2018-11-30 11:02:37****CORRECTIONS****
 W.P.B. PERMIT: 18010531
 REVIEW #3: NOVEMBER 30, 2018
  
 NO RESPONSE SHEET WAS PROVIDED AND I CAN?T SEE THAT
 COMMENTS HAVE BEEN ADDRESSED.
 THE BASIC INFORMATION NEEDS TO BE ESTABLISHED SO THAT
 COMMENTS CAN BE LOOKED AT WITH DESIGN CRITERIA IN MIND.
 THERE ARE TWO OCCUPANCY GROUPS HERE (BUSINESS AND
 STORAGE). THE AMOUNT OF AREA OF EACH NEEDS TO BE SHOWN
 SO THE AMOUNT OF OCCUPANTS CAN BE DETERMINED.
 THE WORK AFFECTS EGREES AND THE LIFE SAFTEY PLAN NOW
 SHOWS NOTHING ABOUT DISTANCE, OCCUPANT LOAD OR COMMON
 PATH OF TRAVEL.
  
 I SUGGEST THAT AN E-MAIL IS SENT TO ME TO REQUEST A
 MEETING WITH BUILDING REVIEW SO THAT DIRECTION IS
 PROVIDED ON WHAT TO SHOW ON PLANS. IF A MEETING IS NOT
 FEASABLE PLEASE CALL ME TO DISCUSS THE COMMENTS VIA
 PHONE AND E-MAIL.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1) SHEET A1.03 IS LISTED AS THE LIFE SAFETY PLAN.
  
 ORIGINAL COMMENT:
 1A) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. NEED TO SPECIFY TYPE OF
 CONSTRUCTION. SEE SEC. 602 FBC.
  
 ORIGINAL COMMENT:
 1B) THIS IS A CHANGE OF OCCUPANCY FROM A STORAGE
 WAREHOUSE OCCUPANCY TO A BUSINESS OCCUPANCY. THE PLANS
 WILL NEED TO STATE THIS IS A CHANGE OF OCCUPANCY AND
 DESIGNED TO THE REQUIREMENTS OF THE:
 2017 EXISTING BUILDING CODE SECTION 1001.2.2 CHANGE OF
 OCCUPANCY CLASSIFICATION OR GROUP. WHERE THE OCCUPANCY
 CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF
 SECTIONS 1002 THROUGH 1012 SHALL APPLY. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION AND A CHANGE TO
 ANOTHER GROUP WITHIN AN OCCUPANCY CLASSIFICATION.
  
 RESPONSE:
 (1)SCOPE OF WORK IS NOT CLEAR. PLANS WERE REVISED
 EXCEPT FOR ELECTRICAL PLAN THAT SHOWS OPEN OFFICE AREA,
 LIBRARY, RECEPTION, CONFERENCE ROOM AND PARKING AREA.
 SEC. 107.2.1 CITY AMENDMENTS. REVISE AS REQUIRED TO
 MATCH.
  
 (2) USE GROUP IN GENERAL NOTES SPECIFY BUSINESS GROUP
 AND STORAGE GROUP S-1. CLEARLY IDENTIFY PROPOSED
 STORAGE MATERIAL. NUMBER OF EXITS WILL BE DETERMINED
 DEPENDING ON TYPE OF STORAGE. AT THIS POINT THE REAR
 DOOR IS NOT AN EXIT. COORDINATE WITH FIRE COMMENTS.
 SEC. 302.1 FBC.
  
 (3) OCCUPANT LOAD IN GENERAL NOTES IS ONLY ACCOUNTING
 FOR THE STORAGE AREA. PROVIDE OCCUPANT LOAD FOR THE
 OFFICE SPACES ALSO. TABLE 1004.1.2 FBC.
  
