Plan Review Details - Permit 19100097
Plan Review Stops For Permit 19100097
Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-12-10 09:33:31PERMIT 19100097S TAMARIND AVE SOUTH OF FERN ST.
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) SURVEY OF UNDERGROUND FACILITIES:
 MISSING UTILITY INFORMATION FROM DRAWING, ALSO COPIES
 OF CITY UTILITY DRAWINGS NOT PROVIDED.
  
 2) DRAWING: SH PS-1, A MINIUM OF 36" IS REQUIRED FOR
 ADA. PROVIDE DIMENSION FROM PROPOSED BOX LOCATION AND
 EXISTING STOP SIGN.

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-10-07 09:28:43PERMIT 19100097S TAMARIND AVE SOUTH OF FERN ST.
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) ENGINEERING PLANS:
  
 A. ALL DRAWINGS TO BE SHOWN OVER AERIALS SHOWING ALL
 CITY OF WEST PALM BEACH UTILITIES.
  
 B. SUBMIT COPIES OF ALL AS-BUILT AND UTILITITY LOCATE
 DRAWINGS FROM THE CITY OF WPB.
  
 C. IRRIGATION LINES NOT SHOWN.
  
 2) SURVEY OF UNDERGROUND FACILITIES:
  
 A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON THE
 SURVEY. THE PROVIDED SURVEY SPECIFICALLY STATES THAT NO
 UNDERGROUND UTILITY LOCATES WERE DONE, WHICH DOES NOT
 COMPLY WITH THE CITY CODE REQUIREMENTS.
  
 B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 3) SURVEY OF ABOVEGROUND FACILITIES - A NEW POLE IS
 BEING INSTALLED ABOVEGROUND SO THIS IS REQUIRED.
  
 A. PLEASE NOTE THAT THE SURVEY DOES NOT PROVIDE THE
 SIZE OF THE PROPOSED POLE BASE DIAMETER, WHICH WILL
 NEED TO BE CORRECTED ON THE REVISED SURVEY.
  
 B. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN
 THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S
 EXISTING FACILITIES - NO INFORMATION ON EXISTING
 FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE
 PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO
 FACILITIES, THIS SHALL BE NOTED ON THE SURVEY.
  
 4) ALL RESTORATION PER CITY OF WEST PALM BEACH
 STANDARDS.
  
 5) CONCEALMENT METHODS DESCRIPTIONS - NO CONCEALMENT
 INFORMATION WAS PROVIDED. PLEASE NOTE THAT THE PROPOSED
 SUPPORT POLE DOES NOT MEET THE CITY CONCEALMENT
 STANDARDS OUTLINED IN SECTION 78-411 OF THE CITY CODE.
 PROVIDE PLANS AND NARRATIVE ON HOW THE INSTALLATION
 COMPLIES WITH THE CITY'S CONCEALMENT REQUIREMENT.
  
 6) RESTORATION ESTIMATE - YOU MUST PROVIDE A
 RESTORATION ESTIMATE FOR THE SPECIFIC LOCATION OF THE
 POLE, NOT A GENERIC ESTIMATE THAT IS NOT LINKED TO THE
 SPECIFIC LOCATION AND WORK TO BE DONE.
  
 7) RADIO FREQUENCY INTERFERENCE - NO INFORMATION WAS
 PROVIDED THAT THE PROPOSED FACILITIES WILL NOT CAUSE
 RADIO FREQUENCY INTERFERENCE WITH THE CITY'S PUBLIC
 SAFETY COMMUNICATIONS EQUIPMENT. PROVIDE A STATEMENT
 REGARDING RADIO FREQUENCY INTERFERENCE.
  
 8) EVIDENCE OF INSURANCE COVERAGE
  
 A. THE CERTIFICATE OF LIABILITY INSURANCE LISTS ONLY
 THE CITY OF WEST PALM BEACH AS THE ADDITIONAL INSURED.
 THE CERTIFICATE OF LIABILITY INSURANCE NEEDS TO BE
 REVISED TO NAME THE CITY OF WEST PALM BEACH, ITS
 COMMISSIONERS, OFFICERS, EMPLOYEES AND AGENTS AS
 ADDITIONAL INSURED.
  
