Plan Review Stops For Permit 22021331 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2023-06-14 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-06-14 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-06-14 |
Time |
09:46 |
Sent To |
|
|
Notes |
2023-06-14 09:46:48 | AN @ ADDRESS NEEDS TO BE ASSIGNED TO THIS PROJECT. | | PLEASE EMAIL A SITE PLAN SHOWING THE EXACT LOCATION OF | | THE WHERE THE WORK IS TO BE DONE. IN THE FUTURE PLEASE | | MAKE SURE THAT YOU COORDINATE WITH | | [email protected] OR CALL 561-805-6659 BEFORE | | APPLYING FOR A PERMIT TO BE ISSUED AN @ ADDRESS. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2022-08-03 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-08-03 |
Time |
12:57 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-08-03 |
Time |
12:57 |
Sent To |
|
|
Notes |
2022-08-03 12:58:25 | PLEASE CONTACT [email protected], TO BE ASSIGNED A | | GENERIC PROPERTY CONTROL NUMBER FOR MCI METRO, ALSO | | PLEASE EMAIL A SITE PLAN SHOWING THE EXACT LOCATION OF | | THE WHERE THE WORK IS TO BE DONE. IN THE FUTURE PLEASE | | MAKE SURE THAT YOU COORDINATE WITH | | [email protected] OR CALL 561-805-6659 BEFORE | | APPLYING FOR A PERMIT TO BE ISSUED AN @ ADDRESS. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2023-07-17 |
|
|
Cont ID |
|
Sent By |
cseifer |
Date |
2023-07-17 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
cseifer |
Date |
2023-07-17 |
Time |
11:04 |
Sent To |
|
|
Notes |
2023-07-17 11:06:55 | 1) PROJECT IS LOCATED WITHIN THE CITY'S TAMARIND AVENUE | | IMPROVEMENTS PROJECT (TAMARIND FROM BANYAN TO PALM | | BEACH LAKES). PLEASE COORDINATE WITH THE PROJECT PM FOR | | SITE UTILITIES, VLADIMIR JEANNOT, [email protected]. | | 2) PERMISSION FROM THE ON-SITE CONTRACTOR WOULD BE | | REQUIRED IF CONSTRUCTION IS ONGOING WHEN YOU PROPOSE TO | | DO YOUR WORK, WHITING-TURNER, | | [email protected]. | | | | CHLOE SEIFER | | [email protected] |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2022-08-16 |
|
|
Cont ID |
|
Sent By |
sberglun |
Date |
2022-08-16 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
sberglun |
Date |
2022-08-16 |
Time |
14:34 |
Sent To |
|
|
Notes |
2022-08-16 14:37:53 | 1) PROJECT IS LOCATED WITHIN THE CITY'S TAMARIND AVENUE | | IMPROVEMENTS PROJECT (TAMARIND FROM BANYAN TO PALM | | BEACH LAKES). PLEASE COORDINATE WITH THE PROJECT PM FOR | | SITE UTILITIES, VLADIMIR JEANNOT, [email protected]. | | 2) PERMISSION FROM THE ON-SITE CONTRACTOR WOULD BE | | REQUIRED IF CONSTRUCTION IS ONGOING WHEN YOU PROPOSE TO | | DO YOUR WORK, WHITING-TURNER, | | [email protected]. | | 2) INCLUDE CITY UNDERGROUND UTILITIY PIPE SIZE, PIPE | | MATERIAL, AND DESCRIPTION ON BOTH PLAN VIEW AND PROFILE | | VIEW. CONTACT JANICE TARBILL, [email protected] FOR | | AS-BUILT INFORMATION. INCLUDE AS-BUILT INFORMATION IN | | YOUR RESUBMITTAL. | | 3) ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE | | REQUIRED PER CITY STANDARD, PARTIAL SIDEWALK FLAG | | REPLACEMNTS ARE NOT ACCEPTABLE. PLEASE USE CITY OF WEST | | PALM BEACH STANDARD DETAILS. | | | | SUZANNE BERGLUND | | [email protected] | | 561-494-1075 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-07-18 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-06-02 |
Time |
10:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-08-26 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2022-08-26 |
Time |
07:46 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-07-14 |
Time |
17:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2022-08-26 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2022-08-26 |
Time |
07:46 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-08-26 |
Time |
07:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2023-06-29 |
|
|
Cont ID |
|
Sent By |
ckimmerl |
Date |
2023-06-29 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
ckimmerl |
Date |
2023-06-29 |
Time |
15:39 |
Sent To |
|
|
Notes |
2023-06-29 15:40:38 | INSUFFICIENT | | | | REPEAT COMMENTS: | | | | 1. PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED | | SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE | | SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG | | THE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY THAT | | THE BORE AND ANY REQUIRED BORE PITS AND HANDHOLES ARE | | WITHIN THE PUBLIC RIGHT-OF-WAY. THE SURVEY NEEDS TO | | INCLUDE THE LOCATION OF PROPOSED HANDHOLES AND THE BORE | | SECTIONS. | | | | IN ORDER TO INSTALL HANDHOLES AND BORE UNDER PRIVATE | | PROPERTY THE SCOPE OF WORK MUST BE WITHIN A GENERAL | | UTILITY EASEMENT. THIS GENERAL UTILITY EASEMENT MUST BE | | CLEARLY SHOWN ON THE SURVEY. | | | | [UPDATE 6.29.23] THANK YOU FOR PROVIDING SURVEY | | SECTIONS, PLEASE OVERLAY THE FIBER CONDUIT PATH AS WELL | | AS ANY BOREPITS OR HANDOLES ON THESE SURVEYS. | | | | 2. THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY | | ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE | | BURIED. | | | | 3. ANY BOREPITS, HANDHOLES, OR EXCAVATION WORK SHALL | | PROVIDE AN 8FT. BUFFER FROM THE TRUNK OF THE TREE TO | | REDUCE THE RISK TO ROOT SYSTEMS. PLEASE PROVIDE | | DIMENSIONS FROM ANY TREES ADJACENT TO EXCAVATIONS. | | | | CHRIS KIMMERLY, AICP | | URBAN DESIGN PLANNER | | 822.1426 [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-08-25 |
|
|
Cont ID |
|
Sent By |
ckimmerl |
Date |
2022-08-25 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
ckimmerl |
Date |
2022-08-25 |
Time |
10:29 |
Sent To |
|
|
Notes |
2022-08-25 10:33:08 | INSUFFICIENT | | | | 1. PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED | | SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE | | SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG | | THE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY THAT | | THE BORE AND ANY REQUIRED BORE PITS AND HANDHOLES ARE | | WITHIN THE PUBLIC RIGHT-OF-WAY. THE SURVEY NEEDS TO | | INCLUDE THE LOCATION OF PROPOSED HANDHOLES AND THE BORE | | SECTIONS. | | | | IN ORDER TO INSTALL HANDHOLES AND BORE UNDER PRIVATE | | PROPERTY THE SCOPE OF WORK MUST BE WITHIN A GENERAL | | UTILITY EASEMENT. THIS GENERAL UTILITY EASEMENT MUST BE | | CLEARLY SHOWN ON THE SURVEY. | | | | 2. THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY | | ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE | | BURIED. | | | | 3. ANY BOREPITS, HANDHOLES, OR EXCAVATION WORK SHALL | | PROVIDE AN 8FT. BUFFER FROM THE TRUNK OF THE TREE TO | | REDUCE THE RISK TO ROOT SYSTEMS. PLEASE PROVIDE | | DIMENSIONS FROM ANY TREES ADJACENT TO EXCAVATIONS. | | | | CHRIS KIMMERLY, AICP | | URBAN DESIGN PLANNER | | 822.1426 [email protected] |
|
|