Plan Review Notes
Plan Review Notes For Permit 17110075
Permit Number 17110075
Review Stop SIGNATURE
Sequence Number 1
Notes
Date Text
2017-12-08 07:23:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 ARCHICTECTURAL SHEETS - KEITH SPINA, GLIDDEN SPINA +
 PARTNERS: DIGITAL SEAL/SIGNATURE AND TITLE BLOCK COMPLY
 WITH FS481, BUT NEW SHEETS SUBMITTED 2ND CYCLE NEED
 REVIEW
  
 CIVIL SHEETS - GREGORY F. BOLEN, PE, SIMMONS & WHITE,
 INC.: DIGITAL SEAL/SIGNATURE AND TITLE BLOCK COMPLY
 WITH FS481, BUT NEW SHEETS SUBMITTED 2ND CYCLE NEED
 REVIEW
  
 LANDSCAPE, IRRIGATION - BRYAN DONAHUE, RLA, WGI: BRYAN
 DONAHUE DIGITAL SEAL/SIGNATURE COMPLY WITH FS481. I WAS
 UNABLE TO LOCATE LANDSCAPE ARCHITECT BUSINESS NUMBER
 7055 AT DBPR WEBSITE (SEARCHED LICENSE NUMBER AND NAME
 OF "WGI"). PLEASE ADDRESS.
 REGARDING IP SHEETS, PLEASE NOTE SCOPE IN FS
 481.303(7); CONSULT WITH YOUR BOARD TO DETERMINE WHO
 CAN SIGN/SEAL THESE PAGES
  
 STRUCTURAL SHEETS - ANDREW P. SULLIVAN, PE,
 MCNAMARA-SALVIA: DIGITAL SEAL/SIGNATURE AND TITLE BLOCK
 COMPLY WITH FS471, BUT NEW SHEETS SUBMITTED 2ND CYCLE
 NEED REVIEW
  
 MECHANICAL, PLUMBING, ELECTRICAL, FIRE PROTECTION
 SHEETS - STEVEN FELLER PE, STEVEN FELLER PE LLC:
 DIGITAL SEAL/SIGNATURE AND TITLE BLOCK COMPLY WITH
 FS471, BUT NEW SHEETS SUBMITTED 2ND CYCLE NEED REVIEW.
 FS 471.0195, DBPR WEBSITE DOES NOT INDICATE THAT
 ENGINEER HAS COMPLETED ADVANCED FLORIDA BUILDING CODE
 COURSE. ENGINEER MAY HAVE ALREADY TAKEN THIS COURSE
 (WHICH WAS REQUIRED TO BE COMPLETED BY 6/30/2016, BUT
 EVIDENCE OF SUCH MUST BE SENT TO FBPE SO THE ENGINEER'S
 RECORD ON WWW.MYFLORIDALICENSE.COM CAN BE UPDATED.
 PLEASE ADDRESS.
  
 LOW VOLTAGE PLANS (SHEETS 840 LVC1 THROUGH 849 CHSLV
 7.1), NOT SIGNED AND SEALED. LOW VOLTAGE REQUIRES A
 SEPARATE PERMIT; THESE PAGES HAVE NOT BEEN REVIEWED.
  
 POOL PLANS, OFELIA TABOADA, PE AND AQUADYNAMICS (SHEETS
 850 SP1.0 THROUGH 862 SP2.04), FS 471.0195, DBPR
 WEBSITE DOES NOT INDICATE THAT ENGINEER HAS COMPLETED
 ADVANCED FLORIDA BUILDING CODE COURSE. ENGINEER MAY
 HAVE ALREADY TAKEN THIS COURSE (WHICH WAS REQUIRED TO
 BE COMPLETED BY 6/30/2016, BUT EVIDENCE OF SUCH MUST BE
 SENT TO FBPE SO THE ENGINEER'S RECORD ON
 WWW.MYFLORIDALICENSE.COM CAN BE UPDATED. PLEASE
 ADDRESS.
  
 SUPPORTING DOCUMENTS (PROVISO: ANY NEW DOCUMENTS
 SUBMITTED FOR ANOTHER REVIEW CYCLE NEED REVIEW):
 ENERGY CALCS INPUT REPORT SIGNATURE/SEAL OK
 ENERGY CALCULATION REPORT SIGNATURE/SEAL OK
 EXPEDITE EMAIL RE: EXPEDITE: PLEASE PROVIDE (DOCUMENT
 ON FILE DOES NOT INCLUDE EMAIL OR LETTER FROM MAYOR
 AUTHORIZING EXPEDITED REVIEWS WITH NO FEE)
 FIRE STANDPIPE CALCS SIGNATURE/SEAL OK
  
 SMOKE CONTROL RATIONAL ANALYSIS: THIS DOCUMENTS LACKS
 SIGNATURE/SEAL, LACKS TITLE BLOCK IN COMPLIANCE WITH
 FS471 AND FAC61G15-23.002 (CERTIFICATE OF AUTHORIZATION
 FOR SLS FIRE PROTECTION ENGINEERS, NAME AND LICENSE
 NUMBER OF INDIVIDUAL PREPARING THE DOCUMENT)
  
 HVAC CALCS: PREPARED BY STEVEN FELLER, LACKS
 SIGNATURE/SEAL.
  
  
  
  
  
  
  
  
  
  
  
  
  
  