2017-11-29 09:56:17 | 290 NORTH OLIVE AVENUE - APARTMENTS/PARKING GARAGE |
| PERMIT #17110075 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| |
| SHEET A1.11.1.A: SUMBIT PRODUCT AND LISTING DATA FOR |
| PREFABRICATED FIRE TABLE. NOTE: NO OPEN FLAME WILL BE |
| PERMITTED BY THIS OFFICE. |
| |
| SHEET A1.11.1.A: OUTDOOR GRILLS (X2) - PER NFPA 1 |
| SECTION 10.11.6.1 NO HIBACHI, GRILL, OR OTHER SIMILAR |
| DEVICES USED FOR COOKING, HEATING, OR ANY OTHER PURPOSE |
| SHALL BE USED OR KINDLED ON ANY BALCONY, UNDER ANY |
| OVERHANGING PORTION, OR WITHIN 10 FEET OF ANY |
| STRUCTURE. |
| |
| SHEET A9.75.2: SUMBIT PRODUCT AND LISTING DATA FOR FIRE |
| PIT. NOTE: NO OPEN FLAME WILL BE PERMITTED BY THIS |
| OFFICE. |
| |
| SHEET A9.75.3: OUTDOOR GRILLS (X3) - PER NFPA 1 SECTION |
| 10.11.6.1 NO HIBACHI, GRILL, OR OTHER SIMILAR DEVICES |
| USED FOR COOKING, HEATING, OR ANY OTHER PURPOSE SHALL |
| BE USED OR KINDLED ON ANY BALCONY, UNDER ANY |
| OVERHANGING PORTION, OR WITHIN 10 FEET OF ANY |
| STRUCTURE. |
| |
| SHEET M1.11.1.A: SMOKE EXHAUST FAN #1 DISCHARGE IS |
| LOCATED WITHIN 6 FEET OF THE FRESH AIR INTAKE LOUVER OF |
| STAIRWELL PRESSURIZATION FAN #1. TO MY KNOWLEDGE, THE |
| CODE DOES NOT PROVIDE A REQUIRE A PRESCRIBED SEPARATION |
| DISTANCE, ONLY THAT THE SEPARATION DISTANCE IS |
| "ADEQUATE." PLEASE PROVIDE A SUPPORTING ARGUMENT AND |
| DOCUMENTATION ENSURING 6 FEET OF CLEARANCE IS ADEQUATE |
| SEPARATION TO AVOID SMOKE BEING TRANSFERRED INTO THE |
| EXIT STAIRWELL. |
| |
| SHEETS M5.0.0, M5.0.1, AND M5.0.2 ARE SUBMITTED TWICE. |
| |
| SHEET P1.1.2B AND P1.1.2C: PLUMBING PIPING IS BEING |
| ROUTED THROUGH THE FIRE RATED STAIR EXIT PASSAGEWAY. |
| PROVIDE A 2-HOUR CEILING IN THE EXIT PASSAGEWAY OR |
| REROUTE THE PLUMBING PIPING PER NFPA 101 SECTION |
| 7.1.3.2. |
| |
| SHEET E1.1.1: ELECTRICAL FEEDERS RUN THROUGH STAIRWELL |
| #2 EXIT PASSAGEWAY. PROVIDE A 2-HOUR CEILING IN THE |
| EXIT PASSAGEWAY OR REROUTE THE ELECTRICAL FEEDERS PER |
| NFPA 101 SECTION 7.1.3.2. |
| |
| SHEET E1.11.1C AND E1.11.1D: ADDITIONAL ILLUMINATED |
| EXIT SIGNS ARE NEEDED ALONG THE EXTERIOR ROOF EGRESS |
| PATH TO DIRECT OCCUPANT IN BOTH DIRECTIONS TO THE |
| STAIRS AS THIS PATH WILL BE UNFAMILIAR TO MOST |
| RESIDENTS. |
| |
| SHEET E3.0.0: PROVIDE MANUAL START AND TRANSFER |
| FEATURES IN COMMAND ROOM FOR EMERGENCY GENERATOR PER |
| NFPA 1 SECTION 11.9.5. |
| |
| GENERAL: IN SUPPORT OF THE FIRE DEPARTMENT'S GOAL TO |
| REDUCE NUISANCE AND FALSE FIRE ALARM CALLS, THIS OFFICE |
| SUGGESTS THE FIRE ALARM SYSTEM BE PROGRAMMED WITH ALARM |
| VERFICATION WITH 30-60 SECOND DELAY PER NFPA 72. (A |
| FEATURE OF AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS |
| TO REDUCE UNWANTED ALARMS WHEREIN SMOKE DETECTORS |
| REPORT ALARM CONDITIONS FOR A MINIMUM |
| PERIOD OF TIME, OR CONFIRM ALARM CONDITIONS WITHIN A |
| GIVEN TIME PERIOD AFTER BEING RESET, IN ORDER TO BE |
| ACCEPTED AS A VALID ALARM INITIATION SIGNAL.) |
| |
| SHEET FA1.1.1A: NO NOTIFICATION APPLIANCE PROVIDED IN |
| PBULIC RESTROOM #100J. |
| |
| SHEET FA1.1.1B: NO NOTIFICATION APPLIANCES PROVIDED IN |
| SEVERAL ROOMS SUCH AS TELEPHONE, STORAGE, AND |
| SWITCHGEAR ROOMS. HOW WILL THIS DESIGN MEET THE |
| AUDIBILITY REQUIREMENTS OF NFPA 72? |
| |
| SHEET FA1.1.1B: SEVERAL ROOM AND PARKING GARAGE VISUAL |
| NOTICATION APPLIANCES APPEAR TO BE COVERING AREAS |
| GREATER THAN THE LISTING OF THE APPLIANCE. FOR EXAMPLE, |
| THE SPEAKER-STROBE APPLIANCE LOCATED ON THE CORRIDOR |
| WALL OF STAIR #2 EXIT PASSAGEWAY IS COVERING NEARLY 50 |
| FEET. A 75CD WALL MOUNTED STROBE WOULD COVER |
| APPROXIMATELY 24 FEET. |
| |
| SHEET FA1.1.1C: MANUAL PULL STATIONS ARE LOCATED 6-FEET |
| FROM THE EXIT DOORS FOR THE TWO DOUBLE EGRESS DOORS IN |
| OLIVE RETAIL AND BANYAN RETAIL SPACES. PER NFPA 72 |
| SECTION 17.14.6 MANUAL FIRE ALARM BOXES SHALL BE |
| LOCATED WITHIN 60-INCHES OF THE EXIT DOORWAY OPENING AT |
| EACH EXIT ON EACH FLOOR. |
| |
| SHEET FA1.1.1D: MANUAL PULL STATIONS ARE LOCATED 6-FEET |
| FROM THE EXIT DOORS FOR THE TWO DOUBLE EGRESS DOORS |
| BANYAN RETAIL SPACE. NO NOTIFICATION APPLIANCE PROVIDED |
| IN EXIT PASSAGEWAY #107. SEVERAL PARKING GARAGE VISUAL |
| NOTICATION APPLIANCES APPEAR TO BE COVERING AREAS |
| GREATER THAN THE LISTING OF THE APPLIANCE. **CHECK |
| COVERAGES THROUGHOUT PARKING GARAGE; ALL LEVELS. |
| |
| SHEET FA1.2.1A: NO SMOKE DETECTOR PROVIDED IN LOBBY FOR |
| PHASE I ELEVATOR RECALL. |
| |
| SHEET FA1.5.1D: NO NOTIFICATION APPLIANCES PROVIDED IN |
| MENS' RESTROOM, WOMENS' RESTROOM OR POOL EQUIPMENT |
| ROOM. |
| |
| SHEET FA1.11.1A: INSUFFICIENT NOTIFICATION APPLIANCES |
| PROVIDED FOR SOUTHEAST AND SOUTHWEST AREAS OF THE ROOF |
| ASSEMBLY SPACE. |
| |
| SHEET FA1.11.1C: NO NOTIFICATION APPLIANCES PROVIDED |
| ALONG ROOF EGRESS PATH LEADING TO STAIR #3. |
| |
| SHEET FP4.0.1: INDICATE ON THE RISERS UP TO WHAT LEVELS |
| THE PRESSURE REDUCING TYPE VALVES WILL BE UTILIZED ON |
| THE SPRINKLER AND STANDPIPE SYSTEMS. |
| |
| NOTE: THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION |
| TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO |
| "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC |
| SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION |
| REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION |
| TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND |
| COMPLIANCE WITH THE FOLLOWING: |
| PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| PER TABLE 4.2.1: |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| |