY HANDHOLES OR BOREPITS ON THE SURVEY.
  
 2. THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY
 ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE
 BURIED.
  
 3. PROVIDE A COPY OF THE FDOT PERMIT APPROVING THE WORK
 WITHIN THEIR RIGHT-OF-WAY.
  
 4. ANY BOREPITS, HANDHOLES, OR EXCAVATION WORK SHALL
 PROVIDE AN 8FT. BUFFER FROM THE TRUNK OF THE TREE TO
 REDUCE THE RISK TO ROOT SYSTEMS. PLEASE PROVIDE
 DIMENSIONS FROM ANY TREES ADJACENT TO EXCAVATIONS.
  
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 822.1426 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-03-21 Cont ID  
Sent By ckimmerl Date 2023-03-21 Time 10:57 Rev Time 0.00
Received By ckimmerl Date 2023-03-21 Time 10:54 Sent To  
Notes
2023-03-21 10:57:28[3.21.23 REPEAT COMMENTS]
  
 INSUFFICIENT
  
 1. PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE
 SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG
 THE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY THAT
 THE BORE AND ANY REQUIRED BORE PITS AND HANDHOLES ARE
 WITHIN THE PUBLIC RIGHT-OF-WAY. THE SURVEY NEEDS TO
 INCLUDE THE LOCATION OF CONDUIT, PROPOSED HANDHOLES,
 AND THE BORE SECTIONS. IN ORDER TO INSTALL HANDHOLES
 AND BORE UNDER PRIVATE PROPERTY THE SCOPE OF WORK MUST
 BE WITHIN A GENERAL UTILITY EASEMENT. THIS GENERAL
 UTILITY EASEMENT MUST BE CLEARLY SHOWN ON THE SURVEY.
  
 [NEW COMMENT 3.21.23] CONDUIT APPEARS TO CROSS OVER
 PRIVATE PROPERTY AT CORNER INTERSECTION OF CLEARWATER
 AND AUSTRALIAN. PLEASE SHOW EASEMENT GRANTING THIS
 CROSSING.
  
 2. THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY
 ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE
 BURIED.
  
 3. PROVIDE A COPY OF THE FDOT PERMIT APPROVING THE WORK
 WITHIN THEIR RIGHT-OF-WAY.
  
 4. ANY BOREPITS, HANDHOLES, OR EXCAVATION WORK SHALL
 PROVIDE AN 8FT. BUFFER FROM THE TRUNK OF THE TREE TO
 REDUCE THE RISK TO ROOT SYSTEMS. PLEASE PROVIDE
 DIMENSIONS FROM ANY TREES ADJACENT TO EXCAVATIONS.
  
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 822.1426 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-25 Cont ID  
Sent By ckimmerl Date 2022-08-25 Time 11:41 Rev Time 0.00
Received By ckimmerl Date 2022-08-25 Time 11:41 Sent To  
Notes
2022-08-25 11:41:30INSUFFICIENT
  
 1. PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE
 SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG
 THE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY THAT
 THE BORE AND ANY REQUIRED BORE PITS AND HANDHOLES ARE
 WITHIN THE PUBLIC RIGHT-OF-WAY. THE SURVEY NEEDS TO
 INCLUDE THE LOCATION OF PROPOSED HANDHOLES AND THE BORE
 SECTIONS.
  
 IN ORDER TO INSTALL HANDHOLES AND BORE UNDER PRIVATE
 PROPERTY THE SCOPE OF WORK MUST BE WITHIN A GENERAL
 UTILITY EASEMENT. THIS GENERAL UTILITY EASEMENT MUST BE
 CLEARLY SHOWN ON THE SURVEY.
  
 2. THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY
 ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE
 BURIED.
  
 3. PROVIDE A COPY OF THE FDOT PERMIT APPROVING THE WORK
 WITHIN THEIR RIGHT-OF-WAY.
  
 4. ANY BOREPITS, HANDHOLES, OR EXCAVATION WORK SHALL
 PROVIDE AN 8FT. BUFFER FROM THE TRUNK OF THE TREE TO
 REDUCE THE RISK TO ROOT SYSTEMS. PLEASE PROVIDE
 DIMENSIONS FROM ANY TREES ADJACENT TO EXCAVATIONS.
  
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 822.1426 [email protected]
  