Plan Review Notes
Plan Review Notes For Permit 18010531
Permit Number 18010531
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-13 09:11:121ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18010531
 2/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE FLORIDA BUILDING CODES SIXTH EDITION-2017 WENT
 INTO EFFECT ON JAN. 1, 2018. THE PERMIT APPLICATION AND
 PLANS FOR THE PROJECT WERE SUBMITTED AFTER THAT DATE.
 PLEASE UPDATE THE DESIGN CRITERIA FOR THE PROJECT
 INCLUDING ALL DRAWINGS, DETAILS, NOTES, ENERGY AND HVAC
 CALCULATIONS ETC. THAT ARE REFERENCING THE OUTDATED
 2014 CODES.
  
 2) PLEASE REMOVE THE ENERGYGAUGE SUBMITTAL FOR A SINGLE
 FAMILY HOME THAT HAS BEEN ATTACHED TO THE FRONT COVER
 OF THE PLAN AND ALSO UPDATE THE ENERGYGAUGE COMPLIANCE
 REPORT FOR THE NEW TENANT BUILD-OUT.
  
 3) SHEET M-1: PROVIDE THE LEGEND AND TEXT THAT
 CORRELATES TO THE KEYNOTES SHOWN ON THE PLAN.
  
 4) PROVIDE AN EXHAUST SYSTEM FOR THE PARKING GARAGE IN
 COMPLIANCE WITH SECTION 404.1
  
 5) VERIFY THE CONCEALED AREAS ABOVE THE LIBRARY, STAFF
 LOUNGE, HALLWAY ARE NOT BEING USED AS RETURN AIR
 PLENUMS- SECTION 602.
  
 6) SUBMIT THE NOA FOR THE GRAVITY VENTILATOR AND THE
 CONDENSER TIE-DOWN CLIPS- RULE 9N-3 FAC.
  
 7) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.
  
  
 THE MECHANICAL REVIEW IS STOPPED AT THIS POINT PEMDING
 SUBMITTAL OF UPDATED PLANS AND CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  