2018-02-13 14:50:08 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY HAVE BEEN NOTED AS ADDRESSED. ITEMS |
| REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. NEW |
| COMMENTS FOLLOW THE PREVIOUS COMMENTS. |
| |
| 1) ADDRESSED. |
| 2) ADDRESSED. |
| 3) ADDRESSED. |
| 4) ADDRESSED. |
| 5) ADDRESSED. |
| 6) ADDRESSED. |
| 7) ADDRESSED. |
| 8) ADDRESSED. |
| 9) ADDRESSED. |
| 10) ADDRESSED. |
| 11) ADDRESSED. |
| 12) ADDRESSED. |
| 13) ADDRESSED. |
| 14) ADDRESSED. |
| 15) ADDRESSED. |
| 16) ADDRESSED. |
| 17) ADDRESSED. |
| 18) ADDRESSED. |
| 19) E4.0.0 PROVIDE SIGNAGE DETAILS FOR NUMBER OF |
| SERVICE DISCONNECTS. IT APPEARS THAT THERE ARE TWO |
| SERVICES IN QUESTION, A 120/208 SERVICE, AND A 277/480 |
| SERVICE. PRIOR TO PLAN APPROVAL, A CORRECT |
| IDENTIFICATION OF EACH SERVICE AND THE CORRESPONDING |
| MAINS WILL NEED TO BE PROVIDED, WITH A MAXIMUM OF SIX |
| SERVICE DISCONNECTS FOR EACH SERVICE PERMITTED. FIRE |
| PUMP SERVICE WILL NEED TO BE INCLUDED AS ONE OF THE |
| MAINS. NEC 230.2(E), 230.70(B), 230.71 (I SEE THE MAINS |
| HAVE BEEN RENUMBERED, BUT I ALSO REQUESTED THE SIGNAGE |
| DETAILS. PROVIDE LOCATIONS OF SIGNS FOR SERVICE AND THE |
| DETAIL OF THE SIGNS ON PLAN. FBC 107.2.1 NEC 230.2) |
| 20) E4.0.0 PROVIDE FULL LOAD CURRENT DETAIL OF FIRE |
| PUMP MOTOR, AND ANY ADDITIONAL MOTORS OR EQUIPMENT |
| ASSOCIATED, TO VERIFY CONDUCTOR SIZE FEEDING THIS |
| EQUIPMENT IS ADEQUATE. NEC 695.6(B), NEC 110.3, 695.10 |
| (I SEARCHED THE FIRE PROTECTION PLANS AND COULD NOT |
| FIND THE SPECIFICATIONS THAT YOU STATED IN THE |
| RESPONSE. PROVIDE AS PREVIOUSLY REQUESTED.) |
| 21) E4.0.0 PROVIDE SPEC SHEETS FOR BUS DUCT SYSTEMS. |
| NEC 110.3 (DEFERRED SUBMITTAL) |
| 22) ADDRESSED. |
| 23) ADDRESSED. |
| 24) E5.0.0 IT APPEARS THAT PANELS MSB1, MSB2, MSB3 ARE |
| MAIN LUG ONLY AND HAVE CAPACITY TO HAVE MORE THAN ONE |
| MAIN BREAKER, WHICH WOULD ALLOW THE SERVICE TO EXCEED |
| THE MAXIMUM NUMBER OF DISCONNECTS. PROVIDE |
| CLARIFICATION. PROVIDE SPEC SHEETS FOR SWITCHGEAR. NEC |
| 110.3, 230.71, 230.72; FBC 107.2.1 (AS THIS WILL AFFECT |
| THE NUMBER OF MAINS, THIS INFORMATION IS REQUIRED AS |
| PREVIOUSLY REQUESTED.) |
| 25) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FROM |
| POWER COMPANY AND TO PANELS TO CONFIRM THE STATED AIC |
| RATING OF PANELS IS ADEQUATE. NEC 110.9, 110.10 |
| (REQUIRED FOR MARKING OF PANELS PER NEC 110.16 AND |
| 110.24. IF YOU ARE COMFORTABLE WITH THE RATINGS OF THE |
| EQUIPMENT, WE WILL ACCEPT THIS LETTER AND CALCULATIONS |
| AS A DEFERRED SUBMITTAL WITH THE UNDERSTANDING THAT |
| THIS MUST BE PROVIDED BEFORE ANY INSPECTIONS. PROVIDE |
| NOTE ON PLAN TO THIS EFFECT.) |
| 26) ADDRESSED. |
| 27) ADDRESSED. |
| 28) E5.0.2 IT APPEARS THAT PANELS EM AND EMG ARE MAIN |
| LUG ONLY AND HAVE CAPACITY TO HAVE MORE THAN ONE MAIN |
| BREAKER, WHICH WOULD ALLOW THE SERVICE TO EXCEED THE |
| MAXIMUM NUMBER OF DISCONNECTS. PROVIDE CLARIFICATION. |
| PROVIDE SPEC SHEETS FOR SWITCHGEAR. NEC 110.3, 230.71, |
| 230.72; FBC 107.2.1 (AS THIS WILL AFFECT THE NUMBER OF |
| MAINS, THIS INFORMATION IS REQUIRED AS PREVIOUSLY |
| REQUESTED.) |
| 29) E5.0.2 PANEL GEQH SHOWS A CIRCUIT FOR THE "JOCKEY |
| PUMP". IS THIS PUMP ASSOCIATED WITH FIRE PUMP |
| EQUIPMENT, OR SOMETHING ELSE? JOCKEY PUMP FOR FIRE PUMP |
| EQUIPMENT MUST BE FED FROM SAME SERVICE AS THE FIRE |
| PUMP. CLARIFY AND/OR CORRECT. FBC 107.2.1; NEC |
| 695.4(B)(3) (RESPONSE TO THIS WAS CONFUSING AND STATED: |
| "JOCKEY PUMP SEPARATE FROM FIRE PUMP CONTROLLER." |
| SEPARATE AS IN SEPARATE LOCATION, OR SEPARATE SYSTEM. |
| WHAT IS THIS JOCKEY PUMP FOR? IF IT IS PART OF THE FIRE |
| PUMP SYSTEM, IT WILL NEED TO BE FED FROM THE FIRE PUMP |
| CONTROLLER. PROVIDE MORE CLARIFICATION.) |
| 30) ADDRESSED. |
| 31)ADDRESSED. |
| 32) ADDRESSED. |
| 33) PROVIDE GRAPH/CALCULATION OF LIGHTING POWER |
| ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| PROPOSED LIGHTING LOAD TO SHOW COMPLIANCE. FBC EC 405.5 |
| (RESPONSE LETTER STATED THIS WAS PROVIDED, BUT I COULD |
| NOT FIND ON PLAN. PROVIDE LOCATION.) |
| 34) ADDRESSED. |
| 35) ADDRESSED. |
| |
| NEW COMMENTS: |
| |
| 36) PANEL MSB1 SHOULD HAVE A CLEARANCE OF 72" BASED ON |
| THE FACT THAT THERE IS ONLY ONE MEANS OF EGRESS FOR THE |
| ELECTRICAL ROOM. IT APPEARS THAT PANEL MSB3 INVADES |
| THIS SPACE AND MSB1 ONLY HAS APPROXIMATELY 59" OF |
| CLEARANCE. PROVIDE CORRECTION. NEC 110.26(C)(2) |
| 37) SHEET E3.0.1, DETAIL 6, IT APPEARS THAT THE 1200 |
| AMP MAINS DO NOT HAVE THE REQUIRED CLEARANCE. PROVIDE |
| CORRECTION. NEC 110.26(C)(2) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |