Plan Review Notes
Plan Review Notes For Permit 18010531
Permit Number 18010531
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-05 17:29:472017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010531
 ADD: 861 N. RAILROAD AVE
 CONT: MEASURE TWICE CONSTRUCTION
 TEL: 561-722-0992
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 05/ 2018
 ACTION: DENIED
  
 1) SHEET A1.03 IS LISTED AS THE LIFE SAFETY PLAN.
  
 1A) 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 1B) THIS IS A CHANGE OF OCCUPANCY FROM A STORAGE
 WAREHOUSE OCCUPANCY TO A BUSINESS OCCUPANCY. THE PLANS
 WILL NEED TO STATE THIS IS A CHANGE OF OCCUPANCY AND
 DESIGNED TO THE REQUIREMENTS OF THE:
  
 2017 EXISTING BUILDING CODE SECTION 1001.2.2 CHANGE OF
 OCCUPANCY CLASSIFICATION OR GROUP. WHERE THE OCCUPANCY
 CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF
 SECTIONS 1002 THROUGH 1012 SHALL APPLY. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION AND A CHANGE TO
 ANOTHER GROUP WITHIN AN OCCUPANCY CLASSIFICATION.
  
 1C) THE LIFE SAFETY SHEET SHOWS A PARKING GARAGE. 2017
 FBC-B 406.4.6 MIXED OCCUPANCY SEPARATION.
 PARKING GARAGES SHALL BE SEPARATED FROM OTHER
 OCCUPANCIES IN ACCORDANCE WITH SECTION 508.1. SEE MIXED
 OCCUPANCIES. FBC-B 508.4 SEPARATED OCCUPANCIES AND
 TABLE 508.4 FOR A NON-SPRINKLERED BUILDING WOULD
 REQUIRE 2 HOUR FIRE SEPARATION BETWEEN THE BUSINESS
 OCCUPANCY AND THE S2 OCCUPANCY.
  
 1D) FBC-B 406.6 ENCLOSED PARKING GARAGES. ENCLOSED
 PARKING GARAGES SHALL COMPLY WITH SECTIONS 406.6.1
 THROUGH 406.6.3.
  
 1E) FBC-B 406.6.2 VENTILATION. A MECHANICAL VENTILATION
 SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL.
  
 1F) HEADING. AREA OF PARKING IS 407 SQ. FT. / 200= NOT
 2 BUT 3 OCCUPANTS, WHEN THERE IS A FRACTION OF A
 OCCUPANT YOU ROUND UP FOR MEANS OF OCCUPANTS. TABLE
 1004.1.2.
  
 1G) THE LIFE SAFETY PLAN SHOWS A NEW RESTROOM AND A
 EXISTING BATHROOM WITH A SHOWER, BUT THE SHOWER IS NOT
 ACCESSIBLE. 2017 FBC-ACCESSIBILITY CODE. 213.2 TOILET
 ROOMS AND BATHING ROOMS. WHERE TOILET ROOMS ARE
 PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH 603. WHERE
 BATHING ROOMS ARE PROVIDED, EACH BATHING ROOM SHALL
 COMPLY WITH 603.
  
 1H) HEADING. NUMBER OF REQUIRED EXITS LIST CODE SECTION
 1015.1 LESS THAN 49 OCCUPANTS 1 EXIT IS REQUIRED.
 MISSING INFORMATION IS SINGLE EXIT TABLE 1006.2.1
 BUSINESS OCCUPANCY AND OCCUPANT LOADS GREATER THAN 30,
 THE MAXIMUM COMMON PATH OF TRAVEL IS 75 FEET, REQUIRING
 2 EXITS. PLEASE UPDATE PLANS.
  
 1I) WITH 2 MEANS OF EGRESS REQUIRED ALSO REVIEW THE
 REQUIREMENT FOR 2 ACCESSIBLE MEANS OF EGRESS, SEE 2017
 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION TO
 ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST
 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH
 404. 2 X 0.60= 1.2 OR 2 ACCESSIBLE MEANS OF EGRESS.
 PLEASE NOTE THE BACK EXIT IS NOT ACCESSIBLE, AND LEAD
 TO THE PUBLIC WAY.
  
 1J) THE LIFE SAFETY PLAN SHOWS 2 PARKING SPACES WITHIN
 THE PARKING GARAGE BUT DOES NOT SHOW A COVERED
 ACCESSIBLE PARKING SPACE NOR ACCESS AISLE , PLEASE ALSO
 NOTE THERE IS A 7 INCH DIFFERENCE IN HEIGHT FROM THE
 GARAGE FLOOR TO THE OPEN OFFICE AREA, NOT AN ACCESSIBLE
 ROUTE. PLEASE SHOW HOW COMPLIANCE WITH THE
 ACCESSIBILITY CODE SECTION 103 EQUIVALENT FACILITATION
 WILL BE MET?
  
 1K) SHEET A1.03 THE LIFE SAFETY PLAN SHOWS A NEW FRONT
 ENTRY DOOR AND REVERSED SWING. 2017 EXISTING BUILDING
 CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 THE NEW EXTERIOR DOOR CANNOT SWING OUT OVER THE PUBLIC
 SIDEWALK.
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
 ABOVE GRADE AND BELOW 8 FEET IN HEIGHT SHALL BE
 PROHIBITED. DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT
 INTO THE PUBLIC RIGHT-OF-WAY.
  
 2) SHEET S-100 INDICATES WINDOW AND DOOR PRESSURES OF
 +46/ -50 PSF. THE SUBMITTED PRODUCT APPROVALS CANNOT BE
 REVIEWED UNTIL THE WIND DESIGN CRITERIA IS PROVIDED.
  
 PLEASE NOTE THE PLANS DOES NOT PROVIDE A WIND DESIGN
 CRITERIA. 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE
 FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL BE
 SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5 DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. / 1609.3.1 WIND SPEED CONVERSION VULT TO
 VASD. ALL PRODUCT APPROVALS ARE VASD.
  
 3) SHEET A3.01 SHOWS STAIRS ON THE WEST SIDE OF THE
 BUILDING.
  
 3A) THE STAIR TOP LANDING SHOWS THE GUARDRAIL AT A
 HEIGHT OF 42 INCHES BUT THEN THE GUARD IS REDUCED IN
 HEIGHT TO 32 INCHES.
 FBC-B 1015.3 HEIGHT. REQUIRED GUARDS SHALL BE NOT LESS
 THAN 42 INCHES (1067 MM) HIGH, MEASURED VERTICALLY AS
 FOLLOWS: 1.FROM THE ADJACENT WALKING SURFACES.
 EXCEPTIONS ARE FOR R2 AND R3 IN THE UNIT ITSELF.
  
 3B) THE PLANS DO NOT INDICATE THE SPACING OF THE
 PICKETS. PLEASE SHOW COMPLIANCE WITH: FBC-B 1015.4
 OPENING LIMITATIONS. REQUIRED GUARDS SHALL NOT HAVE
 OPENINGS THAT ALLOW PASSAGE OF A SPHERE 4 INCHES IN
 DIAMETER.
  
 3C) THE PLANS DO NOT PROVIDE THE DIMENSION OF THE
 TRIANGULAR AREA OF THE STAIR RISE, RUN AND BOTTOM RAIL
 OF THE GUARD. FBC-B 1015.4 EXCEPTION 2. THE TRIANGULAR
 OPENINGS AT THE OPEN SIDES OF A STAIR, FORMED BY THE
 RISER, TREAD AND BOTTOM RAIL SHALL NOT ALLOW PASSAGE OF
 A SPHERE 6 INCHES (152 MM) IN DIAMETER.
  
 3D) THE HANDRAIL HORIZONTAL EXTENSION STOP SHORT OF THE
 BOTTOM TREAD. FBC-B 1014.6 HANDRAIL EXTENSIONS.
 THE HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN
 12 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER. 4.ACCESSIBLE HANDRAIL EXTENSIONS SHALL BE IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 ACCESSIBILITY. THE BOTTOM HORIZONTAL RETURN OF A
 HANDRAIL SHALL BE NO HIGHER THAN 27 INCHES. 2017 ACC.
 CODE 307.3.
  
 3E) SHEET A3.01 ARE SILENT ABOUT THE REQUIRED DESIGN
 LOADS FOR HANDRAILS AND GUARDRAILS. DESIGNED AND
 CONSTRUCTED FOR THE STRUCTURAL LOADING CONDITIONS SET
 FORTH IN THIS SECTION. FBC-B 1607.8.1 HANDRAILS AND
 GUARDS. HANDRAILS AND GUARDS SHALL BE DESIGNED TO
 RESIST A LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT (PLF)
 IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7.
  
 3F) FBC-B 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND
 GUARDS SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD
 OF 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE
 7.
  
 3G) FBC-B 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE
 RAILS (ALL THOSE EXCEPT THE HANDRAIL), BALUSTERS AND
 PANEL FILLERS SHALL BE DESIGNED TO RESIST A
 CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.1 OF ASCE 7.
  
 4) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLANS ARE INCOMPLETE AND WITH THE RESPONSES TO THE
 COMMENTS MAY CREATE ADDITIONAL COMMENTS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  