Plan Review Notes
Plan Review Notes For Permit 17110075
Permit Number 17110075
Review Stop P
Sequence Number 2
Notes
Date Text
2018-02-20 08:18:471ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P1.1.1A, B, C, D THE SANITARY STACKS ARE
 LABELED ALL THE SAME MATCHING THE NOTES PLEASE LABEL TO
 MATCH THE ISOMETRIC DRAWINGS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
 2. IF YOU ARE CAPPING THE GREASE WASTE UNDER THE SLAB
 PLEASE INDICATE ON THE PLAN HOW IT WILL BE LOCATED IN
 THE FUTURE. PER WPB AMEND TO FBC 107.2.1
 3. SHT. P3.1.1 IT APPEARS THAT SANITARY STACK #17 IS
 LABELED AS #19 PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 4. SHT. P3.1.1 THE 4? BUILDING DRAIN BETWEEN STACK #26
 AND #27 IS UNDER SIZED. PER FBC PL TABLE 710.1(1)
 5. SHT. P1.1.1A, B, C, D, PLEASE LABEL THE STORM RISERS
 TO MATCH THE ISOMETRIC DRAWINGS ON P3.11.1 PER WPB
 AMEND TO FBC 107.2.1
 6. SHT. P1.1.1D NOTE #3 LIST A 15? STORM DRAIN THE
 ISOMETRIC ON P3.11.1 SHOWS A 16? THE 15? IS UNDER
 SIZED. PER FBC PL TABLE 1106.3
 7. SHT. P1.1.1D NOTE #7 LIST 12? STORM THE ISO SHOWS
 16? PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 8. IN PREVIOUS COMMENT #30 IS WAS ASKING FOR THE SPECS
 FOR THE PUMPS YOUR RESPONSE WAS FOR THE GREASE
 INTERCEPTOR I STILL NEED THOSE SPECS FOR THE BOOSTER
 PUMPS THE CAN BE SUBMITTALS IF YOU REQUESTED. PER WPB
 AMEND TO FBC 107.3.4.2
 9. SHT. P3.13.1 THE 8? HORIZONTAL STORM DRAIN BETWEEN
 RISER E AND F IS UNDER SIZED THE MAX SQFT FOR 8? @
 1/8FT IS 9200SQFT. PER FBC PL TABLE 1106.2
 10. PER FBC PL SIZING TABLE 1106.2 IT ONLY GOES UP TO
 15? PLEASE PROVIDE THE CALCULATION TO SIZE THE 16?
 STORM. PER WPB AMEND TO FBC 107.2.1
 11. IN THE SPEC B BATHROOMS SUCH AS THE MASTER IN UNIT
 01 D1-1 WHERE THE TOILET IS ADJACENT TO A SHOWER
 BACKING OR REINFORCEMENT WILL BE REQUIRED FOR A FOLD UP
 GRAB BAR PLEASE PROVIDE A DETAIL SHOWING THE DIMENSIONS
 AND HOW THIS WILL BE DONE. PER FHA DESIGN MANUAL
 REQUIREMENT #6 PG 6.6+6.7
 12. IT APPEARS THAT YOU ARE USING MULTIPLE SAFE HARBOR
 DESIGN DOCUMENTS IT IS MY UNDERSTANDING THAT A PROJECT
 SHOULD BE DESIGNED USING ONLY 1 SPECIFIC DESIGN
 DOCUMENT PLEASE CLARIFY .
 13. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACE
 AT THE FIXTURES. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  