2018-06-04 10:33:30 | ****PROVISOS**** |
| ****ISSUED AT APPLICANT'S RISK**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. GENERAL COMMENT, FBC 107, SOME FMEP COMMENTS ARE |
| ALSO FBC B REQUIREMENTS. A BUILDING REVIEW ON THESE |
| ITEMS WILL BE DONE UPON RESUBMITTAL. |
| |
| 2. REVISION REQUIRED PRIOR TO INSTALLATION - FBC 107, |
| 6-A6.4.1, A 2 HOUR HORIZONTAL SHAFT WALL SYSTEM IS |
| SHOWN AND REFERS TO DETAILS 13 AND 14 ON A10.0.1. |
| DETAIL 14 SPECS "1 HOUR RATED SHAFTWALL ASSEMBLIES". |
| SHAFT IS TO BE 2 HOUR, A HORIZONTAL ASSEMBLY IS TO BE |
| SPECIFIED RATHER THAN A WALL ASSEMBLY. PROVIDE LISTING |
| WHICH ADDRESSES USE OF U415 UTILIZED IN A HORIZONTAL |
| ORIENTATION OR REVISE DETAIL. |
| |
| DETAIL TO COMPLY WITH FBC B 717.3.1, 713.4, 703.2.1 |
| (ALSO 713.14, 909.21.3 IF APPLICABLE). |
| |
| 3. FBC B 403.4, 907.2.13.1, 907.3.3, 907.3.4, AUTOMATIC |
| SMOKE DETECTION TO BE IN ACCORDANCE WITH THIS SECTION. |
| FIRE ALARM IS UNDER A SEPARATE PERMIT; PLANS ARE TO |
| COMPLY WITH OR CLARIFY THE FOLLOWING: |
| |
| SHEET FA1.0.0, THE FIRE ALARM LEGEND AND OTHER TEXT ON |
| THE PAGE ARE TOO LIGHT TO BE LEGIBLE. |
| SHEET FA1.1.1A, FBC B 970.2.13.1.1(1), A SMOKE DETECTOR |
| IS REQUIRED IN THE TRANSFORMER VAULT. |
| THE GRAPHIC IN THE EMERGENCY SWITCH GEAR ROOM WITH TEXT |
| R/F IS NOT ON THE LEGEND BUT IS SIMILAR TO THE GRAPHIC |
| FOR "HEAT DETECTOR SENSOR BASE"; CLARIFY. WHAT IS R/F? |
| DOES THIS DEVICE MEET THE REQUIREMENT IN FBC B |
| 907.2.13.1.1? |
| GRAPHICS ARE NOT CLEAR. SEE FA1.3.1A, SEE STAIR #2 ON |
| FIRST FLOOR (AND OTHER LOCATIONS), CLARIFY WHAT S IN A |
| PLAIN SQUARE DEPICTS. ALSO CLARIFY WHY THE EXIT |
| PASSAGEWAYS/EXIT CORRIDORS DO NOT HAVE ANY DEVICES; ARE |
| THE EXEMPTED? |
| HOW WILL THE REQUIREMENTS OF FBC B 908.7.1 BE MET? |
| |
| 4. FBC B 403.5.3, REVISE PLAN TO SHOW COMPLIANCE. |
| |
| RESPONSE STATES THAT E3.0.0 FIRE COMMAND ROOM HAS A |
| DOOR UNLOCKING DEVICE; PLEASE HAVE ENGINEER ADVISE AS |
| TO WHERE THIS CAN BE FOUND. IT DOES NOT APPEAR TO BE |
| ONE OF THE "FIRE COMMAND ROOM KEYNOTES" OR REVISE PLAN |
| TO INCLUDE. |
| |
| 5. FBC B TABLE 705.8, CLARIFY HOW <15% WAS DETERMINED |
| FOR THE WALL WHICH OPENS TO ALLOW HOTEL ACCESS. |
| |
| RESPONSE WILL BE DISCUSSED WITH BUILDING OFFICIAL AND |
| ABO. WALL PERCENTAGE CALCULATIONS ARE DONE BASED ON THE |
| WALL PORTION WHICH IS AFFECTED (PORTION WHICH IS >3' |
| FROM PROPERTY LINE). ON LS1.1 THE CALCULATION UTILIZES |
| THE ENTIRE WALL LENGTH. IT IS POSSIBLE THAT THIS WILL |
| BE PERMITTED DEPENDING ON OPENINGS ON THE ADJACENT |
| PROPERTY IN THIS LOCATION. PROVIDE INFORMATION |
| REGARDING OPENINGS ON THE OTHER SIDE OF THE LOT LINE. |
| |
| 6. THIS PARCEL IS LOCATED IN A SPECIAL FLOOD HAZARD |
| AREA; FLOOD MAP IN EFFECT AT TIME OF FOUNDATION PERMIT |
| APPLICATION 1979 FIRMS + 1' FREEBOARD; MINIMUM |
| ELEVATION = 8.0' NGVD29, PROPOSED LOWEST FINISHED FLOOR |
| ELEVATION = 9.0' NGVD29 |
| A "CONSTRUCTION DRAWING" ELEVATION CERTIFICATE IS |
| RECOMMENDED AT THIS TIME TO AVOID FUTURE DELAYS |
| (CORRECTIONS, IF APPLICABLE, WILL NOT DELAY PERMIT |
| ISSUANCE) |
| A "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE |
| OR FORM BOARD SURVEY IS REQUIRED PRIOR TO CONCRETE |
| POUR. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW |
| A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE IS |
| REQUIRED PRIOR TO FINAL INSPECTION AND/OR CO AND/OR |
| TCO. |
| |
| 7. BARN DOORS TO MAINTAIN THE 25SF LOUVERS, A1.3.1 AND |
| OTHER SHEETS UP TO 3RD FLOOR, FOR COMPLIANCE WITH FBC B |
| 1029.1, OK PER RB. |
| |
| 8. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE |
| FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS |
| SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR |
| PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS, |
| STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS |
| REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW |
| AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION. |
| |
| COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH |
| PRESSURES SHOWN ON SHEET S0.0.5) |
| FBC B 2403.2, SEMI FRAMELESS SHOWER ENCLOSURE |
| ENGINEERING |
| GLASS GUARDS DELEGATED ENGINEERING |
| BALCONY ALUMINUM GUARDRAILS DELEGATED ENGINEERING |
| POOL DECK GUARDRAILS DELEGATED ENGINEERING |
| ALUCOBOND, PROVIDE PRODUCT APPROVALS AND SPEC SHEETS TO |
| SHOW COMPLIANCE WITH FBC B 602.2, 1 |
| TERRACORP, SPEC SHEETS SHOWING COMPLIANCE WITH |
| REQUIREMENTS FOR NON COMBUSTIBLE BUILDINGS, |
| INSTALLATION DETAILS FBC B 1609 |
| DECORATIVE MESH COLUMN ENCLOSURE SHOWN ON A3.1.14 AND |
| OTHER SHEETS, FBC B 602.2 (NON COMBUSTIBLE), 1609 |
| (RESISTANCE TO WIND LOADS), PROVIDE SPEC SHEETS AND |
| PRODUCT APPROVAL OR ENGINEERING TO SHOW COMPLIANCE |
| |
| 9. FBC 1207.2, 1207.3, FIELD TESTING FOR STC/IIC WILL |
| BE DONE, LVT ENVIROQUIET II (NOTE: 8" CONCRETE SLABS) |
| WHISPER MAT CS IS PROPOSED BUT DOES NOT HAVE A FLAME |
| SPREAD TEST FOR LVT. PLEASE CONTACT ME IN A FEW WEEKS; |
| AT THIS TIME THE WHISPER MAT CS SPEC SHEET HAS BEEN |
| VOIDED, BUT WE ARE CURRENTLY EVALUATING THIS AND OTHER |
| UNDERLAYMENTS IN THIS APPLICATION. |
| |
| 10. THE FOLLOWING ITEMS MAY REQUIRE A DETAIL OR SPEC |
| SHEETS TO BE SUBMITTED SUBJECT TO INSPECTOR'S |
| DISCRETION: |
| FBC B 603, "WOOD SLATS AT ROOF FASCIA" IS SHOWN; |
| PROVIDE SPEC SHEETS AT INSPECTION TO SHOW COMPLIANCE. |
| FBC B 603.1 2-A8.3.3 AND OTHER LOCATIONS, IPE WOOD IS |
| PROPOSED; PROVIDE SPEC SHEETS AT INSPECTION TO SHOW |
| COMPLIANCE. |
| FBC A FAIR HOUSING REQUIREMENT 2 ANSI 4.1-4.3.1, |
| RECEPTION DESK IN RESIDENTS LOBBY TO COMPLY. |
| FBC B 603.1(15), A3.1.11 AND OTHER SHEETS, KRINKLGLAS, |
| SHOWN ON VARIOUS PAGES, TO COMPLY WITH CHAPTER 26 |
| |
| 11. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) |
| ARE REQUIRED FOR: |
| LIGHT POLES/SITE LIGHTING |
| SWIMMING POOL |
| FIRE ALARM |
| FIRE SPRINKLER |
| LOW VOLTAGE |
| ACCESS |
| LANDSCAPING |
| IRRIGATION |
| ALL OTHER ITEMS OTHER THAN BMEP |
| |
| 12. PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A |
| PDF VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL. |
| |
| 13. AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED |
| PRIOR TO C.O. |
| |
| 14. SHORING/RESHORE ENGINEERING IS REQUIRED TO BE |
| SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. THE |
| ENGINEERING IS TO BE SUBMITTED, REVIEWED AND ISSUED |
| PRIOR TO CONCRETE POUR. |
| |
| 15. A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS |
| REQUIRED TO BE PROVIDED PRIOR TO INSTALLATION. |
| |
| |
| |