Plan Review Details - Permit 20060809
Plan Review Stops For Permit 20060809
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-17 Cont ID  
Sent By cthroop Date 2020-06-17 Time 13:09 Rev Time 0.00
Received By cthroop Date 2020-06-17 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-16 Cont ID  
Sent By cthroop Date 2020-06-16 Time 16:11 Rev Time 0.00
Received By cthroop Date 2020-06-16 Time 15:53 Sent To  
Notes
2020-06-16 16:13:46PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IDENTIFY LOCATION OF TENTS ON SITE PLAN.
 107.2 CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE TIE DOWN DETAIL.
 107.2 CONSTRUCTION DOCUMENTS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-17 Cont ID  
Sent By pleduc Date 2020-06-17 Time   Rev Time 0.00
Received By pleduc Date 2020-06-17 Time 15:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-16 Cont ID  
Sent By pleduc Date 2020-06-16 Time   Rev Time 0.00
Received By pleduc Date 2020-06-16 Time 15:38 Sent To  
Notes
2020-06-16 15:42:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) FIRE HAS NO OBJECTION TO THE INTENT OF THE TENTS;
 HOWEVER, THERE ARE NO LOCATIONS INDICATED ON THE
 SHEETS.
  
 TENT LOCATIONS ARE NEEDED TO ENSURE SAFE LOCATIONS.IE.
 AWAY FROM ROADWAYS, TOO CLOSE TO BUILDINGS, ETC.
  
 PLEASE PROVIDE THE LOCATIONS
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cthroop Date 2020-06-17 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-16 Cont ID  
Sent By cthroop Date 2020-06-16 Time 16:13 Rev Time 0.00
Received By cthroop Date 2020-06-16 Time 13:05 Sent To  
Notes
***NONE***