 B. THE CERTIFICATE OF LIABILITY INSURANCE STATES THAT
 THE INSTALLATION IS IN ST. LUCIE COUNTY. THE WORK IS
 ACTUALLY WITHIN WEST PALM BEACH AND THE CERTIFICATE OF
 LIABILITY INSURANCE NEEDS TO BE CHANGED TO REFLECT
 THIS.
  
 9) START OF OPERATION - AN ATTESTATION FROM THE
 COMMUNICATIONS FACILITIES SERVICE PROVIDER THAT
 COMMUNICATIONS SERVICES FACILITIES WILL BE INSTALLED
 AND OPERATIONAL ON THE PROPOSED STRUCTURE NO LATER THAN
 NINE MONTHS AFTER THE DATE THE APPLICATION IS APPROVED
 IS REQUIRED. PROVIDE THE REQUIRED ATTESTATION.
  
  
 10) ELECTRONIC FORMAT OF SUBMITTAL - THE SUBMITTAL WAS
 NOT PROVIDED IN ELECTRONIC FORM. A COPY OF ALL OF THE
 SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC
 FORMAT.
  
 11) PROOF OF MAILING NOTICE TO OWNERS, ONE COPY OF
 ADDRESS LIST OF PROPERTY OWNER'S ADDRESSES WITHIN 250
 FEET AND ONE COPY OF RADIUS MAP PROVIDED BY THE PAPA
 SHOWING THOSE PROPERTIES WITHIN 250 FEET OF AFFECTED
 RIGHTS-OF-WAY - A COPY OF THE RADIUS MAP WAS NOT
 SUBMITTED. THE OWNER'S ADDRESS LIST, WHILE SUBMITTED IS
 SUCH A SMALL FONT THAT IT IS NOT EASILY READABLE.
 PLEASE PROVIDE THE RADIUS MAP FROM PAPA AND THE ADDRESS
 LIST AT A BIGGER, READABLE FONT.
  
 12) NO WIND LOAD CALCULATIONS WERE PROVIDED.
  
 CONTACT GORDON PATRIE @ (561) 494-1082
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-12-18 Cont ID  
Sent By eschneid Date 2019-12-18 Time 16:33 Rev Time 0.25
Received By eschneid Date 2019-12-18 Time 15:53 Sent To  
Notes
2019-12-18 16:33:40INSUFFICIENT - DO NOT RESUBMIT IF SURVEY PREPARED BY
 FLORIDA LICENSED SURVEYOR SHOWS POLE ON PRIVATE
 PROPERTY
  
 PERMIT 19100097 SPRINT MI90XS888-1 412 S. TAMARIND
 2ND REVIEW
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) REVISED COMMENT: ENGINEERING PLAN
  
 A. THE SUBMITTED ENGINEERING PLAN MUST BE BASED ON THE
 REQUIRED SURVEYS. NOTE: EVEN THOUGH YOUR SURVEY EXHIBIT
 SHEET DOES NOT QUALIFY AS A SURVEY, IT SHOWS THE
 EXISTING POLE LOCATION ON PRIVATE PROPERTY; THEREFORE,
 THIS IS NOT A RIGHT-OF-WAY INSTALLATION. THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS ONLY PERMIT THE
 ATTACHMENT OF NON-CONCEALED WIRELESS EQUIPMENT ON HIGH
 VOLTAGE ELECTRIC POWER TRANSMISSION TOWERS AND LIGHT
 STANCHIONS NOT LOCATED IN PUBLIC RIGHTS-OF-WAY. THE
 EXISTING POLE IS NEITHER OF THESE, SO YOU MAY NOT MOUNT
 AN ANTENNA TO IT.
  
 B. IF THIS IS A MOUNTING ON AN EXISTING POLE, THEN YOU
 MUST SUBMIT A STRUCTURAL CAPACITY REPORT FOR THE
 SUPPORT STRUCTURE, AS EVIDENCED BY A SEALED STATEMENT
 FROM A STRUCTURAL ENGINEER LICENSED IN THE STATE OF
 FLORIDA, THAT THE POLE CAN SUPPORT THE PROPOSED
 ELEMENTS. THIS WAS NOT PROVIDED.
  
