2017-12-11 12:54:42 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. A10.0.0 |
| A) DETAIL #1 THE CENTERLINE OF THE TOILET IS SHOWN AS |
| 18? ABSOLUTE DIMENSION, ALL OF THE DIMENSIONS SHOWN ON |
| THE ENLARGED UNIT PLAN SHEETS ARE OVER 18? PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| B) ON THE FIGURE SHOWING THE BACKING ON THE BACK WALL |
| OF THE TOILET PLEASE PROVIDE DIMENSION FOR THE TOTAL |
| LENGTH OF THE BACKING. PER FHA GUIDELINES REQUIREMENT 6 |
| FIG. 3 |
| C) ON THE FIGURE SHOWING THE BACKING ON THE BACK WALL |
| OF THE TUB PROVIDE THE DIMENSION FROM THE TOP OF THE |
| TUB TO THE BOTTOM OF THE BACKING. PER FHA GUIDELINES |
| REQUIREMENT 6 FIG. 4 |
| |
| 2. SHT. A10.0.0 PLEASE CLARIFY EXACTLY WHICH DESIGN |
| DOCUMENTS WERE USED FOR MEETING THE FHA REQUIREMENTS OF |
| THIS PROJECT. PER WPB AMEND TO FBC 107.2.1 |
| |
| 3. SHT. LS.7.1 WHAT OCCUPANT LOAD ARE YOU USING FOR |
| PLUMBING FIXTURE COUNT PLEASE CLARIFY. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 4. SHTS. A9.70.5, A9.73.5, A9.74.5, A9.75.5 PLEASE |
| PROVIDE DIMENSIONS SHOWING COMPLIANCE WITH KNEE AND TOE |
| CLEARANCE FOR LAVATORY?S. PER ANSI A117.1 SEC 419 FIG. |
| 31 |
| |
| 5. SHTS. A9.70.5, A9.73.5, A9.74.5, A9.75.5 PROVIDE |
| DIMENSION TO SHOW COMPLIANCE WITH THE LENGTH OF THE |
| GRAB BAR AND THE DISTANCE OF THE END OF THE GRAB BAR |
| OFF THE SIDE WALL AND BACK WALL. PER ANSI A!!7.1 SEC |
| 417 FIG. 30 |
| |
| 6. SHT. A99.70.5 DETAIL #3 COFFEE BAR PER FHA |
| GUIDELINES COMMON AREA CHART THE COFFEE BAR WOULD FALL |
| UNDER #14 AND SHALL COMPLY WITH ANSI A117.1 SEC 4.1- |
| 4.30 THE HEIGHT OF THE COFFEE BAR SHALL BE MIN 28? MAX |
| 34? OFF FINISHED FLOOR. AND A 30? X 48? CLEAR FLOOR |
| SPACE PER ANSI 4.30.4, 4.30.2, 4.30.3 |
| |
| 7. WILL THE POOL AND DECK EVER BE LEASED OUT FOR |
| SPECIAL EVENTS PLEASE PROVIDE RESPONSE IN SIGNED AND |
| SEALED LETTER. PER WPB AMEND TO FBC 107.2.1 |
| |
| 8. SHT. A9.73.1 THE SINK IN THE MEDIA ROOM SHALL COMPLY |
| WITH ANSI A117.1 SEC 1.19.3 FIG 31 + 32 |
| |
| 9. SHT. A9.73.5 PLEASE SHOW COMPLIANCE WITH ANSI 4.15 |
| +4. 4.1 |
| |
| 10. SHT. A9.74.3, A9.76.3 SHOW CLEAR FLOOR SPACE FOR |
| THE TOILET. PER WPB AMEND TO FBC 107.2.1 |
| |
| 11. SHT. A9.74.5, A9.75.5 PLEASE SHOW COMPLIANCE WITH |
| ANSI 4.18 |
| |
| 12. THE SINKS IN THE BBQ AREA OF THE POOL DECK AND |
| SUNSET DECK SHALL COMPLY WITH ANSI A117.1 SEC 4.19 |
| |
| 13. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR |
| SPACES FOR THE FIXTURES IN THE ADAPTABLE BATHROOMS IN |
| THE DWELLING UNITS. PER FHA GUIDELINES REQUIREMENT 7 |
| FIGURE 7(A)(B)(C)(D) |
| |
| 14. IN THE GUEST BATHROOM FHA DESIGN A THE CLEAR FLOOR |
| SPACE FOR THE TUB SHALL EXTEND ALL THE WAT TO THE EDGE |
| OF THE TUB. . PER FHA GUIDELINES REQUIREMENT 7 FIGURE |
| 7(B) |
| |
| 15. PLEASE NUMBER THE RISERS AND STACKS ON THE FLOOR |
| PLANS TO ALL THE RISER AND ISOMETRIC PLANS. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 16. ON THE SANITARY COLLECTION AND RISER PLANS IT IS |
| DIFFICULT TO MATCH UP THE STACKS TO THE TAG NUMBER |
| PLEASE DRAW A LINE CONNECTING THE TAG TO THE STACK. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 17. AAV ARE NOT PERMITTED BELOW THE 4TH BRANCH |
| INTERVALS FROM THE TOP OF THE STACK UNLESS THEY HAVE A |
| RELIEF VENT CONNECTING TO A VENT STACK OR STACK VENT. |
| PER FBC PL 918.3.1 |
| |
| 18. PLEASE PROVIDE A LIST WITH PLAN SHEETS P2.1.1 |
| THROUGH P2.22.1 MATCHED WITH THE UNIT NUMBERS. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| ON THE SANITARY COLLECTION PLAN SHEETS THERE ARE VENT |
| AND DRAIN PIPES THAT ARE NOT CONNECTED PLEASE PROVIDE |
| SOME KIND OF IDENTIFICATION AS TO WHERE THESE PIPE |
| CONNECT. PER WPB AMEND TO FBC 107.2.1 |
| |
| 19. PLEASE LABEL THE STORM PIPING AND THE PAD, CD, AD, |
| DD,OD ON THE FLOOR PLANS SO THEY MATCH UP AND CAN BE |
| EASILY IDENTIFIED ON THE COLLECTION AND RISER DRAWINGS. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 20. SHT. A8.1.2 DETAIL #1 HOW WILL THE DRAIN BE |
| CONNECTED TO ROOF SLAB. . PER WPB AMEND TO FBC 107.2.1 |
| |
| 21. SHT. A8.1.1 PROVIDE DIMENSIONS FOR EMERGENCY |
| SCUPPERS. PER FBC PL 1108.3 |
| |
| 22. P1.11.1A, P1.11.1B, P1.11.1C, P1.11.1D PLEASE LABEL |
| EACH EMERGENCY WITH THE SQFT IT WILL BE DRAINING. PER |
| FBC PL 1108.3 |
| |
| 23. PROVIDE DETAIL SHOWING DIMENSION FROM THE BOTTOM OF |
| THE EMERGENCY SCUPPER TO THE LOWEST POINT OF ROOF BEING |
| SERVED TO SHOW COMPLIANCE WITH FBC PL 1101..7 |
| |
| 24. SHT. P3.14.1 KEY NOTE #2 PROVIDE LOCATION. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 25. SHT. P3.14.1 PLEASE SHOW FLOOR LEVEL ON THE |
| ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1 |
| |
| 26. SHT. P3.16.1 LABEL ALL PIPES AND PROVIDE KEY NOTE. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 27. SHT. P3.23.1 PLACE NOTE ON PLAN THE NON POTABLE |
| WATER PIPING SHALL BE LABELED. PER FBC PL 606.7 |
| |
| 28. SHT. P4.1.1 THE 4? DOUBLE SANITARY TEE CANNOT BE |
| USED AS A SAMPLING PORT A 4? TWO WAY CLEAN OUT IS |
| ALLOWED. PER CITY WPB UTILITIES DEPT. |
| |
| 29. PROVIDE MANUFACTURE SIZING CALCULATIONS FOR THE |
| GREASE INTERCEPTOR. PER FBC PL 1003.3.4 |
| |
| 30. SHT. P4.4.1 PROVIDE THE MANUFACTURE SPECIFICATIONS |
| THAT SHOW THE UL LISTING NUMBERS AND THE NSF LISTING |
| NUMBERS AND ANY OTHER STANDARDS THAT THEY MEET. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 31. SHT. P3.13.1 THE 8? HORIZONTAL DRAIN CONNECTING TO |
| RISER A IS OVER THE SQFT FOR 8? PIPE. PER FBC PL TABLE |
| 1106.3 |
| |
| 32. SHT. P3.13.1 THE 16? HORIZONTAL DRAIN LINE IS |
| MISSING THE SQFT PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 33. SHT. P3.13.1 RISER #1 IS MISSING SQFT PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 34. SHT. P3 .12.1 THE 6? HORIZONTAL DRAIN CONNECTING TO |
| RISER I IS MISSING SQFT PER WPB AMEND TO FBC 107.2.1 |
| |
| 35. SHT. P3.11.1 THE 4? HORIZONTAL BRANCH DRAIN |
| CONNECTING THE DD 1802 SQFT IS UNDERSIZED. PER FBC PL |
| TABLE 1106.3 |
| |
| 36. SHT. P3.11.1 SIZE THE HORIZONTAL BRANCHES ON RISERS |
| C, D, E. PER WPB AMEND TO FBC 107.2.1 |
| |
| 37. PLACE NOT ON PLAN POOL PLANS FOR REFERENCE ONLY |
| WILL BE REVIEWED UNDER SEPARATE POOL PERMIT. |
| |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |