Plan Review Details - Permit 19100092
Plan Review Stops For Permit 19100092
Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 2 Status F Date 2019-12-10 Cont ID  
Sent By gpatrie Date 2019-12-10 Time 11:16 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2019-12-10 11:01:29PERMIT 19100092 FERN ST EAST OF QUADRILLE. (QUADRILLE
 BLVD IS A FDOT ROADWAY)
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) ENGINEERING PLANS:
  
 A. SUBMIT COPIES OF ALL AS-BUILT AND UTILITITY LOCATE
 DRAWINGS FROM THE CITY OF WPB NOT PROVIDED.
  
 B. CITY UTILITIES NOT LOCATED.
  
 2) POLE LOCATION IS IN SITE TRIANGLE OF DRIVEWAY.
  
 A. POLE DESIGN DOES NOT MEET CITY STEALTH REQUIREMENTS.
  
 CONTACT GORDON PATRIE @ (561) 494-1082
 [email protected]

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-10-07 09:07:05PERMIT 19100092 FERN ST EAST OF QUADRILLE. (QUADRILLE
 BLVD IS A FDOT ROADWAY)
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) ENGINEERING PLANS:
  
 A. ALL DRAWINGS TO BE SHOWN OVER AERIALS SHOWING ALL
 CITY OF WEST PALM BEACH UTILITIES.
  
 B. SUBMIT COPIES OF ALL AS-BUILT AND UTILITITY LOCATE
 DRAWINGS FROM THE CITY OF WPB.
  
 C. IRRIGATION LINES NOT SHOWN.
  
 2) SURVEY OF UNDERGROUND FACILITIES:
  
 A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON THE
 SURVEY. THE PROVIDED SURVEY SPECIFICALLY STATES THAT NO
 UNDERGROUND UTILITY LOCATES WERE DONE, WHICH DOES NOT
 COMPLY WITH THE CITY CODE REQUIREMENTS.
  
 B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 3) SURVEY OF ABOVEGROUND FACILITIES - A NEW POLE IS
 BEING INSTALLED ABOVEGROUND SO THIS IS REQUIRED.
  
 A. PLEASE NOTE THAT THE SURVEY DOES NOT PROVIDE THE
 SIZE OF THE PROPOSED POLE BASE DIAMETER, WHICH WILL
 NEED TO BE CORRECTED ON THE REVISED SURVEY.
  
 B. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN
 THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S
 EXISTING FACILITIES - NO INFORMATION ON EXISTING
 FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE
 PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO
 FACILITIES, THIS SHALL BE NOTED ON THE SURVEY.
  
 4) ALL RESTORATION PER CITY OF WEST PALM BEACH
 STANDARDS.
  
 5) CONCEALMENT METHODS DESCRIPTIONS - NO CONCEALMENT
 INFORMATION WAS PROVIDED. PLEASE NOTE THAT THE PROPOSED
 SUPPORT POLE DOES NOT MEET THE CITY CONCEALMENT
 STANDARDS OUTLINED IN SECTION 78-411 OF THE CITY CODE.
 PROVIDE PLANS AND NARRATIVE ON HOW THE INSTALLATION
 COMPLIES WITH THE CITY'S CONCEALMENT REQUIREMENT.
  
 6) RESTORATION ESTIMATE - YOU MUST PROVIDE A
 RESTORATION ESTIMATE FOR THE SPECIFIC LOCATION OF THE
 POLE, NOT A GENERIC ESTIMATE THAT IS NOT LINKED TO THE
 SPECIFIC LOCATION AND WORK TO BE DONE.
  
 7) RADIO FREQUENCY INTERFERENCE - NO INFORMATION WAS
 PROVIDED THAT THE PROPOSED FACILITIES WILL NOT CAUSE
 RADIO FREQUENCY INTERFERENCE WITH THE CITY'S PUBLIC
 SAFETY COMMUNICATIONS EQUIPMENT. PROVIDE A STATEMENT
 REGARDING RADIO FREQUENCY INTERFERENCE.
  
