Plan Review Details - Permit 13060440
Plan Review Stops For Permit 13060440
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-25 Cont ID  
Sent By dharvey Date 2013-06-25 Time 14:00 Rev Time 0.00
Received By dharvey Date 2013-06-25 Time 13:08 Sent To ENG
Notes
2013-06-25 14:00:30PERMIT ISSUED WITH THE FOLLOWING PROVISO:
 LOW VOLTAGE DATA CONDUCTORS ARE REQUIRED TO BE
 SEPARATED FROM THE POWER CONDUCTORS WITHIN A
 NONCONDUCTIVE SLEEVE. NEC 725.136 (D)(2)
  
 80 AMP MAIN BREAKER IS THE MAXIMUM ALLOWED FOR LISTED
 SERVICE CONDUCTORS. NEC T310.16
  
 RL
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-07-11 Cont ID  
Sent By mgonzale Date 2013-07-11 Time   Rev Time 0.50
Received By mgonzale Date 2013-06-28 Time   Sent To I
Notes
2013-06-28 15:15:42COMMENTS
  
 #1 PROVIDE SIGNED PALM BEACH COUNTY ROW CONSTRUCTION
 PERMIT.
 REF PERMIT # RW31504-0613.
  
 #2 PROVIDE AS-BUILTS AND JOB COMPLETION CERTIFICATION
 TO THE CITY OF WPB.
  
 #3 PROVIDE A 24 HOUR EMERGENCY AND MAINTENANCE CONTACT
 INFO.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-11 Cont ID  
Sent By mgonzale Date 2013-07-11 Time 10:03 Rev Time 0.00
Received By mgonzale Date 2013-06-14 Time 13:17 Sent To I
Notes
2013-06-14 13:19:05TO ELEC (ENGINEERING REQUESTED ELEC REVIEW FIRST)
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved