Plan Review Notes
Plan Review Notes For Permit 17110075
Permit Number 17110075
Review Stop P
Sequence Number 1
Notes
Date Text
2017-12-11 12:54:421ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A10.0.0
 A) DETAIL #1 THE CENTERLINE OF THE TOILET IS SHOWN AS
 18? ABSOLUTE DIMENSION, ALL OF THE DIMENSIONS SHOWN ON
 THE ENLARGED UNIT PLAN SHEETS ARE OVER 18? PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 B) ON THE FIGURE SHOWING THE BACKING ON THE BACK WALL
 OF THE TOILET PLEASE PROVIDE DIMENSION FOR THE TOTAL
 LENGTH OF THE BACKING. PER FHA GUIDELINES REQUIREMENT 6
 FIG. 3
 C) ON THE FIGURE SHOWING THE BACKING ON THE BACK WALL
 OF THE TUB PROVIDE THE DIMENSION FROM THE TOP OF THE
 TUB TO THE BOTTOM OF THE BACKING. PER FHA GUIDELINES
 REQUIREMENT 6 FIG. 4
  
 2. SHT. A10.0.0 PLEASE CLARIFY EXACTLY WHICH DESIGN
 DOCUMENTS WERE USED FOR MEETING THE FHA REQUIREMENTS OF
 THIS PROJECT. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. LS.7.1 WHAT OCCUPANT LOAD ARE YOU USING FOR
 PLUMBING FIXTURE COUNT PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 4. SHTS. A9.70.5, A9.73.5, A9.74.5, A9.75.5 PLEASE
 PROVIDE DIMENSIONS SHOWING COMPLIANCE WITH KNEE AND TOE
 CLEARANCE FOR LAVATORY?S. PER ANSI A117.1 SEC 419 FIG.
 31
  
 5. SHTS. A9.70.5, A9.73.5, A9.74.5, A9.75.5 PROVIDE
 DIMENSION TO SHOW COMPLIANCE WITH THE LENGTH OF THE
 GRAB BAR AND THE DISTANCE OF THE END OF THE GRAB BAR
 OFF THE SIDE WALL AND BACK WALL. PER ANSI A!!7.1 SEC
 417 FIG. 30
  
 6. SHT. A99.70.5 DETAIL #3 COFFEE BAR PER FHA
 GUIDELINES COMMON AREA CHART THE COFFEE BAR WOULD FALL
 UNDER #14 AND SHALL COMPLY WITH ANSI A117.1 SEC 4.1-
 4.30 THE HEIGHT OF THE COFFEE BAR SHALL BE MIN 28? MAX
 34? OFF FINISHED FLOOR. AND A 30? X 48? CLEAR FLOOR
 SPACE PER ANSI 4.30.4, 4.30.2, 4.30.3
  
 7. WILL THE POOL AND DECK EVER BE LEASED OUT FOR
 SPECIAL EVENTS PLEASE PROVIDE RESPONSE IN SIGNED AND
 SEALED LETTER. PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. A9.73.1 THE SINK IN THE MEDIA ROOM SHALL COMPLY
 WITH ANSI A117.1 SEC 1.19.3 FIG 31 + 32
  
 9. SHT. A9.73.5 PLEASE SHOW COMPLIANCE WITH ANSI 4.15
 +4. 4.1
  
 10. SHT. A9.74.3, A9.76.3 SHOW CLEAR FLOOR SPACE FOR
 THE TOILET. PER WPB AMEND TO FBC 107.2.1
  
 11. SHT. A9.74.5, A9.75.5 PLEASE SHOW COMPLIANCE WITH
 ANSI 4.18
  
 12. THE SINKS IN THE BBQ AREA OF THE POOL DECK AND
 SUNSET DECK SHALL COMPLY WITH ANSI A117.1 SEC 4.19
  
 13. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR
 SPACES FOR THE FIXTURES IN THE ADAPTABLE BATHROOMS IN
 THE DWELLING UNITS. PER FHA GUIDELINES REQUIREMENT 7
 FIGURE 7(A)(B)(C)(D)
  
 14. IN THE GUEST BATHROOM FHA DESIGN A THE CLEAR FLOOR
 SPACE FOR THE TUB SHALL EXTEND ALL THE WAT TO THE EDGE
 OF THE TUB. . PER FHA GUIDELINES REQUIREMENT 7 FIGURE
 7(B)
  
 15. PLEASE NUMBER THE RISERS AND STACKS ON THE FLOOR
 PLANS TO ALL THE RISER AND ISOMETRIC PLANS. PER WPB
 AMEND TO FBC 107.2.1
  
 16. ON THE SANITARY COLLECTION AND RISER PLANS IT IS
 DIFFICULT TO MATCH UP THE STACKS TO THE TAG NUMBER
 PLEASE DRAW A LINE CONNECTING THE TAG TO THE STACK. PER
 WPB AMEND TO FBC 107.2.1
  
 17. AAV ARE NOT PERMITTED BELOW THE 4TH BRANCH
 INTERVALS FROM THE TOP OF THE STACK UNLESS THEY HAVE A
 RELIEF VENT CONNECTING TO A VENT STACK OR STACK VENT.
 PER FBC PL 918.3.1
  
 18. PLEASE PROVIDE A LIST WITH PLAN SHEETS P2.1.1
 THROUGH P2.22.1 MATCHED WITH THE UNIT NUMBERS. PER WPB
 AMEND TO FBC 107.2.1
  
 ON THE SANITARY COLLECTION PLAN SHEETS THERE ARE VENT
 AND DRAIN PIPES THAT ARE NOT CONNECTED PLEASE PROVIDE
 SOME KIND OF IDENTIFICATION AS TO WHERE THESE PIPE
 CONNECT. PER WPB AMEND TO FBC 107.2.1
  
 19. PLEASE LABEL THE STORM PIPING AND THE PAD, CD, AD,
 DD,OD ON THE FLOOR PLANS SO THEY MATCH UP AND CAN BE
 EASILY IDENTIFIED ON THE COLLECTION AND RISER DRAWINGS.
 PER WPB AMEND TO FBC 107.2.1
  
 20. SHT. A8.1.2 DETAIL #1 HOW WILL THE DRAIN BE
 CONNECTED TO ROOF SLAB. . PER WPB AMEND TO FBC 107.2.1
  
 21. SHT. A8.1.1 PROVIDE DIMENSIONS FOR EMERGENCY
 SCUPPERS. PER FBC PL 1108.3
  
 22. P1.11.1A, P1.11.1B, P1.11.1C, P1.11.1D PLEASE LABEL
 EACH EMERGENCY WITH THE SQFT IT WILL BE DRAINING. PER
 FBC PL 1108.3
  
 23. PROVIDE DETAIL SHOWING DIMENSION FROM THE BOTTOM OF
 THE EMERGENCY SCUPPER TO THE LOWEST POINT OF ROOF BEING
 SERVED TO SHOW COMPLIANCE WITH FBC PL 1101..7
  
 24. SHT. P3.14.1 KEY NOTE #2 PROVIDE LOCATION. PER WPB
 AMEND TO FBC 107.2.1
  
 25. SHT. P3.14.1 PLEASE SHOW FLOOR LEVEL ON THE
 ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1
  
 26. SHT. P3.16.1 LABEL ALL PIPES AND PROVIDE KEY NOTE.
 PER WPB AMEND TO FBC 107.2.1
  
 27. SHT. P3.23.1 PLACE NOTE ON PLAN THE NON POTABLE
 WATER PIPING SHALL BE LABELED. PER FBC PL 606.7
  
 28. SHT. P4.1.1 THE 4? DOUBLE SANITARY TEE CANNOT BE
 USED AS A SAMPLING PORT A 4? TWO WAY CLEAN OUT IS
 ALLOWED. PER CITY WPB UTILITIES DEPT.
  
 29. PROVIDE MANUFACTURE SIZING CALCULATIONS FOR THE
 GREASE INTERCEPTOR. PER FBC PL 1003.3.4
  
 30. SHT. P4.4.1 PROVIDE THE MANUFACTURE SPECIFICATIONS
 THAT SHOW THE UL LISTING NUMBERS AND THE NSF LISTING
 NUMBERS AND ANY OTHER STANDARDS THAT THEY MEET. PER WPB
 AMEND TO FBC 107.2.1
  
 31. SHT. P3.13.1 THE 8? HORIZONTAL DRAIN CONNECTING TO
 RISER A IS OVER THE SQFT FOR 8? PIPE. PER FBC PL TABLE
 1106.3
  
 32. SHT. P3.13.1 THE 16? HORIZONTAL DRAIN LINE IS
 MISSING THE SQFT PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 33. SHT. P3.13.1 RISER #1 IS MISSING SQFT PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 34. SHT. P3 .12.1 THE 6? HORIZONTAL DRAIN CONNECTING TO
 RISER I IS MISSING SQFT PER WPB AMEND TO FBC 107.2.1
  
 35. SHT. P3.11.1 THE 4? HORIZONTAL BRANCH DRAIN
 CONNECTING THE DD 1802 SQFT IS UNDERSIZED. PER FBC PL
 TABLE 1106.3
  
 36. SHT. P3.11.1 SIZE THE HORIZONTAL BRANCHES ON RISERS
 C, D, E. PER WPB AMEND TO FBC 107.2.1
  
 37. PLACE NOT ON PLAN POOL PLANS FOR REFERENCE ONLY
 WILL BE REVIEWED UNDER SEPARATE POOL PERMIT.
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  