2018-05-27 14:54:04 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| COMMENTS FROM PREVIOUS LIST: |
| |
| 22. GENERAL COMMENT, FBC 107, SOME FMEP COMMENTS ARE |
| ALSO FBC B REQUIREMENTS. A BUILDING REVIEW ON THESE |
| ITEMS WILL BE DONE UPON RESUBMITTAL. |
| |
| 23-28. OK |
| |
| 29. FBC 107, 6-A6.4.1, A 2 HOUR HORIZONTAL SHAFT WALL |
| SYSTEM IS SHOWN AND REFERS TO DETAILS 13 AND 14 ON |
| A10.0.1. DETAIL 14 SPECS "1 HOUR RATED SHAFTWALL |
| ASSEMBLIES". SHAFT IS TO BE 2 HOUR, A HORIZONTAL |
| ASSEMBLY IS TO BE SPECIFIED RATHER THAN A WALL |
| ASSEMBLY. PROVIDE LISTING WHICH ADDRESSES USE OF U415 |
| UTILIZED IN A HORIZONTAL ORIENTATION OR REVISE DETAIL. |
| |
| 3RD REVIEW, RESPONSE LETTER STATES THAT UL U497 WAS |
| ADDED AND HAS HORIZONTAL ASSEMBLIES. PLEASE SEE THE |
| DETAIL AT THIS WEBSITE: |
| |
| HTTP://DATABASE.UL.COM/CGI-BIN/XYV/TEMPLATE/LISEXT/1FRA |
| ME/SHOWPAGE.HTML?NAME=BXUV.U497&CCNSHORTTITLE=FIRE-RESI |
| STANCE+RATINGS+-+ANSI/UL+263&OBJID=1074330896&CFGID=107 |
| 3741824&VERSION=VERSIONLESS&PARENT_ID=1073984818&SEQUEN |
| CE=1 |
| |
| UL U ASSEMBLIES ARE FOR WALLS (VERTICAL). I WAS UNABLE |
| TO LOCATE THE ASSEMBLY WHI694-0300.2; PLEASE PROVIDE. |
| |
| PLEASE SEND A PROPOSED DETAIL VIA EMAIL. DETAIL TO |
| COMPLY WITH FBC B 717.3.1, 713.4, 703.2.1 (ALSO 713.14, |
| 909.21.3 IF APPLICABLE). PLEASE CONTACT ME TO DISCUSS. |
| THIS REQUIREMENT WAS CONFIRMED WITH A FBC ISSUED |
| DECLARATORY STATEMENT. |
| |
| 30-35. OK |
| |
| 36. FBC B 403.4, 907.2.13.1, 907.3.3, 907.3.4, |
| AUTOMATIC SMOKE DETECTION TO BE IN ACCORDANCE WITH THIS |
| SECTION. FIRE ALARM IS UNDER A SEPARATE PERMIT WHICH IS |
| NOT REVIEWED BY BUILDING. PLEASE REVISE PLAN TO NOTE |
| COMPLIANCE. |
| |
| ARCHITECT'S RESPONSE IS THAT THEY PREFER THAT THE FIRE |
| ALARM DRAWINGS ARE REVIEWED AT THIS TIME. PLEASE REVISE |
| THE FOLLOWING: |
| |
| SHEET FA1.0.0, THE FIRE ALARM LEGEND AND OTHER TEXT ON |
| THE PAGE ARE TOO LIGHT TO BE LEGIBLE. |
| SHEET FA1.1.1A, FBC B 970.2.13.1.1(1), A SMOKE DETECTOR |
| IS REQUIRED IN THE TRANSFORMER VAULT. |
| THE GRAPHIC IN THE EMERGENCY SWITCH GEAR ROOM WITH TEXT |
| R/F IS NOT ON THE LEGEND BUT IS SIMILAR TO THE GRAPHIC |
| FOR "HEAT DETECTOR SENSOR BASE"; CLARIFY. WHAT IS R/F? |
| DOES THIS DEVICE MEET THE REQUIREMENT IN FBC B |
| 907.2.13.1.1? |
| GRAPHICS ARE NOT CLEAR. SEE FA1.3.1A, SEE STAIR #2 ON |
| FIRST FLOOR (AND OTHER LOCATIONS), CLARIFY WHAT S IN A |
| PLAIN SQUARE DEPICTS. ALSO CLARIFY WHY THE EXIT |
| PASSAGEWAYS/EXIT CORRIDORS DO NOT HAVE ANY DEVICES; ARE |
| THE EXEMPTED? |
| HOW WILL THE REQUIREMENTS OF FBC B 908.7.1 BE MET? |
| |
| IT IS POSSIBLE THAT, IF FIRE PROTECTION ENGINEER |
| CONTACTS ME TO ADVISE HOW THESE ISSUES WILL BE |
| ADDRESSED WHEN THE FIRE ALARM PERMIT IS SUBMITTED, THIS |
| CAN BE A PROVISO ITEM. |
| |
| 37. FBC B 403.5.3, COMPLIANCE NOT CLEAR, PLEASE ADVISE |
| WHERE STAIRWAY DOOR LOCKING IS ADDRESSED, OR REVISE |
| PLAN TO SHOW COMPLIANCE. |
| |
| RESPONSE STATES THAT E3.0.0 FIRE COMMAND ROOM HAS A |
| DOOR UNLOCKING DEVICE; PLEASE HAVE ENGINEER ADVISE AS |