 C. YOU MAY NOT INSTALL GROUND EQUIPMENT IN A
 RIGHT-OF-WAY FOR AN ANTENNA INSTALLATION ON PRIVATE
 PROPERTY.
  
 2) REPEAT COMMENT: SURVEY OF UNDERGROUND FACILITIES -
 THE BASE OF THE POLE IS BEING INSTALLED UNDERGROUND SO
 THIS IS REQUIRED.
  
 A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON A
 SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
  
 B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 3) REPEAT COMMENT: SURVEY OF ABOVEGROUND FACILITIES - A
 NEW POLE IS BEING USED OR INSTALLED ABOVEGROUND SO THIS
 IS REQUIRED. PLEASE NOTE THAT AS PART OF THE
 APPLICATION YOU WILL NEED TO PROVIDE THE CONSENT FROM
 FPL FOR THE ATTACHMENT TO THEIR POLE. CONTRARY TO THE
 RESPONSE TO THESE COMMENTS THE CONSENT WAS NOT
 INCLUDED. OWNERSHIP INFORMATION MUST BE SHOWN ON THE
 SURVEY.
  
 A. IDENTIFY ALL ABOVEGROUND FEATURES TO INCLUDE TREES
 ON A SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
 SHEET SE-1 IS NOT A SURVEY PREPARED BY A FLORIDA
 LICENSED SURVEYOR, NOR DOES IT SHOW ALL THE ABOVEGROUND
 FEATURES.
  
 B. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN
 THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S
 EXISTING FACILITIES - NO INFORMATION ON EXISTING
 FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE
 PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO
 FACILITIES, THIS SHALL BE NOTED ON THE SURVEY.
  
 C. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 4) REPEAT COMMENT: CONCEALMENT METHODS DESCRIPTIONS -
 NO CONCEALMENT INFORMATION WAS PROVIDED. REGARDLESS OF
 IF THIS IS A NEW POLE OR ATTACHMENT TO AN EXISTING
 POLE, THE EXTERIOR CABLES, NON-CONCEALED ANTENNAS AND A
 REMOTE EQUIPMENT CABINET DO NOT COMPLY WITH THE
 CONCEALMENT STANDARDS OUTLINED IN SECTION 78-411 OF THE
 CITY CODE. THE POLE ELEVATION MUST INCLUDE ALL THE
 DIMENSIONS. PLEASE NOTE THAT NON-CONCEALED ATTACHMENTS
 ARE ONLY PERMITTED ON ELECTRICAL TRANSMISSION POLES AND
 LIGHT POLES, WHICH THIS POLE IS NOT.
  
 5) REPEAT COMMENT: CONSTRUCTION TIMETABLE - YOU MUST
 PROVIDE AN ESTIMATED TIMETABLE FOR CONSTRUCTION OF THE
 PROJECT.
  
 6) REPEAT COMMENT: RESTORATION ESTIMATE - YOU MUST
 PROVIDE A RESTORATION ESTIMATE, WHICH IS THE COST FOR
 THE RESTORATION THAT YOU LIST ON SHEET R-1. THE NOTES
 ON SHEET R-1 MUST BE UPDATED TO NOT REFERENCE THE CITY
 OF FORT LAUDERDALE REQUIREMENTS..
  
 7) REPEAT COMMENT: EVIDENCE OF INSURANCE COVERAGE - YOU
 ARE REQUIRED TO SUBMIT VERIFICATION OF INSURANCE IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 78-406 OF THE
 CITY CODE OF ORDINANCES.
  
 8) REPEAT COMMENT: START OF OPERATION - AN ATTESTATION
 FROM THE COMMUNICATIONS FACILITIES SERVICE PROVIDER
 THAT COMMUNICATIONS SERVICES FACILITIES WILL BE
 INSTALLED AND OPERATIONAL ON THE PROPOSED STRUCTURE NO
 LATER THAN NINE MONTHS AFTER THE DATE THE APPLICATION
 IS APPROVED IS REQUIRED. PROVIDE THE REQUIRED
 ATTESTATION.
  
 9) REPEAT COMMENT: PUBLIC UTILITY LETTERS, TELEPHONE,
 NATURAL GAS, ELECTRIC SERVICE, AND TELEVISION CABLE -
 THE PUBLIC UTILITY LETTERS WERE NOT PROVIDED. PROVIDE
 COPIES OF THE PUBLIC UTILITY LETTERS.
  
 10) REPEAT COMMENT: POLE OWNER APPROVAL - THE APPROVAL
 FROM THE OWNER OF THE POLE PERMITTING THE INSTALLATION
 OF A FACILITY WAS NOT PROVIDED. PLEASE NOTE THAT IF
 THIS IS BEING INSTALLED ON A CITY POLE, THEN FEE IS
 REQUIRED TO BE PAID TO THE CITY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-07 Cont ID  
Sent By eschneid Date 2019-10-07 Time 18:13 Rev Time 0.50
Received By eschneid Date 2019-10-07 Time 17:16 Sent To  
Notes
2019-10-07 18:16:40INSUFFICIENT
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) ENGINEERING PLAN
  
 A. THE SUBMITTED ENGINEERING PLAN MUST BE BASED ON THE
 REQUIRED SURVEYS.
  
 B. THERE IS A DISCREPANCY IN YOUR APPLICATION AND PLANS
 AS TO WHETHER THIS IS A NEW POLE OR MOUNTING ON AN
 EXISTING POLE.
  
 C. IF THIS IS A NEW POLE, THEN THE SIZE OF THE PROPOSED
 POLE BASE WITHIN THE RIGHT-OF-WAY MUST BE SHOWN ON THE
 ENGINEERING PLAN.
  
 D. IF THIS IS A MOUNTING ON AN EXISTING POLE, THEN YOU
 MUST SUBMIT A STRUCTURAL CAPACITY REPORT FOR THE
 SUPPORT STRUCTURE, AS EVIDENCED BY A SEALED STATEMENT
 FROM A STRUCTURAL ENGINEER LICENSED IN THE STATE OF
 FLORIDA, THAT THE POLE CAN SUPPORT THE PROPOSED
 ELEMENTS.
  
 2) SURVEY OF UNDERGROUND FACILITIES - THE BASE OF THE
 POLE IS BEING INSTALLED UNDERGROUND SO THIS IS
 REQUIRED.
  
 A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON A
 SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
  
 B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 3) SURVEY OF ABOVEGROUND FACILITIES - A NEW POLE IS
 BEING USED OR INSTALLED ABOVEGROUND SO THIS IS
 REQUIRED. PLEASE NOTE THAT YOU ARE REQUIRED TO VERIFY
 THE POLE OWNERSHIP AND INCLUDE THE INFORMATION ON THE
 SURVEY.
  
 A. IDENTIFY ALL ABOVEGROUND FEATURES TO INCLUDE TREES
 ON A SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
  
 B. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN
 THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S
 EXISTING FACILITIES - NO INFORMATION ON EXISTING
 FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE
 PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO
 FACILITIES, THIS SHALL BE NOTED ON THE SURVEY.
  
 C. YOU ARE REQUIRED TO PROVIDE INFORMATION REGARDING
 EXISTING UTILITY POLES (INCLUDING LIGHT POLES) WITHIN
 50 FEET OF YOUR PROPOSED POLE. THE POLE HEIGHT AND BASE
 DIAMETER SHALL BE INCLUDED. PLEASE NOTE: THE SUPPORT
 POLE INCLUDED WITH THIS APPLICATION IS 43 FEET ABOVE
 GRADE IN HEIGHT. WITHOUT THE INFORMATION REGARDING THE
 SURROUNDING POLE HEIGHTS, STAFF CANNOT DETERMINE IF IT
 COMPLIES WITH THE HEIGHT STANDARDS LISTED IN SECTION
 78-411(G)(1) OF THE CITY CODE.
  
