Plan Review Details - Permit 20060481
Plan Review Stops For Permit 20060481
Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 2 Status F Date 2020-09-23 Cont ID  
Sent By gpatrie Date 2020-09-23 Time 10:38 Rev Time 0.00
Received By gpatrie Date 2020-09-23 Time 10:35 Sent To  
Notes
2020-09-23 10:38:36LAT & LONG LOCATION ON DRAWING PLACE THE POLE IN THE
 ROADWAY ALSO THE POLE NEED TO BE MOVED EAST TO THE 912
 TH ST PROPERITY LINE AWAY FRON THE WATER LINE LATERALS.
  
 CONTACT: [email protected]

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status F Date 2020-06-22 Cont ID  
Sent By gpatrie Date 2020-06-22 Time 13:14 Rev Time 0.00
Received By gpatrie Date 2020-06-22 Time 13:04 Sent To  
Notes
2020-06-22 13:14:19BLOCK 900 5TH ST
  
 1) ENGINEERING PLANS NOT OVER AERIAL WITH CITY LOCATES
 SHOWN.
 DRAWING NOT SIGNED AND SEALED.
 DRAWING NOT SHOWN IN ANY SCALE.
 ONLY ONE COPY OF DRAWING SUBMITTED NO 11X17.
  
 2) NOUNDER GROUND SURVEY SUBMITTED.
  
 3) NO ABOVE GROUNG SURVEY SUBMITTED.
  
 4) NO ADDRESS LIST PROVIDED.
  
 5) NO RADIUS MAP PROVIDED.
  
 CONTACT: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-25 Cont ID  
Sent By shill Date 2020-10-05 Time 11:10 Rev Time 0.00
Received By shill Date 2020-06-09 Time 11:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-10-05 Cont ID  
Sent By eschneid Date 2020-10-05 Time 14:47 Rev Time 1.00
Received By eschneid Date 2020-10-05 Time 08:56 Sent To  
Notes
2020-10-05 14:49:49INSUFFICIENT - 2ND REVIEW
  
 PERMIT 20060481 AT&T CRAN_RTFL_PBC36_01 4 916 5TH ST
  
 THE PROPOSED POLE LOCATION IS IN A RESIDENTIAL AREA. IN
 ACCORDANCE WITH SECTION 78-411(B)(2) OF THE CITY CODE,
 WHENEVER WIRELESS FACILITIES MUST BE PLACED IN A
 RIGHT-OF-WAY WITH RESIDENTIAL USES ON ONE OR BOTH
 SIDES, NEITHER POLES, EQUIPMENT, ANTENNAS OR OTHER
 STRUCTURES SHALL BE PLACED DIRECTLY IN FRONT OF A
 RESIDENTIAL STRUCTURE. ALL WIRELESS FACILITIES SHALL BE
 LOCATED SUCH THAT VIEWS FROM RESIDENTIAL STRUCTURES ARE
 NOT SIGNIFICANTLY IMPAIRED. THANK YOU FOR MOVING THE
 POLE FROM IN FRONT OF THE RESIDENTIAL STRUCTURE AT 908
 5TH STREET; HOWEVER, THE NEW PROPOSED LOCATION IS NOW
 PROPOSED SUCH THAT IT WILL BE IN FRONT OF A FUTURE
 RESIDENTIAL STRUCTURE AT 916 5TH STREET. SINCE THIS
 SEEMS TO BE YOUR DESIRED LOCATION FOR THE POLE, IN
 ORDER TO COMPLY WITH CITY REQUIREMENTS, THE POLE NEEDS
 TO BE INSTALLED IN THE PARKWAY AREA AT THE PROPERTY
 LINE EXTENDED BETWEEN 908 AND 916 5TH STREET. THE
 PROPERTY LINE NEEDS TO BE CLEARLY SHOWN ON THE SURVEY
 SO THAT STAFF CAN VERIFY LOCATION COMPLIANCE.
  
 THE SURVEY SHOWS THAT THE POLE WILL BE WITHIN FIVE (5)
 FEET OF THE EXISTING WATER CONNECTIONS AND METERS FOR
 THE 916 5TH STREET PROPERTY. THE POLE MAY NOT BE THIS
 CLOSE TO THE WATER LINES AND REINFORCES THE MOVE
 EASTWARD TO THE PROPERTY LINE EXTENDED.
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) ENGINEERING PLAN - NO UPDATED ENGINEERING PLAN WAS
 SUBMITTED.
  
 A. THE ENGINEERING PLANS DID NOT INCLUDE A SCALE. THE
 CITY CODE REQUIRES THE PLANS TO BE DRAWN AT A 10FT,
 20FT, OR 40FT SCALE. PROVIDE THE PLANS AT THE REQUIRED
 SCALE.
  
 B. THE SUBMITTED ENGINEERING PLAN MUST BE BASED ON THE
 SURVEY AND SHOW THE ABOVE AND BELOW GROUND FEATURES.
 THIS INCLUDES THE TREES ALONG THE RIGHT-OF-WAY.
  
