Plan Review Notes
Plan Review Notes For Permit 21090648
Permit Number 21090648
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-10-12 15:56:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A WALL BEING REMOVED;
 HOWEVER, IT IS NOT CLEAR THE SIZE OF THE OPENING AND IF
 THE WALL IS REMOVED TO THE CEILING.
  
 IF THE WALL IS REMOVED TO THE CEILING FIRE SPRINKLER
 PROTECTION MAY NEED MODIFICATIONS.
  
 FOR THE OFFICIAL RECORD AND CLARIFICATION, PLEASE
 PROVIDE A HORIZONATAL VIEW OF THE PROPOSED CUT-OUT
 OPENING AND WHAT REMAINS AS EXISITNG.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  