Plan Review Notes For Permit 21090648 |
Permit Number |
21090648 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-10-12 15:56:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF A WALL BEING REMOVED; | | HOWEVER, IT IS NOT CLEAR THE SIZE OF THE OPENING AND IF | | THE WALL IS REMOVED TO THE CEILING. | | | | IF THE WALL IS REMOVED TO THE CEILING FIRE SPRINKLER | | PROTECTION MAY NEED MODIFICATIONS. | | | | FOR THE OFFICIAL RECORD AND CLARIFICATION, PLEASE | | PROVIDE A HORIZONATAL VIEW OF THE PROPOSED CUT-OUT | | OPENING AND WHAT REMAINS AS EXISITNG. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|