 C. THE SIZE OF THE PROPOSED POLE BASE WITHIN THE
 RIGHT-OF-WAY MUST BE SHOWN ON THE ENGINEERING PLAN.
  
 D. YOU ARE REQUIRED TO PROVIDE INFORMATION REGARDING
 EXISTING UTILITY POLES (INCLUDING LIGHT POLES) WITHIN
 50 FEET OF YOUR PROPOSED POLE. THE POLE HEIGHT AND BASE
 DIAMETER SHALL BE INCLUDED. THIS WILL BE USED TO VERIFY
 IF THE PROPOSED 25 FOOT SUPPORT POLE (WITH 5 FOOT
 ANTENNA CANNISTER) HEIGHT COMPLIES WITH THE HEIGHTS OF
 EXISTING UTILITY POLES.
  
 E. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 2) THANK YOU FOR USING A POLE STYLE THAT MEETS THE
 CITY'S CONCEALMENT REQUIREMENTS. AT THIS LOCATION, THE
 CITY REQUIRES THE POLE TO BE EITHER BLACK OR GREEN, NOT
 ITS NATURAL STEEL COLOR. PLEASE SPECIFY THE COLOR YOU
 CHOOSE TO USE ON THE PLANS.
  
 3) EVIDENCE OF INSURANCE COVERAGE - YOU ARE REQUIRED TO
 SUBMIT VERIFICATION OF INSURANCE IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 78-406 OF THE CITY CODE OF
 ORDINANCES. PLEASE REMEMBER THAT THE CERTIFICATE OF
 LIABILITY INSURANCE NEEDS TO BE ISSUED TO THE APPLICANT
 LISTED ON THE COMMUNICATIONS FACILITIES PLACEMENT
 PERMIT APPLICATION - NEW CINGULAR WIRELESS LLC.
  
 4) ELECTRONIC FORMAT OF SUBMITTAL - THE SUBMITTAL WAS
 NOT PROVIDED IN ELECTRONIC FORM. A COPY OF ALL OF THE
 SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC
 FORMAT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By eschneid Date 2020-07-24 Time 11:32 Rev Time 1.00
Received By eschneid Date 2020-07-24 Time 11:32 Sent To  
Notes
2020-07-24 11:36:21PERMIT 20060481 AT&T CRAN_RTFL_PBC36_01 4 916 5TH ST
  
 THE PROPOSED POLE LOCATION IS IN A RESIDENTIAL AREA. IN
 ACCORDANCE WITH SECTION 78-411(B)(2) OF THE CITY CODE,
 WHENEVER WIRELESS FACILITIES MUST BE PLACED IN A
 RIGHT-OF-WAY WITH RESIDENTIAL USES ON ONE OR BOTH
 SIDES, NEITHER POLES, EQUIPMENT, ANTENNAS OR OTHER
 STRUCTURES SHALL BE PLACED DIRECTLY IN FRONT OF A
 RESIDENTIAL STRUCTURE. ALL WIRELESS FACILITIES SHALL BE
 LOCATED SUCH THAT VIEWS FROM RESIDENTIAL STRUCTURES ARE
 NOT SIGNIFICANTLY IMPAIRED. THE SITE PLAN PROVIDED WITH
 THE APPLICATION APPEARS TO CONFLICT WITH THE LOCATIONAL
 REQUIREMENT. ONCE THE REQUIRED SURVEY IS PROVIDED,
 STAFF WILL BE ABLE TO VERIFY COMPLIANCE. IN THE EVENT
 THAT THE POLE IS PROPOSED IN FRONT OF THE RESIDENCE (AS
 INDICATED ON THE SITE PLAN), THEN THE POLE MUST BE
 RELOCATED. STAFF SUGGESTS TO THE WEST AT THE PROPERY
 LINE EXTENDED BETWEEN THE RESIDENCE AND THE NEIGHBORING
 LOT.
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) ENGINEERING PLAN - SIGNED BY A FLORIDA REGISTERED
 ENGINEER
  
 A. THE ENGINEERING PLANS DID NOT INCLUDE A SCALE. THE
 CITY CODE REQUIRES THE PLANS TO BE DRAWN AT A 10FT,
 20FT, OR 40FT SCALE. PROVIDE THE PLANS AT THE REQUIRED
 SCALE.
  
 B. THE SUBMITTED ENGINEERING PLAN MUST BE BASED ON THE
 REQUIRED SURVEYS AND SHOW THE ABOVE AND BELOW GROUND
 FEATURES. THIS INCLUDES THE TREES ALONG THE
 RIGHT-OF-WAY.
  
 C. THE SIZE OF THE PROPOSED POLE BASE WITHIN THE
 RIGHT-OF-WAY MUST BE SHOWN ON THE ENGINEERING PLAN.
  
 2) REPEAT COMMENT: SURVEY OF UNDERGROUND FACILITIES -
 THE BASE OF THE POLE IS BEING INSTALLED UNDERGROUND SO
 THIS IS REQUIRED.
  
 A. THE SURVEY, PREPARED BY A FLORIDA REGISTERED
 SURVEYOR, MUST CLEARLY SHOW THE RIGHT-OF-WAY LINE, THE
 SIDEWALK AND THE UTILITY EASEMENT LISTED ON THE
 ENGINEERING PLANS.
  
 B. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON THE
 SURVEY. IF THE BORE IS PROPOSED WITHIN FIVE (5) FEET OF
 AN EXISTING UTILITY, YOU NEED TO PROVIDE A LETTER FROM
 THAT UTILITY THAT THE PROPOSED BORE DOES NOT INTERFERE
 WITH THE PROVISIONS OF THEIR SERVICES.
  
 C. THE TREES AND THEIR ROOT ZONE NEED TO BE SHOWN. THE
 FIBER BORE NEEDS TO BE CLEARLY SHOWN AVOIDING DAMAGE TO
 THE TREE ROOT ZONES.
 D. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 3) REPEAT COMMENT: SURVEY OF ABOVEGROUND FACILITIES - A
 NEW POLE IS BEING INSTALLED ABOVEGROUND SO THIS IS
 REQUIRED.
  
 A. IDENTIFY ALL ABOVEGROUND FEATURES TO INCLUDE TREES
 ON A SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
  
 B. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN
 THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S
 EXISTING FACILITIES - NO INFORMATION ON EXISTING
 FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE
 PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO
 FACILITIES, THIS SHALL BE NOTED ON THE SURVEY.
  
 C. YOU ARE REQUIRED TO PROVIDE INFORMATION REGARDING
 EXISTING UTILITY POLES (INCLUDING LIGHT POLES) WITHIN
 50 FEET OF YOUR PROPOSED POLE. THE POLE HEIGHT AND BASE
 DIAMETER SHALL BE INCLUDED. THIS WILL BE USED TO VERIFY
 IF THE PROPOSED 25 FOOT SUPPORT POLE HEIGHT COMPLIES
 WITH THE HEIGHTS OF EXISTING UTILITY POLES.
  
 D. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 4) RADIO FREQUENCY INTERFERENCE - NO INFORMATION WAS
 PROVIDED THAT THE PROPOSED FACILITIES WILL NOT CAUSE
 RADIO FREQUENCY INTERFERENCE WITH THE CITY'S PUBLIC
 SAFETY COMMUNICATIONS EQUIPMENT. PROVIDE A STATEMENT
 REGARDING RADIO FREQUENCY INTERFERENCE.
  
 5) THANK YOU FOR USING A POLE STYLE THAT MEETS THE
 CITY'S CONCEALMENT REQUIREMENTS. AT THIS LOCATION, THE
 CITY REQUIRES THE POLE TO BE EITHER BLACK OR GREEN, NOT
 ITS NATURAL STEEL COLOR. PLEASE SPECIFY THE COLOR YOU
 CHOOSE TO USE ON THE PLANS.
  
 6) EVIDENCE OF INSURANCE COVERAGE - YOU ARE REQUIRED TO
 SUBMIT VERIFICATION OF INSURANCE IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 78-406 OF THE CITY CODE OF
 ORDINANCES. PLEASE REMEMBER THAT THE CERTIFICATE OF
 LIABILITY INSURANCE NEEDS TO BE ISSUED TO THE APPLICANT
 LISTED ON THE COMMUNICATIONS FACILITIES PLACEMENT
 PERMIT APPLICATION - NEW CINGULAR WIRELESS LLC.
  
 7) START OF OPERATION - AN ATTESTATION FROM THE
 COMMUNICATIONS FACILITIES SERVICE PROVIDER THAT
 COMMUNICATIONS SERVICES FACILITIES WILL BE INSTALLED
 AND OPERATIONAL ON THE PROPOSED STRUCTURE NO LATER THAN
 NINE MONTHS AFTER THE DATE THE APPLICATION IS APPROVED
 IS REQUIRED. PROVIDE THE REQUIRED ATTESTATION.
  
 8) PUBLIC UTILITY LETTERS, TELEPHONE, NATURAL GAS,
 ELECTRIC SERVICE, AND TELEVISION CABLE - THE PUBLIC
 UTILITY LETTERS WERE NOT PROVIDED. PROVIDE COPIES OF
 THE PUBLIC UTILITY LETTERS FROM ANY PROVIDER WITH
 FACILITIES SHOWN ON THE SURVEY WITHIN FIVE (5) FEET OF
 THE POLE BASE.
  
 9) ELECTRONIC FORMAT OF SUBMITTAL - THE SUBMITTAL WAS
 NOT PROVIDED IN ELECTRONIC FORM. A COPY OF ALL OF THE
 SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC
 FORMAT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  