Inspection Details
INSPECTION DETAILS FOR PERMIT 18030320
Permit Number 18030320 Owner Name WEST PALM BEACH CITY OF
Permit Type ELEC Permit Address BLOCK 900 FERN ST
Inspection Type EARLY POWER RELEASE-1 City WEST PALM BEACH
Inspect Area   Inspector 8156
Request Date 2018-03-07 Scheduled Date 2018-03-08
Instructions POWER FOR STREET LIGHTS PP
Contract Info  
Contractor   Inspect Date 2018-03-08
Result F Fail Code F11
Comments  
Work Time   Confirm 484246
Fee ID  
Inspector Notes
Date Text
2018-03-08 13:56:26NEUTRAL CONDUCTOR NOT BONDED TO GEC
 250.24A1
  
 CANT LOCATE SECOND GROUND ROD?
  
 NO DUCT SEAL IN CONDUITS 300.5G AND
 230.8
  
 BACK-FED MAIN BREAKER IS NOT PROPERLY
 SEATED ON BUS. 110.3
  
 PANEL COVER NEEDS BLANKS, OPEN SPACES IN
 PANEL COVER. 408.7
  
 WHO INSPECTED UNDERGROUND INSTALLATION?