 8) EVIDENCE OF INSURANCE COVERAGE
  
 A. THE CERTIFICATE OF LIABILITY INSURANCE LISTS ONLY
 THE CITY OF WEST PALM BEACH AS THE ADDITIONAL INSURED.
 THE CERTIFICATE OF LIABILITY INSURANCE NEEDS TO BE
 REVISED TO NAME THE CITY OF WEST PALM BEACH, ITS
 COMMISSIONERS, OFFICERS, EMPLOYEES AND AGENTS AS
 ADDITIONAL INSURED.
  
 B. THE CERTIFICATE OF LIABILITY INSURANCE STATES THAT
 THE INSTALLATION IS IN ST. LUCIE COUNTY. THE WORK IS
 ACTUALLY WITHIN WEST PALM BEACH AND THE CERTIFICATE OF
 LIABILITY INSURANCE NEEDS TO BE CHANGED TO REFLECT
 THIS.
  
 9) START OF OPERATION - AN ATTESTATION FROM THE
 COMMUNICATIONS FACILITIES SERVICE PROVIDER THAT
 COMMUNICATIONS SERVICES FACILITIES WILL BE INSTALLED
 AND OPERATIONAL ON THE PROPOSED STRUCTURE NO LATER THAN
 NINE MONTHS AFTER THE DATE THE APPLICATION IS APPROVED
 IS REQUIRED. PROVIDE THE REQUIRED ATTESTATION.
  
  
 10) ELECTRONIC FORMAT OF SUBMITTAL - THE SUBMITTAL WAS
 NOT PROVIDED IN ELECTRONIC FORM. A COPY OF ALL OF THE
 SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC
 FORMAT.
  
 11) PROOF OF MAILING NOTICE TO OWNERS, ONE COPY OF
 ADDRESS LIST OF PROPERTY OWNER'S ADDRESSES WITHIN 250
 FEET AND ONE COPY OF RADIUS MAP PROVIDED BY THE PAPA
 SHOWING THOSE PROPERTIES WITHIN 250 FEET OF AFFECTED
 RIGHTS-OF-WAY - A COPY OF THE RADIUS MAP WAS NOT
 SUBMITTED. THE OWNER'S ADDRESS LIST, WHILE SUBMITTED IS
 SUCH A SMALL FONT THAT IT IS NOT EASILY READABLE.
 PLEASE PROVIDE THE RADIUS MAP FROM PAPA AND THE ADDRESS
 LIST AT A BIGGER, READABLE FONT.
  
 12) NO WIND LOAD CALCULATIONS WERE PROVIDED.
  
 CONTACT GORDON PATRIE @ (561) 494-1082
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-12-18 Cont ID  
Sent By eschneid Date 2019-12-18 Time 13:50 Rev Time 0.25
Received By eschneid Date 2019-12-13 Time 16:06 Sent To  
Notes
2019-12-18 13:50:28INSUFFICIENT
  
 PERMIT 19100092 SPRINT MI90XSR04-F 429 FERN ST
 2ND REVIEW
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) REPEAT COMMENT: ENGINEERING PLAN
  
 A. THE SUBMITTED ENGINEERING PLAN MUST BE BASED ON THE
 REQUIRED SURVEYS. NOTE: EVEN THOUGH YOUR SURVEY EXHIBIT
 SHEET DOES NOT QUALIFY AS A SURVEY, IT SHOWS THE
 PROPOSED POLE LOCATION IN A DIFFERENT LOCATION FROM THE
 ENGINEERING PLANS (NEITHER OF WHICH COMPLIES WITH
 COMMENT C BELOW).
  
 B. THE SIZE OF THE PROPOSED POLE BASE WITHIN THE
 RIGHT-OF-WAY MUST BE SHOWN ON THE ENGINEERING PLAN.
  
 C. PLEASE NOTE THAT THE NEW POLES ARE TO BE LOCATED SO
 AS TO ALIGN WITH EXISTING POLES IN THE RIGHT-OF-WAY.
 THE PROPOSED POLE NEEDS TO BE LOCATED CLOSER TO THE
 CURB ALIGNED WITH THE LIGHT POLE TO THE EAST (AND THE
 TREES IN THE RIGHT-OF-WAY).
  
 2) REPEAT COMMENT: SURVEY OF UNDERGROUND FACILITIES -
 THE BASE OF THE POLE IS BEING INSTALLED UNDERGROUND SO
 THIS IS REQUIRED.
  
 A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON A
 SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR. SHEET
 SE-1 IS NOT A SURVEY PREPARED BY A FLORIDA LICENSED
 SURVEYOR, NOR DOES IT SHOW THE UNDERGROUND UTILITIES.
  
 B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 3) REPEAT COMMENT: SURVEY OF ABOVEGROUND FACILITIES - A
 NEW POLE IS BEING INSTALLED ABOVEGROUND SO THIS IS
 REQUIRED.
  
 A. IDENTIFY ALL ABOVEGROUND FEATURES TO INCLUDE TREES
 ON A SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
 SHEET SE-1 IS NOT A SURVEY PREPARED BY A FLORIDA
 LICENSED SURVEYOR, NOR DOES IT SHOW ALL THE ABOVEGROUND
 FEATURES.
  
 B. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN
 THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S
 EXISTING FACILITIES - NO INFORMATION ON EXISTING
 FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE
 PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO
 FACILITIES, THIS SHALL BE NOTED ON THE SURVEY.
  
 C. YOU ARE REQUIRED TO PROVIDE INFORMATION REGARDING
 EXISTING UTILITY POLES (INCLUDING LIGHT POLES) WITHIN
 50 FEET OF YOUR PROPOSED POLE. THE POLE HEIGHT AND BASE
 DIAMETER SHALL BE INCLUDED. PLEASE NOTE: THE SUPPORT
 POLE INCLUDED WITH THIS APPLICATION IS 35 FEET ABOVE
 GRADE IN HEIGHT, WHICH DOES NOT APPEAR TO COMPLY WITH
 THE HEIGHT STANDARDS LISTED IN SECTION 78-411(G)(1) OF
 THE CITY CODE.
  
 D. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 4) REPEAT COMMENT: CONCEALMENT METHODS DESCRIPTIONS -
 NO CONCEALMENT INFORMATION WAS PROVIDED. PLEASE NOTE
 THAT THE PROPOSED SUPPORT POLE, INCLUDING THE ANTENNA,
 EQUIPMENT AND METER ATTACHMENTS, DOES NOT MEET THE CITY
 CONCEALMENT STANDARDS OUTLINED IN SECTION 78-411 OF THE
 CITY CODE. THE POLE ELEVATION MUST INCLUDE ALL THE
 DIMENSIONS. NOTE: THE POLE AND WIRELESS COMMUNICATION
 EQUIPMENT MAY NOT BE TWO INSTALLATIONS, BUT MUST RATHER
 BE ONE INTEGRATED INSTALLATION. YOU ARE NOT ATTACHING
 EQUIPMENT TO AN EXISTING POLE AS STATED IN THE RESPONSE
 SINCE THERE IS NO EXISTING POLE. YOU MUST SUBMIT A
 CONCEALED DESIGN.
  
 5) REPEAT COMMENT: CONSTRUCTION TIMETABLE - YOU MUST
 PROVIDE AN ESTIMATED TIMETABLE FOR CONSTRUCTION OF THE
 PROJECT.
  
 6) REPEAT COMMENT: RESTORATION ESTIMATE - YOU MUST
 PROVIDE A RESTORATION ESTIMATE, WHICH IS THE COST FOR
 THE RESTORATION THAT YOU LIST ON SHEET R-1. THE NOTES
 ON SHEET R-1 MUST BE UPDATED TO NOT REFERENCE THE CITY
 OF FORT LAUDERDALE REQUIREMENTS.
  
 7) REPEAT COMMENT: EVIDENCE OF INSURANCE COVERAGE - YOU
 ARE REQUIRED TO SUBMIT VERIFICATION OF INSURANCE IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 78-406 OF THE
 CITY CODE OF ORDINANCES.
  
 8) REPEAT COMMENT: START OF OPERATION - AN ATTESTATION
 FROM THE COMMUNICATIONS FACILITIES SERVICE PROVIDER
 THAT COMMUNICATIONS SERVICES FACILITIES WILL BE
 INSTALLED AND OPERATIONAL ON THE PROPOSED STRUCTURE NO
 LATER THAN NINE MONTHS AFTER THE DATE THE APPLICATION
 IS APPROVED IS REQUIRED. PROVIDE THE REQUIRED
 ATTESTATION.
  
 9) REPEAT COMMENT: PUBLIC UTILITY LETTERS, TELEPHONE,
 NATURAL GAS, ELECTRIC SERVICE, AND TELEVISION CABLE -
 THE PUBLIC UTILITY LETTERS WERE NOT PROVIDED. PROVIDE
 COPIES OF THE PUBLIC UTILITY LETTERS.
  
 10) REPEAT COMMENT: PROVIDER CLARIFICATION - ON THE
 COMMUNICATIONS FACILITIES PLACEMENT PERMIT APPLICATION,
 YOU MARKED THAT THIS IS A PASS THROUGH PROVIDER, YET
 YOU HAVE ALSO MARKED THAT YOU ARE A COMMUNICATION
 SERVICES PROVIDER THAT REMITS TAXES TO THE CITY. BY
 CITY DEFINITION, YOU CANNOT BE BOTH. IF YOU ARE A PASS
 THROUGH PROVIDER, YOU ARE REQUIRED TO PAY AN
 APPLICATION FEE TO THE CITY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-07 Cont ID  
Sent By eschneid Date 2019-10-07 Time 17:14 Rev Time 0.50
Received By eschneid Date 2019-10-07 Time 17:14 Sent To  
Notes
2019-10-07 17:14:46INSUFFICIENT
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) ENGINEERING PLAN
  
 A. THE SUBMITTED ENGINEERING PLAN MUST BE BASED ON THE
 REQUIRED SURVEYS.
  
 B. THE SIZE OF THE PROPOSED POLE BASE WITHIN THE
 RIGHT-OF-WAY MUST BE SHOWN ON THE ENGINEERING PLAN.
  
 C. PLEASE NOTE THAT THE NEW POLES ARE TO BE LOCATED SO
 AS TO ALIGN WITH EXISTING POLES IN THE RIGHT-OF-WAY.
 THE PROPOSED POLE NEEDS TO BE LOCATED CLOSER TO THE
 CURB ALIGNED WITH THE LIGHT POLE TO THE EAST (AND THE
 TREES IN THE RIGHT-OF-WAY).
  
 2) SURVEY OF UNDERGROUND FACILITIES - THE BASE OF THE
 POLE IS BEING INSTALLED UNDERGROUND SO THIS IS
 REQUIRED.
  
 A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON A
 SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
  
 B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 3) SURVEY OF ABOVEGROUND FACILITIES - A NEW POLE IS
 BEING INSTALLED ABOVEGROUND SO THIS IS REQUIRED.
  
 A. IDENTIFY ALL ABOVEGROUND FEATURES TO INCLUDE TREES
 ON A SURVEY PREPARED BY A FLORIDA LICENSED SURVEYOR.
  
 B. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN
 THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S
 EXISTING FACILITIES - NO INFORMATION ON EXISTING
 FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE
 PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO
 FACILITIES, THIS SHALL BE NOTED ON THE SURVEY.
  
