2018-02-20 08:33:442ND REVIEW: FBC 2014 5TH EDITION
  
  
  
 GAS COMMENTS:
 PREVIOUS COMMENT 2ND REQUEST 1. KEY NOTE LIST THE
 RETAIL METER AS #14 THE PLAN SHOWS IT AS #16 PLEASE
 CLARIFY. AMEND TO FBC 107.2.1 METERS STILL LABELED THE
 SAME.
  
 NEW COMMENTS:
  
 1. PROVIDE INSTALLATION GUIDE FOR POOL HEATER VENTING
 AND MANUFACTURE SPECIFICATIONS FOR REGULATORS. THESE
 CAN BE DIFFERED SUBMITTALS IF REQUESTED.
  
 2. THE LONGEST RUN AFTER THE REGULATOR ON THE POOL
 HEATER IS LISTED AT 25' PER FBC FG TABLE 402.5(2) THE
 MAX FOR THAT RUN AT 1" WOULD BE 374,000 BTU IT SHALL BE
 11/4 AT 25' FOR A LOAD OF 400,000 BTU
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  