Date |
Text |
2018-06-04 10:49:23 | ****PROVISOS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| ARCHITECT - KEITH SPINA, GLIDDEN SPINA |
| STRUCTURAL - ANDREW P. SULLIVAN, PE, MCNAMARA-SALVIA |
| MEP - STEPHEN FELLERS, PE |
| |
| FS471, FS481 REQUIRE THAT DOCUMENTS PREPARED BY AN |
| ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| SIGNED, SEALED, DATED ORIGINALS. |
| |
| 1. ARCH, CIVIL OK |
| |
| 2. THE NEW PLUMBING PAGES HAVE AN ERROR THAT THE |
| SIGNATURE IS OK, BUT THERE ARE UNSIGNED CHANGES MADE |
| AFTER SIGNING. I'VE SEEN THIS ERROR ASSOCIATED WITH |
| UTILIZING A DIFFERENT SOFTWARE (BLUEBEAM?). |
| |
| PLUMBING HAS PASSED REVIEW. PLEASE CONTACT ME VIA EMAIL |
| TO DISCUSS HOW THIS WILL BE RESOLVED. THIS WILL BE A |
| PROVISO ITEM. |
| |
| 3. THE NEW MECHANICAL PAGES HAVE AN ERROR THAT THE |
| SIGNATURE IS OK, BUT THERE ARE UNSIGNED CHANGES MADE |
| AFTER SIGNING. I'VE SEEN THIS ERROR ASSOCIATED WITH |
| UTILIZING A DIFFERENT SOFTWARE (BLUEBEAM?). |
| |
| AC CALCS PREPARED BY STEPHEN FELLER, PE ARE NOT |
| DIGITALLY SIGNED AND SEALED. A DIGITALLY SIGNED AND |
| SEALED DOCUMENT WILL BE REQUIRED AT THE SAME TIME THAT |
| PLAN PAGES ARE ADDRESSED (PROVISO ITEM). |
| |
| SHEETS M5.0.0 (TWO DIFFERENT PAGES WITH SAME NUMBER, |
| DIFFERENT RISER INFORMATION), M5.0.1, M5.0.2 (TWO |
| DIFFERENT PAGES WITH SAME NUMBER, DIFFERENT |
| INFORMATION) |
| |
| ENERGY CALCS - OK |
| FIRE STANDPIPE CALCS - OK |
| |
| 4. ELECTRICAL SHEETS OK |
| |
| 5. SLS CONSULTING, INC. FIRE PROTECTION ENGINEERS - |
| SMOKE CONTROL RATIONAL ANALYSIS - OK (4/13/18 VERSION) |
| |
| 6. THE COVER SHEET AND INDEX PAGES ARE NUMBERED 570, |
| 571 AND 572, WHICH WILL MAKE THEM PRINT IN THE MIDDLE |
| OF THE PLAN SET. ARE THESE DUPLICATES OF THE COVER |
| SHEET AND INDEX PAGES AT THE BEGINNING OF THE DOCUMENT? |
| CAN THEY BE VOIDED OR DELETED? |
| |
| |
| |
| |
| |
| |
| |