Date |
Text |
2017-12-06 08:18:56 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1) E1.1.1 BE ADVISED THAT FIRE ALARM, LOW VOLTAGE |
| SYSTEMS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL |
| HOOD SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| 107.2.1 |
| 2) E1.1.1A MAIN SWITCHGEAR ROOM DOES NOT SHOW AUTOMATIC |
| LIGHTING CONTROL NEEDED PER FBC EC 405.2.2 PROVIDE |
| CORRECTION. |
| 3) E1.1.1B EMERGENCY SWITCH GEAR ROOM, TV/PHONE ROOM, |
| BACKFLOW ROOM, AND FIRE PUMP ROOM DO NOT SHOW AUTOMATIC |
| LIGHTING CONTROL NEEDED PER FBC EC 405.2.2 PROVIDE |
| CORRECTION. |
| 4) E1.2.1A PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR GENERATOR ROOM. ALSO, HOW ARE PARKING |
| GARAGE LIGHTS CONTROLLED? FBC 107.2.1 |
| 5) E1.3.1C PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR METER ROOM. |
| 6) E1.4.1A PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR EQUIPMENT ROOM THAT HAS CU-5-1, CU-5-2, |
| CU-4-3, AND CU-4-4. |
| 7) E1.4.1C PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR EQUIPMENT ROOM THAT HAS RETAIL CU?S. |
| 8) E1.5.1A PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR CLUB ROOM, AND OUTDOOR AREAS. |
| 9) E1.5.1B PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR ELECTRICAL CLOSET. |
| 10) E1.6.1B PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR ELECTRICAL CLOSET. |
| 11) E1.6.1C PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR ELECTRICAL CLOSET. |
| 12) E1.6.1D PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR ELECTRICAL CLOSET. |
| 13) E1.11.1A ALL EXTERIOR WP RECEPTACLES NEED GFCI |
| PROTECTION. PROVIDE CORRECTION. NEC 210.8 ALSO, SEE NO |
| AUTOMATIC LIGHTING CONTROL PER FBC EC 405.2.2 FOR |
| RESTROOMS OR ELEVATOR CLOSET LIGHT (RH-2). HOW ARE |
| EXTERIOR LIGHTS CONTROLLED? FBC 107.2.1 |
| 14) E1.11.1B PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR ELECTRICAL CLOSET. |
| 15) E1.11.1D PROVIDE AUTOMATIC LIGHTING CONTROL PER FBC |
| EC 405.2.2 FOR ELECTRICAL AND ELEVATOR CLOSET. |
| 16) E2.1.1 DINING ROOM RECEPTACLES AND LIGHTING ARE NOT |
| PERMITTED TO BE ON SAME CIRCUIT. PROVIDE CORRECTION. |
| NEC 210.52(B)(2) |
| 17) E2.13.1 DINING ROOM RECEPTACLES AND LIGHTING ARE |
| NOT PERMITTED TO BE ON SAME CIRCUIT. PROVIDE |
| CORRECTION. NEC 210.52(B)(2) |
| 18) E2.15.1 DINING ROOM RECEPTACLES AND LIGHTING ARE |
| NOT PERMITTED TO BE ON SAME CIRCUIT. PROVIDE |
| CORRECTION. NEC 210.52(B)(2) |
| 19) E4.0.0 PROVIDE SIGNAGE DETAILS FOR NUMBER OF |
| SERVICE DISCONNECTS. IT APPEARS THAT THERE ARE TWO |
| SERVICES IN QUESTION, A 120/208 SERVICE, AND A 277/480 |
| SERVICE. PRIOR TO PLAN APPROVAL, A CORRECT |
| IDENTIFICATION OF EACH SERVICE AND THE CORRESPONDING |
| MAINS WILL NEED TO BE PROVIDED, WITH A MAXIMUM OF SIX |
| SERVICE DISCONNECTS FOR EACH SERVICE PERMITTED. FIRE |
| PUMP SERVICE WILL NEED TO BE INCLUDED AS ONE OF THE |
| MAINS. NEC 230.2(E), 230.70(B), 230.71 |
| 20) E4.0.0 PROVIDE FULL LOAD CURRENT DETAIL OF FIRE |
| PUMP MOTOR, AND ANY ADDITIONAL MOTORS OR EQUIPMENT |
| ASSOCIATED, TO VERIFY CONDUCTOR SIZE FEEDING THIS |
| EQUIPMENT IS ADEQUATE. NEC 695.6(B), NEC 110.3, 695.10 |
| 21) E4.0.0 PROVIDE SPEC SHEETS FOR BUS DUCT SYSTEMS. |
| NEC 110.3 |
| 22) E4.0.0 DRAWING KEY NOTE # 5 REFERENCES NEC 700.8, |
