2018-02-13 09:11:12 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #18010531 |
| 2/13/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE FLORIDA BUILDING CODES SIXTH EDITION-2017 WENT |
| INTO EFFECT ON JAN. 1, 2018. THE PERMIT APPLICATION AND |
| PLANS FOR THE PROJECT WERE SUBMITTED AFTER THAT DATE. |
| PLEASE UPDATE THE DESIGN CRITERIA FOR THE PROJECT |
| INCLUDING ALL DRAWINGS, DETAILS, NOTES, ENERGY AND HVAC |
| CALCULATIONS ETC. THAT ARE REFERENCING THE OUTDATED |
| 2014 CODES. |
| |
| 2) PLEASE REMOVE THE ENERGYGAUGE SUBMITTAL FOR A SINGLE |
| FAMILY HOME THAT HAS BEEN ATTACHED TO THE FRONT COVER |
| OF THE PLAN AND ALSO UPDATE THE ENERGYGAUGE COMPLIANCE |
| REPORT FOR THE NEW TENANT BUILD-OUT. |
| |
| 3) SHEET M-1: PROVIDE THE LEGEND AND TEXT THAT |
| CORRELATES TO THE KEYNOTES SHOWN ON THE PLAN. |
| |
| 4) PROVIDE AN EXHAUST SYSTEM FOR THE PARKING GARAGE IN |
| COMPLIANCE WITH SECTION 404.1 |
| |
| 5) VERIFY THE CONCEALED AREAS ABOVE THE LIBRARY, STAFF |
| LOUNGE, HALLWAY ARE NOT BEING USED AS RETURN AIR |
| PLENUMS- SECTION 602. |
| |
| 6) SUBMIT THE NOA FOR THE GRAVITY VENTILATOR AND THE |
| CONDENSER TIE-DOWN CLIPS- RULE 9N-3 FAC. |
| |
| 7) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307. |
| |
| |
| THE MECHANICAL REVIEW IS STOPPED AT THIS POINT PEMDING |
| SUBMITTAL OF UPDATED PLANS AND CALCULATIONS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| |