| TO WHERE THIS CAN BE FOUND. IT DOES NOT APPEAR TO BE |
| ONE OF THE "FIRE COMMAND ROOM KEYNOTES". |
| |
| RESPONSE LETTER ALSO STATES THAT ACCESS CONTROL |
| DRAWINGS 840-849 INDICATE WHICH DOORS AND THE CONTROLS |
| FOR THESE DOORS TO LOCK AND UNLOCK. THESE PAGES ARE NOT |
| DESIGNED BY AN ARCHITECT OR ENGINEER AND CANNOT BE USED |
| TO DEMONSTRATE CODE COMPLIANCE. ALL DOORS ARE REQUIRED |
| TO RELEASE. |
| |
| IT IS POSSIBLE THAT, IF FIRE PROTECTION ENGINEER |
| CONTACTS ME TO CLARIFY, THIS CAN BE A PROVISO ITEM. |
| |
| 38. FBC B TABLE 705.8, CLARIFY HOW <15% WAS DETERMINED |
| FOR THE WALL WHICH OPENS TO ALLOW HOTEL ACCESS. |
| |
| 3RD REVIEW; RESPONSE WILL BE DISCUSSED WITH BUILDING |
| OFFICIAL AND ABO. WALL PERCENTAGE CALCULATIONS ARE DONE |
| BASED ON THE WALL PORTION WHICH IS AFFECTED (PORTION |
| WHICH IS >3' FROM PROPERTY LINE). ON LS1.1 THE |
| CALCULATION UTILIZES THE ENTIRE WALL LENGTH. IT IS |
| POSSIBLE THAT THIS WILL BE PERMITTED DEPENDING ON |
| OPENINGS ON THE ADJACENT PROPERTY IN THIS LOCATION. IF |
| READILY AVAILABLE, PROVIDE THIS INFORMATION VIA EMAIL. |
| IF NOT READILY AVAILABLE TO ARCHITECT, I CAN GET IT |
| FROM THE HOTEL PERMIT DOCUMENTS. |
| |
| 39-40. OK |
| |
| 41. REGARDING THRESHOLD STATEMENT, RESPONSE IS THAT |
| THIS IS ON EVERY STRUCTURAL PAGE. I APOLOGIZE FOR THE |
| COMMENT NOT BEING CLEAR; I CANNOT LOCATE THIS STATEMENT |
| ON THE ARCHITECTURAL PLANS. STATUTE STATES: |
| |
| W.P.B. AMENDMENT 110.3.7.4.4, FS553.79(7)(D): ALL PLANS |
| FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND |
| SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A |
| STATEMENT THAT, TO THE BEST OF THE ARCHITECT'S OR |
| ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS |
| COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND |
| THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY |
| THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND |
| CHAPTER 633. |
| |
| IF YOU ARE OF THE OPINION THAT THE ARCHITECT IS NOT |
| REQUIRED TO INCLUDE THE THRESHOLD STATEMENT, PLEASE |
| ADVISE AND I'LL DO FURTHER RESEARCH. ALL THRESHOLD |
| BUILDINGS THAT I'VE REVIEWED HAVE INCLUDED THE |
| STATEMENT BY BOTH ARCHITECT AND ENGINEER, EITHER ON ALL |
| PAGES OR ON ONE PAGE. |
| |
| 42. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| PROVISOS: |
| |
| A. THIS PARCEL IS LOCATED IN A SPECIAL FLOOD HAZARD |
| AREA; FLOOD MAP IN EFFECT AT TIME OF FOUNDATION PERMIT |
| APPLICATION 1979 FIRMS + 1' FREEBOARD; MINIMUM |
| ELEVATION = 8.0' NGVD29, PROPOSED LOWEST FINISHED FLOOR |
| ELEVATION = 9.0' NGVD29 |
| A "CONSTRUCTION DRAWING" ELEVATION CERTIFICATE IS |
| RECOMMENDED AT THIS TIME TO AVOID FUTURE DELAYS |
| (CORRECTIONS, IF APPLICABLE, WILL NOT DELAY PERMIT |
| ISSUANCE) |
| A "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE |
| OR FORM BOARD SURVEY IS REQUIRED PRIOR TO CONCRETE |
| POUR. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW |
| A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE IS |
| REQUIRED PRIOR TO FINAL INSPECTION AND/OR CO AND/OR |
| TCO. |
| |
| B. BARN DOORS TO MAINTAIN THE 25SF LOUVERS, A1.3.1 AND |
| OTHER SHEETS UP TO 3RD FLOOR, FOR COMPLIANCE WITH FBC B |
| 1029.1, OK PER RB. |
| |
| C. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE |
| FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS |
| SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR |
| PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS, |
| STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS |
| REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW |
| AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION. |
| |
| COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH |
| PRESSURES SHOWN ON SHEET S0.0.5) |
| FBC B 2403.2, SEMI FRAMELESS SHOWER ENCLOSURE |
| ENGINEERING |
| GLASS GUARDS DELEGATED ENGINEERING |
| BALCONY ALUMINUM GUARDRAILS DELEGATED ENGINEERING |
| POOL DECK GUARDRAILS DELEGATED ENGINEERING |
| ALUCOBOND, PROVIDE PRODUCT APPROVALS AND SPEC SHEETS TO |
| SHOW COMPLIANCE WITH FBC B 602.2, 1 |
| TERRACORP, SPEC SHEETS SHOWING COMPLIANCE WITH |
| REQUIREMENTS FOR NON COMBUSTIBLE BUILDINGS, |
| INSTALLATION DETAILS FBC B 1609 |
| DECORATIVE MESH COLUMN ENCLOSURE SHOWN ON A3.1.14 AND |
| OTHER SHEETS, FBC B 602.2 (NON COMBUSTIBLE), 1609 |
| (RESISTANCE TO WIND LOADS), PROVIDE SPEC SHEETS AND |
| PRODUCT APPROVAL OR ENGINEERING TO SHOW COMPLIANCE |
| |
| D. FBC 1207.2, 1207.3, FIELD TESTING FOR STC/IIC WILL |
| BE DONE, LVT ENVIROQUIET II (NOTE: 8" CONCRETE SLABS) |
| WHISPER MAT CS IS PROPOSED BUT DOES NOT HAVE A FLAME |
| SPREAD TEST FOR LVT. PLEASE CONTACT ME IN A FEW WEEKS; |
| AT THIS TIME THE WHISPER MAT CS SPEC SHEET HAS BEEN |
| VOIDED, BUT WE ARE CURRENTLY EVALUATING THIS AND OTHER |
| UNDERLAYMENTS IN THIS APPLICATION. |
| |
| E. THE FOLLOWING ITEMS MAY REQUIRE A DETAIL OR SPEC |
| SHEETS TO BE SUBMITTED SUBJECT TO INSPECTOR'S |
| DISCRETION: |
| FBC B 603, "WOOD SLATS AT ROOF FASCIA" IS SHOWN; |
| PROVIDE SPEC SHEETS AT INSPECTION TO SHOW COMPLIANCE. |
| FBC B 603.1 2-A8.3.3 AND OTHER LOCATIONS, IPE WOOD IS |
| PROPOSED; PROVIDE SPEC SHEETS AT INSPECTION TO SHOW |
| COMPLIANCE. |
| FBC A FAIR HOUSING REQUIREMENT 2 ANSI 4.1-4.3.1, |
| RECEPTION DESK IN RESIDENTS LOBBY TO COMPLY. |
| FBC B 603.1(15), A3.1.11 AND OTHER SHEETS, KRINKLGLAS, |
| SHOWN ON VARIOUS PAGES, TO COMPLY WITH CHAPTER 26 |
| |
| F. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| REQUIRED FOR: |
| LIGHT POLES/SITE LIGHTING |
| SWIMMING POOL |
| FIRE ALARM |
| FIRE SPRINKLER |
| LOW VOLTAGE |
| ACCESS |
| LANDSCAPING |
| IRRIGATION |
| ALL OTHER ITEMS OTHER THAN BMEP |
| |
| G. PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A |
| PDF VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL. |
| |
| H. AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED |
| PRIOR TO C.O. |
| |
| I. SHORING/RESHORE ENGINEERING IS REQUIRED TO BE |
| SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. THE |
| ENGINEERING IS TO BE SUBMITTED, REVIEWED AND ISSUED |
| PRIOR TO CONCRETE POUR. |
| |
| J. A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS |
| REQUIRED TO BE PROVIDED PRIOR TO INSTALLATION. |
| |
| |
| |