| WHICH DOES NOT EXIST IN THE 2011 NEC. PROVIDE |
| CORRECTION. NEC 700.7 |
| 23) E4.0.0 FEEDER SCHEDULE DOES NOT SHOW ALL FEEDERS ON |
| RISER DIAGRAM. PROVIDE DETAILS FOR ALL FEEDERS. NEC |
| 215.5; FBC 107.2.1 |
| 24) E5.0.0 IT APPEARS THAT PANELS MSB1, MSB2, MSB3 ARE |
| MAIN LUG ONLY AND HAVE CAPACITY TO HAVE MORE THAN ONE |
| MAIN BREAKER, WHICH WOULD ALLOW THE SERVICE TO EXCEED |
| THE MAXIMUM NUMBER OF DISCONNECTS. PROVIDE |
| CLARIFICATION. PROVIDE SPEC SHEETS FOR SWITCHGEAR. NEC |
| 110.3, 230.71, 230.72; FBC 107.2.1 |
| 25) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FROM |
| POWER COMPANY AND TO PANELS TO CONFIRM THE STATED AIC |
| RATING OF PANELS IS ADEQUATE. NEC 110.9, 110.10 |
| 26) E5.0.1 PANEL BL CIRCUIT 47,49, AND PANEL RTH |
| CIRCUIT 17, SHOW OUTDOOR LIGHTING BEING FED VIA |
| PHOTOCELL. FBC ENERGY STATES: ?LIGHTING NOT DESIGNATED |
| FOR DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY |
| EITHER A COMBINATION OF A PHOTOSENSOR AND A TIME |
| SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING |
| DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR A |
| PHOTOSENSOR.? CLARIFY WHAT TYPE OF LOAD THIS IS. FBC |
| 107.2.1; FBC EC 405.2.4 |
| 27) E5.0.1 NO LOAD CALCULATION OR PANEL SCHEDULES |
| PROVIDED FOR PANEL MSB5. IN PANEL SCHEDULE FOR PANEL |
| RTH, PLAN SHOWS THIS BEING FED FROM MSB4, BUT RISER |
| DIAGRAM SHOWS IT BEING FED FROM MSB5. CURRENTLY, LOAD |
| CALCULATION FOR MSB4 DOES NOT INCLUDE PANEL RTH. |
| CLARIFY AND/OR CORRECT. PROVIDE ALL DETAILS FOR MSB5. |
| HOW ARE LOADS FOR RETAIL AREAS CALCULATED? FBC 107.2.1; |
| NEC 215.5, 408.4 |
| 28) E5.0.2 IT APPEARS THAT PANELS EM AND EMG ARE MAIN |
| LUG ONLY AND HAVE CAPACITY TO HAVE MORE THAN ONE MAIN |
| BREAKER, WHICH WOULD ALLOW THE SERVICE TO EXCEED THE |
| MAXIMUM NUMBER OF DISCONNECTS. PROVIDE CLARIFICATION. |
| PROVIDE SPEC SHEETS FOR SWITCHGEAR. NEC 110.3, 230.71, |
| 230.72; FBC 107.2.1 |
| 29) E5.0.2 PANEL GEQH SHOWS A CIRCUIT FOR THE ?JOCKEY |
| PUMP?. IS THIS PUMP ASSOCIATED WITH FIRE PUMP |
| EQUIPMENT, OR SOMETHING ELSE? JOCKEY PUMP FOR FIRE PUMP |
| EQUIPMENT MUST BE FED FROM SAME SERVICE AS THE FIRE |
| PUMP. CLARIFY AND/OR CORRECT. FBC 107.2.1; NEC |
| 695.4(B)(3) |
| 30) E5.0.3 PANEL REQHN IS LABELED AS ?SECTION 2 OF 2?. |
| RISER DIAGRAM ONLY SHOWS THIS PANEL IN ONE LOCATION AND |
| WITH 1 SECTION. NO OTHER PANEL SCHEDULE EXIST FOR |
| ?SECTION 1?. CLARIFY AND/OR CORRECT. FBC 107.2.1 |
| 31) E5.0.4, E5.0.5, E5.0.6 PROVIDE AFCI PROTECTION PER |
| CODE. (MAYBE THAT?S WHAT THE NOTES ABOVE ARE FOR?) NEC |
| 210.12 |
| 32) E5.0.4, E5.0.5, E5.0.6 PANEL SCHEDULES SHOW THE |
| WATER HEATER ON A 30 AMP BREAKER. STANDARD WATER |
| HEATERS WITH A 4500 WATT ELEMENT DRAW 16.25 AMPS ON 208 |
| VOLTS, MULTIPLIED TIMES 1.25 EQUALS 20.31 AMPS. THE |
| NEXT HIGHEST SIZE IS 25 AMPS. PROVIDE CORRECTION. NEC |
| 422.13 |
| 33) PROVIDE GRAPH/CALCULATION OF LIGHTING POWER |
| ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| PROPOSED LIGHTING LOAD TO SHOW COMPLIANCE. FBC EC 405.5 |
| 34) PROVIDE NOTE THAT LIGHTING IN CLOSETS TO COMPLY |
| WITH NEC 410.16. |
| 35) PROVIDE NOTE THAT LIGHTING IN DAMP LOCATIONS TO |
| COMPLY WITH NEC 410.10. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |