2018-02-13 14:50:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY HAVE BEEN NOTED AS ADDRESSED. ITEMS
 REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. NEW
 COMMENTS FOLLOW THE PREVIOUS COMMENTS.
  
 1) ADDRESSED.
 2) ADDRESSED.
 3) ADDRESSED.
 4) ADDRESSED.
 5) ADDRESSED.
 6) ADDRESSED.
 7) ADDRESSED.
 8) ADDRESSED.
 9) ADDRESSED.
 10) ADDRESSED.
 11) ADDRESSED.
 12) ADDRESSED.
 13) ADDRESSED.
 14) ADDRESSED.
 15) ADDRESSED.
 16) ADDRESSED.
 17) ADDRESSED.
 18) ADDRESSED.
 19) E4.0.0 PROVIDE SIGNAGE DETAILS FOR NUMBER OF
 SERVICE DISCONNECTS. IT APPEARS THAT THERE ARE TWO
 SERVICES IN QUESTION, A 120/208 SERVICE, AND A 277/480
 SERVICE. PRIOR TO PLAN APPROVAL, A CORRECT
 IDENTIFICATION OF EACH SERVICE AND THE CORRESPONDING
 MAINS WILL NEED TO BE PROVIDED, WITH A MAXIMUM OF SIX
 SERVICE DISCONNECTS FOR EACH SERVICE PERMITTED. FIRE
 PUMP SERVICE WILL NEED TO BE INCLUDED AS ONE OF THE
 MAINS. NEC 230.2(E), 230.70(B), 230.71 (I SEE THE MAINS
 HAVE BEEN RENUMBERED, BUT I ALSO REQUESTED THE SIGNAGE
 DETAILS. PROVIDE LOCATIONS OF SIGNS FOR SERVICE AND THE
 DETAIL OF THE SIGNS ON PLAN. FBC 107.2.1 NEC 230.2)
 20) E4.0.0 PROVIDE FULL LOAD CURRENT DETAIL OF FIRE
 PUMP MOTOR, AND ANY ADDITIONAL MOTORS OR EQUIPMENT
 ASSOCIATED, TO VERIFY CONDUCTOR SIZE FEEDING THIS
 EQUIPMENT IS ADEQUATE. NEC 695.6(B), NEC 110.3, 695.10
 (I SEARCHED THE FIRE PROTECTION PLANS AND COULD NOT
 FIND THE SPECIFICATIONS THAT YOU STATED IN THE
 RESPONSE. PROVIDE AS PREVIOUSLY REQUESTED.)
 21) E4.0.0 PROVIDE SPEC SHEETS FOR BUS DUCT SYSTEMS.
 NEC 110.3 (DEFERRED SUBMITTAL)
 22) ADDRESSED.
 23) ADDRESSED.
 24) E5.0.0 IT APPEARS THAT PANELS MSB1, MSB2, MSB3 ARE
 MAIN LUG ONLY AND HAVE CAPACITY TO HAVE MORE THAN ONE
 MAIN BREAKER, WHICH WOULD ALLOW THE SERVICE TO EXCEED
 THE MAXIMUM NUMBER OF DISCONNECTS. PROVIDE
 CLARIFICATION. PROVIDE SPEC SHEETS FOR SWITCHGEAR. NEC
 110.3, 230.71, 230.72; FBC 107.2.1 (AS THIS WILL AFFECT
 THE NUMBER OF MAINS, THIS INFORMATION IS REQUIRED AS
 PREVIOUSLY REQUESTED.)
 25) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FROM
 POWER COMPANY AND TO PANELS TO CONFIRM THE STATED AIC
 RATING OF PANELS IS ADEQUATE. NEC 110.9, 110.10
 (REQUIRED FOR MARKING OF PANELS PER NEC 110.16 AND
 110.24. IF YOU ARE COMFORTABLE WITH THE RATINGS OF THE
 EQUIPMENT, WE WILL ACCEPT THIS LETTER AND CALCULATIONS
 AS A DEFERRED SUBMITTAL WITH THE UNDERSTANDING THAT
 THIS MUST BE PROVIDED BEFORE ANY INSPECTIONS. PROVIDE
 NOTE ON PLAN TO THIS EFFECT.)
 26) ADDRESSED.
 27) ADDRESSED.
 28) E5.0.2 IT APPEARS THAT PANELS EM AND EMG ARE MAIN
 LUG ONLY AND HAVE CAPACITY TO HAVE MORE THAN ONE MAIN
 BREAKER, WHICH WOULD ALLOW THE SERVICE TO EXCEED THE
 MAXIMUM NUMBER OF DISCONNECTS. PROVIDE CLARIFICATION.
 PROVIDE SPEC SHEETS FOR SWITCHGEAR. NEC 110.3, 230.71,
 230.72; FBC 107.2.1 (AS THIS WILL AFFECT THE NUMBER OF
 MAINS, THIS INFORMATION IS REQUIRED AS PREVIOUSLY
 REQUESTED.)
 29) E5.0.2 PANEL GEQH SHOWS A CIRCUIT FOR THE "JOCKEY
 PUMP". IS THIS PUMP ASSOCIATED WITH FIRE PUMP
 EQUIPMENT, OR SOMETHING ELSE? JOCKEY PUMP FOR FIRE PUMP
 EQUIPMENT MUST BE FED FROM SAME SERVICE AS THE FIRE
 PUMP. CLARIFY AND/OR CORRECT. FBC 107.2.1; NEC
 695.4(B)(3) (RESPONSE TO THIS WAS CONFUSING AND STATED:
 "JOCKEY PUMP SEPARATE FROM FIRE PUMP CONTROLLER."
 SEPARATE AS IN SEPARATE LOCATION, OR SEPARATE SYSTEM.
 WHAT IS THIS JOCKEY PUMP FOR? IF IT IS PART OF THE FIRE
 PUMP SYSTEM, IT WILL NEED TO BE FED FROM THE FIRE PUMP
 CONTROLLER. PROVIDE MORE CLARIFICATION.)
 30) ADDRESSED.
 31)ADDRESSED.
 32) ADDRESSED.
 33) PROVIDE GRAPH/CALCULATION OF LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 PROPOSED LIGHTING LOAD TO SHOW COMPLIANCE. FBC EC 405.5
 (RESPONSE LETTER STATED THIS WAS PROVIDED, BUT I COULD
 NOT FIND ON PLAN. PROVIDE LOCATION.)
 34) ADDRESSED.
 35) ADDRESSED.
  
 NEW COMMENTS:
  
 36) PANEL MSB1 SHOULD HAVE A CLEARANCE OF 72" BASED ON
 THE FACT THAT THERE IS ONLY ONE MEANS OF EGRESS FOR THE
 ELECTRICAL ROOM. IT APPEARS THAT PANEL MSB3 INVADES
 THIS SPACE AND MSB1 ONLY HAS APPROXIMATELY 59" OF
 CLEARANCE. PROVIDE CORRECTION. NEC 110.26(C)(2)
 37) SHEET E3.0.1, DETAIL 6, IT APPEARS THAT THE 1200
 AMP MAINS DO NOT HAVE THE REQUIRED CLEARANCE. PROVIDE
 CORRECTION. NEC 110.26(C)(2)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  