Plan Review Notes For Permit 19061346 |
Permit Number |
19061346 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-05 14:06:22 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 107, PROVIDE A PLAN SHOWING LOCATION OF PROPOSED | | DOORS. | | | | 2. FBC B 1010.1.10, LABEL ROOMS SERVED WITH OCCUPANCY | | CLASSIFICATION OR ROOM DESIGNATION. NOTE THAT PANIC | | BARS/FIRE EXIT HARDWARE (AND OUTSWING) IS REQUIRED FOR | | ASSEMBLY OCCUPANCY AND ELECTRICAL ROOMS WITH EQUIPMENT | | RATED 1200 AMPERES OR MORE AND OVER 6' WIDE, AND THAT | | CONTAIN OVERCURRENT DEVICES, SWITCHING DEVICES OR | | CONTROL DEVICES. | | | | 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | |
|