 D. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 4) CONCEALMENT METHODS DESCRIPTIONS - NO CONCEALMENT
 INFORMATION WAS PROVIDED. REGARDLESS OF IF THIS IS A
 NEW POLE OR ATTACHMENT TO AN EXISTING POLE, THE
 EXTERIOR CABLES, NON-CONCEALED ANTENNAS AND A REMOTE
 EQUIPMENT CABINET DO NOT COMPLY WITH THE CONCEALMENT
 STANDARDS OUTLINED IN SECTION 78-411 OF THE CITY CODE.
 THE POLE ELEVATION MUST INCLUDE ALL THE DIMENSIONS.
 PLEASE NOTE THAT NON-CONCEALED ATTACHMENTS ARE ONLY
 PERMITTED ON ELECTRICAL TRANSMISSION POLES AND LIGHT
 POLES, WHICH THIS POLE IS NOT.
  
 5) CONSTRUCTION TIMETABLE - YOU MUST PROVIDE AN
 ESTIMATED TIMETABLE FOR CONSTRUCTION OF THE PROJECT.
  
 6) RESTORATION ESTIMATE - YOU MUST PROVIDE A
 RESTORATION ESTIMATE.
  
 7) RADIO FREQUENCY INTERFERENCE - NO INFORMATION WAS
 PROVIDED THAT THE PROPOSED FACILITIES WILL NOT CAUSE
 RADIO FREQUENCY INTERFERENCE WITH THE CITY'S PUBLIC
 SAFETY COMMUNICATIONS EQUIPMENT. PROVIDE A STATEMENT
 REGARDING RADIO FREQUENCY INTERFERENCE.
  
 8) EVIDENCE OF INSURANCE COVERAGE - YOU ARE REQUIRED TO
 SUBMIT VERIFICATION OF INSURANCE IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 78-406 OF THE CITY CODE OF
 ORDINANCES.
  
 9) START OF OPERATION - AN ATTESTATION FROM THE
 COMMUNICATIONS FACILITIES SERVICE PROVIDER THAT
 COMMUNICATIONS SERVICES FACILITIES WILL BE INSTALLED
 AND OPERATIONAL ON THE PROPOSED STRUCTURE NO LATER THAN
 NINE MONTHS AFTER THE DATE THE APPLICATION IS APPROVED
 IS REQUIRED. PROVIDE THE REQUIRED ATTESTATION.
  
 10) PUBLIC UTILITY LETTERS, TELEPHONE, NATURAL GAS,
 ELECTRIC SERVICE, AND TELEVISION CABLE - THE PUBLIC
 UTILITY LETTERS WERE NOT PROVIDED. PROVIDE COPIES OF
 THE PUBLIC UTILITY LETTERS.
  
 11) ELECTRONIC FORMAT OF SUBMITTAL - THE SUBMITTAL WAS
 NOT PROVIDED IN ELECTRONIC FORM. A COPY OF ALL OF THE
 SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC
 FORMAT.
  
 12) PROVIDER CLARIFICATION - ON THE COMMUNICATIONS
 FACILITIES PLACEMENT PERMIT APPLICATION, YOU MARKED
 THAT THIS IS A PASS THROUGH PROVIDER, YET YOU HAVE ALSO
 MARKED THAT YOU ARE A COMMUNICATION SERVICES PROVIDER
 THAT REMITS TAXES TO THE CITY. BY CITY DEFINITION, YOU
 CANNOT BE BOTH. IF YOU ARE A PASS THROUGH PROVIDER, YOU
 ARE REQUIRED TO PAY AN APPLICATION FEE TO THE CITY.
  
 13) POLE OWNER APPROVAL - THE APPROVAL FROM THE OWNER
 OF THE POLE PERMITTING THE INSTALLATION OF A FACILITY
 WAS NOT PROVIDED. PLEASE NOTE THAT IF THIS IS BEING
 INSTALLED ON A CITY POLE, THEN FEE IS REQUIRED TO BE
 PAID TO THE CITY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  