 C. YOU ARE REQUIRED TO PROVIDE INFORMATION REGARDING
 EXISTING UTILITY POLES (INCLUDING LIGHT POLES) WITHIN
 50 FEET OF YOUR PROPOSED POLE. THE POLE HEIGHT AND BASE
 DIAMETER SHALL BE INCLUDED. PLEASE NOTE: THE SUPPORT
 POLE INCLUDED WITH THIS APPLICATION IS 35 FEET ABOVE
 GRADE IN HEIGHT, WHICH DOES NOT COMPLY WITH THE HEIGHT
 STANDARDS LISTED IN SECTION 78-411(G)(1) OF THE CITY
 CODE.
  
 D. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 4) CONCEALMENT METHODS DESCRIPTIONS - NO CONCEALMENT
 INFORMATION WAS PROVIDED. PLEASE NOTE THAT THE PROPOSED
 SUPPORT POLE, INCLUDING THE ANTENNA, EQUIPMENT AND
 METER ATTACHMENTS, DOES NOT MEET THE CITY CONCEALMENT
 STANDARDS OUTLINED IN SECTION 78-411 OF THE CITY CODE.
 THE POLE ELEVATION MUST INCLUDE ALL THE DIMENSIONS.
  
 5) CONSTRUCTION TIMETABLE - YOU MUST PROVIDE AN
 ESTIMATED TIMETABLE FOR CONSTRUCTION OF THE PROJECT.
  
 6) RESTORATION ESTIMATE - YOU MUST PROVIDE A
 RESTORATION ESTIMATE.
  
 7) RADIO FREQUENCY INTERFERENCE - NO INFORMATION WAS
 PROVIDED THAT THE PROPOSED FACILITIES WILL NOT CAUSE
 RADIO FREQUENCY INTERFERENCE WITH THE CITY'S PUBLIC
 SAFETY COMMUNICATIONS EQUIPMENT. PROVIDE A STATEMENT
 REGARDING RADIO FREQUENCY INTERFERENCE.
  
 8) EVIDENCE OF INSURANCE COVERAGE - YOU ARE REQUIRED TO
 SUBMIT VERIFICATION OF INSURANCE IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 78-406 OF THE CITY CODE OF
 ORDINANCES.
  
 9) START OF OPERATION - AN ATTESTATION FROM THE
 COMMUNICATIONS FACILITIES SERVICE PROVIDER THAT
 COMMUNICATIONS SERVICES FACILITIES WILL BE INSTALLED
 AND OPERATIONAL ON THE PROPOSED STRUCTURE NO LATER THAN
 NINE MONTHS AFTER THE DATE THE APPLICATION IS APPROVED
 IS REQUIRED. PROVIDE THE REQUIRED ATTESTATION.
  
 10) PUBLIC UTILITY LETTERS, TELEPHONE, NATURAL GAS,
 ELECTRIC SERVICE, AND TELEVISION CABLE - THE PUBLIC
 UTILITY LETTERS WERE NOT PROVIDED. PROVIDE COPIES OF
 THE PUBLIC UTILITY LETTERS.
  
 11) ELECTRONIC FORMAT OF SUBMITTAL - THE SUBMITTAL WAS
 NOT PROVIDED IN ELECTRONIC FORM. A COPY OF ALL OF THE
 SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC
 FORMAT.
  
 12) PROVIDER CLARIFICATION - ON THE COMMUNICATIONS
 FACILITIES PLACEMENT PERMIT APPLICATION, YOU MARKED
 THAT THIS IS A PASS THROUGH PROVIDER, YET YOU HAVE ALSO
 MARKED THAT YOU ARE A COMMUNICATION SERVICES PROVIDER
 THAT REMITS TAXES TO THE CITY. BY CITY DEFINITION, YOU
 CANNOT BE BOTH. IF YOU ARE A PASS THROUGH PROVIDER, YOU
 ARE REQUIRED TO PAY AN APPLICATION FEE TO THE CITY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  