 ORIGINAL COMMENT:
 1G) THE LIFE SAFETY PLAN SHOWS A NEW RESTROOM AND A
 EXISTING BATHROOM WITH A SHOWER, BUT THE SHOWER IS NOT
 ACCESSIBLE. 2017 FBC-ACCESSIBILITY CODE. 213.2 TOILET
 ROOMS AND BATHING ROOMS. WHERE TOILET ROOMS ARE
 PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH 603. WHERE
 BATHING ROOMS ARE PROVIDED, EACH BATHING ROOM SHALL
 COMPLY WITH 603.
  
 RESPONSE:
 PLANS SHOW ONLY ONE RESTROOM COMPLYING WITH SEC. 603
 FBC ACCESSIBILITY. BOTH RESTROOMS NEED TO COMPLY AS
 REQUIRED BY SEC. 213.2 FBC ACCESSIBILITY.
  
 ORIGINAL COMMENT:
 1I) WITH 2 MEANS OF EGRESS REQUIRED ALSO REVIEW THE
 REQUIREMENT FOR 2 ACCESSIBLE MEANS OF EGRESS, SEE 2017
 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION TO
 ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST
 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH
 404. 2 X 0.60= 1.2 OR 2 ACCESSIBLE MEANS OF EGRESS.
 PLEASE NOTE THE BACK EXIT IS NOT ACCESSIBLE, AND LEAD
 TO THE PUBLIC WAY.
  
 RESPONSE:
 THIS ITEM WILL BE REVIEWED ONCE STORAGE CLASSIFICATION
 AND FIRE COMMENTS ARE ADDRESSED, INCLUDING REQUIRED
 NUMBER OF EXITS. SEE FIRE COMMENTS.
  
 ORIGINAL COMMENT:
 1J) THE LIFE SAFETY PLAN SHOWS 2 PARKING SPACES WITHIN
 THE PARKING GARAGE BUT DOES NOT SHOW A COVERED
 ACCESSIBLE PARKING SPACE NOR ACCESS AISLE , PLEASE ALSO
 NOTE THERE IS A 7 INCH DIFFERENCE IN HEIGHT FROM THE
 GARAGE FLOOR TO THE OPEN OFFICE AREA, NOT AN ACCESSIBLE
 ROUTE. PLEASE SHOW HOW COMPLIANCE WITH THE
 ACCESSIBILITY CODE SECTION 103 EQUIVALENT FACILITATION
 WILL BE MET?
  
 RESPONSE:
 PLANS ARE NOT CLEAR REGARDING THE 7 INCH DIFFERENCE IN
 HEIGHT FROM THE GARAGE FLOOR SHOWN ON PREVIOUS PLANS.
 PROVIDE COMPLETE DETAIL/SPECIFICATIONS SHOWING HOW
 DEALING WITH THE 7 INCH DROP. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 ORIGINAL COMMENT:
 NOTE: THE ORIGINAL COMMENTS BELOW WERE FOR THE PROPOSED
 NEW STAIRS. REVISED PLANS SHOW EXISTING STAIRS. THESE
 STAIRS DON'T HAVE HANDRAILS AND ACCORDING TO PICTURES
 IN WEBSITE SHOWING THE WORK BEING PERFORMED IN THIS
 BUILDING THE STAIRS DON'T SEEM TO BE SAFE. PLEASE
 ADDRESS HOW PROVIDING SAFE STAIRS (MAY USE COMMENTS
 BELOW FOR REFERENCE) SEC. 101.3 FBC-EXISTING BUILDING.
 BUILDING INSPECTOR SITE VISIT MAY BE REQUIRED.
  
 3) SHEET A3.01 SHOWS STAIRS ON THE WEST SIDE OF THE
 BUILDING.
  
 3A) THE STAIR TOP LANDING SHOWS THE GUARDRAIL AT A
 HEIGHT OF 42 INCHES BUT THEN THE GUARD IS REDUCED IN
 HEIGHT TO 32 INCHES.
 FBC-B 1015.3 HEIGHT. REQUIRED GUARDS SHALL BE NOT LESS
 THAN 42 INCHES (1067 MM) HIGH, MEASURED VERTICALLY AS
 FOLLOWS: 1.FROM THE ADJACENT WALKING SURFACES.
 EXCEPTIONS ARE FOR R2 AND R3 IN THE UNIT ITSELF.
  
 3B) THE PLANS DO NOT INDICATE THE SPACING OF THE
 PICKETS. PLEASE SHOW COMPLIANCE WITH: FBC-B 1015.4
 OPENING LIMITATIONS. REQUIRED GUARDS SHALL NOT HAVE
 OPENINGS THAT ALLOW PASSAGE OF A SPHERE 4 INCHES IN
 DIAMETER.
  
 3C) THE PLANS DO NOT PROVIDE THE DIMENSION OF THE
 TRIANGULAR AREA OF THE STAIR RISE, RUN AND BOTTOM RAIL
 OF THE GUARD. FBC-B 1015.4 EXCEPTION 2. THE TRIANGULAR
 OPENINGS AT THE OPEN SIDES OF A STAIR, FORMED BY THE
 RISER, TREAD AND BOTTOM RAIL SHALL NOT ALLOW PASSAGE OF
 A SPHERE 6 INCHES (152 MM) IN DIAMETER.
  
 3D) THE HANDRAIL HORIZONTAL EXTENSION STOP SHORT OF THE
 BOTTOM TREAD. FBC-B 1014.6 HANDRAIL EXTENSIONS.
 THE HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN
 12 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER. 4.ACCESSIBLE HANDRAIL EXTENSIONS SHALL BE IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 ACCESSIBILITY. THE BOTTOM HORIZONTAL RETURN OF A
 HANDRAIL SHALL BE NO HIGHER THAN 27 INCHES. 2017 ACC.
 CODE 307.3.
  
 3E) SHEET A3.01 ARE SILENT ABOUT THE REQUIRED DESIGN
 LOADS FOR HANDRAILS AND GUARDRAILS. DESIGNED AND
 CONSTRUCTED FOR THE STRUCTURAL LOADING CONDITIONS SET
 FORTH IN THIS SECTION. FBC-B 1607.8.1 HANDRAILS AND
 GUARDS. HANDRAILS AND GUARDS SHALL BE DESIGNED TO
 RESIST A LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT (PLF)
 IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7.
  
 3F) FBC-B 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND
 GUARDS SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD
 OF 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE
 7.
  
 3G) FBC-B 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE
 RAILS (ALL THOSE EXCEPT THE HANDRAIL), BALUSTERS AND
 PANEL FILLERS SHALL BE DESIGNED TO RESIST A
 CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.1 OF ASCE 7.
  
 ORIGINAL COMMENT:
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A RESPONSE LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLANS ARE INCOMPLETE AND WITH THE RESPONSES TO THE
 COMMENTS MAY CREATE ADDITIONAL COMMENTS.
  
  
 NEW COMMENTS:
 1-PLANS SUBMITTED DON'T MATCH PLANS SPECIFIED ON THE
 DRAWING INDEX ON COVER SHEET. MISSING SOME DRAWIINGS.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- COVER SHEET IS MISSING THE ARCHITECT'S TITLE BLOCK.
 ALSO, THE TITLE BLOCK IN ALL OTHER DRAWINGS IS MISSING
 THE NAME AND LICENSE NUMBER OF THE ARCHITECT
 RESPONSIBLE FOR THE DESIGN. SEE BELOW.
  
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED.
 (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO
 BE A CORPORATION, LIMITED LIABILITY COMPANY,
 PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME,
 OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN
 HIS OR HER OWN NAME.
 RULEMAKING AUTHORITY 481.2055, 481.221(1), (3) FS. LAW
 IMPLEMENTED 481.219, 481.221(1), (3) FS. HISTORY?NEW
 9-7-00, AMENDED 3-16-14
  